Universal-XR
15/17
UXR01212015_REV1.4mm
Installation and Operating Instructions
Hy
Differential
4
Pr1
1
45
LS
Minimum set point value
-50
Pr2
-67
75
US
Maximum set point value
230
Pr2
75
302
AC
Anti-short cycle delay
1
Pr2
0
50
AC1
Second compressor start delay
0
Pr2
0
255
ALP
Probe selection for temperature alarms
0
Pr2
ALC
Temperature alarm configuration
Ab
Pr2
ALU
High temperature alarm
230
Pr1
-50
302
ALL
Low temperature alarm
-50
Pr1
-67
230
AFH
Differential for temperature alarm recovery
1
Pr1
1
45
ALd
Temperature alarm delay
15
Pr2
0
255
dAo
Delay before activating a temperature alarm at
start up
90
Pr2
0
720
odS
Delay before activating outputs at start up
0
Pr2
0
255
CCt
Continuous cycle duration
0
Pr2
0
990
CCS
Set point for continuous cycle
0
Pr2
-67
302
dAF
Defrost delay after fast freezing
2
Pr2
0
255
idF
Interval between defrost cycles
6
Pr1
0
250
dSd
Start defrost delay
0
Pr2
0
255
dFP
Probe selection for first defrost
3
Pr2
MdF
(Maximum) length for first defrost
30
Pr1
0
255
dtE
Defrost termination temperature (first evaporator)
46
Pr1
-67
122
dSP
Probe selection for second defrost
0
Pr2
MdS
(Maximum) length for second defrost
0
Pr2
0
255
dtS
Defrost termination temperature (second
evaporator)
0
Pr2
-67
122
dFd
Display during defrost
3
Pr2
dAd
Max display delay after defrost
10
Pr2
0
255
tdF
Defrost type
0
Pr2
Fdt
Drain down time
2
Pr1
0
255
dPo
First defrost after start-up
0
Pr2
FnC
Fan operating mode
1
Pr2
FSt
Fan stop temperature
46
Pr1
-67
122
Fnd
Fan delay after defrost
5
Pr1
0
255
Fon
Fan on time with compressor off
0
Pr2
0
15
FoF
Fan off time with compressor off
0
Pr2
0
15
FAP
Probe selection for fan management
1
Pr2
FCt
Differential of temperature to force fan activation
5
Pr2
0
90
FSU
Fan management
0
Pr2