1592015620 Quick reference guide iCHILL 200D EVO FW 4.5 rel. 1.0.doc
26/42
16. WIRING CONNECTIONS
16.1 IC205D CONNECTIONS
5 x digital outputs (relays)
Max current on the relay contacts relè 5(2)A 250V
Max current on common line 10A 250V
9 x digital inputs (free of voltage)
8 x analogue inputs:
5 x NTC preobe / PTC probe / digital input
3 x NTC preobe / PTC probe / digital input / pressure transducer 4÷20 mA / pressure
transducer ratio-metric 0÷ 5.0 Volt
4 modulating outputs:
1 x 0 ÷ 10 Volt
2 x 0 ÷ 10.0 Volt or PWM (for modulating condenser fan)
1 x output to connect a remote keyboard (max 2 remote keyboards)
1 x LAN to connect an I/O expansion module (ICX207D)
1 x TTL output for “HotKey 64” (for parameters programming) or for XJ485CX (interface
module for monitoring system)
1 x RS485 output to connect the instrument to a RS485 network (monitoring system) or
XWEB system.