Installation and Operating Instructions
ot
Thermostat probe calibration
0
Pr2
-21
21
P2P
Evaporator probe presence
1
Pr2
oE
Evaporator probe calibration
0
Pr2
-21
21
P3P
Third probe presence
0
Pr2
o3
Third probe calibration
0
Pr2
-21
21
rES
Display resolution
1
Pr2
CF
Temperature measurement unit
1
Pr2
Lod
Display visualization
0
Pr2
dLy
Delay before updating the displayed temperature
0.00
Pr2
CH
Kind of action: heating or cooling
0
Pr2
Con
Compressor ON time with faulty probe
15
Pr2
0
255
CoF
Compressor OFF time with faulty probe
310
Pr2
0
255
tbA
Alarm output disabling by pushing any button
0
Pr2
i2F
Digital input 2 configuration
5
Pr2
i2P
Digital input 2 polarity
0
Pr2
di2
Digital input 2 alarm delay
0
Pr2
0
255
odC
Compressor and fan status when the door is open
0
Pr2
oAA
First output configuration
0
Pr2
oAb
Second output configuration
3
Pr2
AoP
Alarm relay polarity
0
Pr2
dot
Temperature alarm exclusion with door open
20
Pr2
0
255
rrd
Regulation restart with door open alarm
0
Pr2
AP2
Probe selection for condenser temperature
alarms
0
Pr2
AL2
Condenser low temperature alarm
0
Pr2
-67
302
AU2
Condenser high temperature alarm
0
Pr2
-67
302
AH2
Differ. for condenser temp. alarm recovery
1
Pr2
1
45
Ad2
Condenser temperature alarm delay
0
Pr2
dA2
Delay of condenser temper. alarm at start up
0
Pr2
0
720
bLL
Compressor off for condenser low temperature
alarm
0
Pr2
AC2
Compressor off for condenser high temperature
alarm
0
Pr2
HES
Differential for Energy Saving
0
Pr2
-54
54
onF
On/off key configuration
2
Pr2
bEn
Buzzer enabling
1
Pr2
Ptb
Map code
READ ONLY
Pr2
0
655
35
Adr
Serial address
1
Pr2
1
247
SEt
Set point
75
-50
230