1592002750 XH240K GB r1.0 15.06.2004 *

                           

XH240K

1/4

XH240K

TEMPERATURE AND HUMIDITY CONTROLLER

1.

 

GENERAL WARNING

1.1

 

PLEASE READ BEFORE USING THIS MANUAL

 

This manual is part of the product and should be kept near the instrument for easy and quick
reference.

 

The instrument shall not be used for purposes different from those described hereunder. It cannot
be used as a safety device.

 

Check the application limits before proceeding.

1.2

 

 SAFETY PRECAUTIONS

 

Check the supply voltage is correct before connecting the instrument.

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding
sudden temperature changes with high atmospheric humidity to prevent  formation of
condensation

 

Warning: disconnect all electrical connections before any kind of maintenance.

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened.

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell s.r.l.”
(see address) with a detailed description of the fault.

 

Consider the maximum current which can be applied to each relay (see Technical Data).

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from
each other, without crossing or intertwining.

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in
parallel with inductive loads could be useful.

2.

 

GENERAL DESCRIPTION

The 

XH240K

 is microprocessor controller suitable for applications on medium temperature

refrigerating units. It must be connected by means of a two-wire cable (

 1mm) at a distance of

up to 30 meters to the keyboard 

VH620, 100x64

mm format. It controls both humidity and

temperature. It has 4 output relays to control compressor, heating elements , fan and humidifier.
It has 2 analogue inputs: one for temperature control, the other for humidity. There is one digital
input (free contact). An  output allows the user to programme the parameter list with the 

“Hot

Key”.

3.

 

TEMPERATURE REGULATION

The temperature regulation is performed through neutral zone using compressor and heater
output relays.

Set point

OFF

ON

• 

Heating

 output: CUT IN is “SET_TEMP-dbt”, CUT OUT is when the temperature reaches the

set point.
• 

Compressor

 output CUT IN is “ SEdbt”, CUT OUT is when the temperature

reaches the set point.

3.1

 

DEFROST

During the defrost temperature regulation is disabled.. Parameter “

IdF

” controls the interval

between defrost cycles, while its length is controlled by parameter “

MdF

”.

To disable defrost set the MdF parameter to zero.
Humidity regulation, during defrost, depends on the 

Hud 

parameter. With

Hud=no

 humidity regulation is disabled during defrosts.

Hud=yES

 humidity regulation is performed also during defrosts.

4.

 

HUMIDITY REGULATION

The humidity regulation is performed through neutral zone, by humidifying dehumidifying.
Humidity control can be disabled setting the SET_RH to “nu” value. In this case only the
temperature control is perform.

4.1

 

HUMIDIFYING ACTION

The humidifying action is done enabling the humidifier relay when the humidity is lower than the
“SET_RH-dbH” value.
The relay is disable when humidity reaches the set values.

4.2

 

DEHUMIDIFYING ACTION

The dehumidifying action is performed enabling the heating and compressor output together
when humidity is higher than dbH value.

Outputs are disabled when humidity comes back to the SET_RH value.

4.2.1  Relation between cooling, heating and dehumidifying

1.

 

If is simultaneously present a request of cooling (temp>Sdbt) and
dehumidifying (RH > dbH): the cooling action has the priority over the
dehumidifying action: only the compressor relay is energised till the SET_TEMP is
reached at this point also the heating relay is enabled.

2.

 

If is simultaneously present a request of heating (temp< SET_TEMP-dbt) and
dehumidifying (RH > dbH): the dehumidifying action has the priority over the
heating action: both the compressor and the heating relays are energised till the humidity
set is reached at this point only the heating relay is enabled.

5.

 

FANS

The fan control mode is selected by means of the “

FnC

” parameter:

C-n

 = running when a load is on, OFF during the defrost;

C-y

 = running when a load is on, ON during the defrost;

O-n

 = continuous mode, OFF during the defrost;

O-y

 = continuous mode, ON during the defrost;

6.

 

THE DISPLAY

To display and modify target
temperature set point. (SET_TEMP)

To display and modify target humidity
set point (SET_RH); in programming
mode it selects a parameter or confirm
an operation.
In programming mode it browses the
parameter codes or increases the
displayed value.
In programming mode it browses the
parameter codes or decreases the
displayed value.

By holding it pressed for 3s the defrost

is started..

Switch ON and OFF the instrument.

KEY COMBINATIONS

 

+

 

To lock and unlock the keyboard

 

+

To enter the programming mode.

 

+

 

To exit the programming mode.

6.1

 

ICONS AND SYMBOLS

Each LED function is described in the following table.

LED2

LED3

LED4

Temperature Display 

Humidity Display 

LED

MODE

FUNCTION

ON

- ALARM signal

Led 4

ON

- Instrument in stand by.
- In “Pr2” indicates that the parameter is also present in “Pr1”.

ON

°C

ON

The compressor is running

FLASHING

- Anti-short cycle delay enabled

LED 3

ON

The defrost is enabled

LED 3

FLASHING

Drip time in progress

LED 2

FLASHING

Programming Phase (flashing with LED3)

ON

Heating enabled

 (temp)

FLASHING

Temperature Set programming phase