background image

 

IMCB34-E1 

 

3

 

3. WIRING 

3.1 Wiring Cautions 

  For thermocouple input, use the appropriate compensation wire. 
  For RTD input, use low resistance lead wire with no difference in resistance between the three lead wires. 
  To avoid noise induction, keep input signal wire away from instrument power line, load lines and power lines of other electric equipment. 
  For the current input specification, an external resistor (250    0.02 %, 0.25 W or more,  10 ppm/ C) must be connected between the input 

terminals. For external resistor (shunt resistor), use the KD100-55: sold separately (RKC product). If this resistor is installed, close horizontal 
mounting is not possible. 

  Signal connected to Voltage input and Current input shall be low voltage defined as “SELV” circuit per IEC 60950-1. 
  If there is electrical noise in the vicinity of the instrument that could affect operation, use a noise filter. 

Shorten the distance between the twisted power supply wire pitches 
to achieve the most effective noise reduction. 

Always install the noise filter on a grounded panel. Minimize the wiring 
distance  between  the  noise  filter  output  and  the  instrument  power 
supply terminals to achieve the most effective noise reduction. 

-

  Do  not connect  fuses  or  switches  to  the  noise  filter output  wiring  as 

this will reduce the effectiveness of the noise filter. 

  Allow approximately 4 seconds for contact output when the instrument is turned on. Use a delay relay when the output line is used for an 

external interlock circuit. 

  Power supply wiring must be twisted and have a low voltage drop. 
  This instrument with 24 V power supply is not provided with an overcurrent protection device. 

For safety install an overcurrent protection device (such as fuse) with adequate breaking capacity close to the instrument. 

Fuse type:  Time-lag fuse (Approved fuse according IEC60127-2 and/or UL248-14) 

-

 Fuse rating:  Rated current: 0.5 A 

  For an instrument with 24 V power supply input, supply power from "SELV" circuit defined as IEC 60950-1. 
  A suitable power supply  should be considered in end-use equipment.  The power supply  must be in  compliance  with a limited-energy  circuits 

(maximum available current of 8 A). 

  Use the solderless terminal appropriate to the screw size. 

-

 Screw size: 

M3 x 6 

Recommended tightening torque: 0.4 N m [4 kgf cm] 

Specified solderless terminals: 

With isolation 

-

 Applicable wire: 

Solid/twisted wire of 0.25 to 1.65 mm

2

 

  Make sure that during field wiring parts of conductors can not come into contact with adjacent conductive parts. 

 

 

3.2 Terminal Configuration 

 

Alarm output

Power supply

Control output 

Input

 

Communication

NO: Normally open 
NC: Normally closed 

7
8
9

10
11
12

13
14
15
16
17
18

1
2
3
4
5
6

100 to 240V

AC

24V

DC

24V

AC

2

2

1

1

2

1

L

N

L

N

13

14

15

T/R(A)

T/R(B)

SG

RS-485

(Optional)

CT input

 

Current 

transformer input

18

17

CT1

TC

TC input 

11

12

A

B

B

RTD

10

 

RTD input 

11

12

IN

Voltage input 

0 to 5 V DC

1 to 5 V DC

11

12

11

12

Current input

0 to 20 mA DC

4 to 20 mA DC

W, A action types

Relay contact

Voltage pulse

Current

Triac

NO

OUT2

NO

OUT1

3

4

5

6

OUT2

OUT1

3

4

5

6

OUT2

3

4

Triac out

5

6

OUT1

Triac out

Relay contact

Voltage pulse 
Current

Triac

Trigger 

F, D action types 

NC

NO

OUT1

4

5

6

OUT1

6

5

Triac out

OUT1

5

4

OUT1

T2

T1

G

4

6

5

CB100 

* Cautions for Communication terminal wiring   : 

Make sure that lugs or unshielded cables of the communication terminals are not touched to the screw heads, lugs, or unshielded 
cables  of  the  power  supply  terminals  to  prevent  electric  shock  or  instrument  failure.  Use  additional  care  when  two  lugs  are 

screwed to one communication terminal. 

It is recommended that the host computer communication line be isolated from the power supply and earth.

 

External 
resistor

(Optional)

(Optional)

Alarm 1

Alarm 2

NO

ALM1

ALM2

7

8

9

NO

 

 

Power supply

Control output 

NO: Normally open 
NC: Normally closed 

100 to 240V

AC

24V

DC

24V

AC

2

2

1

1

2

1

L

N

L

N

Communication

13

14

15

T/R(A)

T/R(B)

SG

RS-485

Alarm output

Input

TC

TC input 

11

12

A

B

B

RTD

10

RTD input

11

12

IN

Voltage input 

0 to 5 V DC

1 to 5 V DC

11

12

11

12

Current input

0 to 20 mA DC

4 to 20 mA DC

W, A action types

Relay contact

Voltage pulse

Current

Triac

NO

OUT2

NO

OUT1

3

4

5

6

OUT2

OUT1

3

4

5

6

OUT2

3

4

Triac out

5

6

OUT1

Triac out

Relay contact

Voltage pulse 

Current

Triac

Trigger 

F, D action types 

NC

NO

OUT1

4

5

6

OUT1

6

5

Triac out

OUT1

5

4

OUT1

T2

T1

G

4

6

5

CB400 

The terminal arrangement of CB500 is as shown in   
the following diagram, but the terminal configuration   
of CB500 is the same as that of CB400. 

1

2
3
4
5
6
7
8

10
11

9

12

13 
14 
15 
16 
17 
18 

19 

20 

22 
23 

21 

24 

13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6 7 8 9 10 11 12

 

CT input

 

Current

transformer input

24

23

CT1

External 
resistor

(Optional)

(Optional)

(Optional)

Alarm 1

Alarm 2

NO

ALM1

ALM2

7

8

9

NO

 

OUT

Minimize

distance

Instrument

power 

terminals

IN 

Twist these leadwires 

Shorten distance between

pitches 

Instrument power 

Noise filter

 3.2 MIN

 5.5 MAX

4 mm 

Summary of Contents for MHE-02

Page 1: ...INSTALLATION OPERATING AND MAINTENANCE MANUAL for the Mini Water Heater Electric Model MHE 02 440 VAC Supply x 24 VDC Controls Document No KI OM 523 Legacy No 05984 805 Part No KI40026AA...

Page 2: ...Intentionally Blank...

Page 3: ...AC Supply x 24 VDC Controls REV DATE BY CHECK APP COMMENTS 0 31 03 2010 R Carli N Maske R Faustmann First Issue 1 11 06 2010 R Carli N Maske R Faustmann Update as per ECN CT 00276 2 26 10 2012 V Garzo...

Page 4: ...ii Approval Sheet KI OM 523 R2 Intentionally Blank...

Page 5: ...5 1 3 4 Electrical System Detail Control Logic and Component Identification 5 1 3 5 Heater System and Heater Selection 6 1 3 6 Control System 7 CHAPTER 2 INITIAL SET UP 11 2 1 Installation 11 2 1 1 Ge...

Page 6: ...RECOMMENDED SPARE PARTS LIST ACQUISITION FORM 39 B 1 Recommended Spare Parts List Spares Kit KI40026AA KIT 39 B 2 Recommended Spare Parts Not in Spares Kit KI040026AA KIT 41 APPENDIX C SPARES ACQUISI...

Page 7: ...KI OM 523 FILENAME AND PATH EQUIPMENT TYPE Mini Water Heater Electric MHE 02 440V x 24V EQUIPMENT SERIAL NO CUSTOMER VESSEL LOCATION IF KNOWN DATE OF ISSUE IMPORTANT Please quote the above informatio...

Page 8: ...vi Data Sheet KI OM 523 R2 Intentionally Blank...

Page 9: ...document Divex makes no guarantees therefore Misuse of the equipment described in this manual could result in injury It is the responsibility of the user to ensure that the equipment is used and maint...

Page 10: ...viii Disclaimer KI OM 523 R2 Intentionally Blank...

Page 11: ...formation IV CONFIDENTIAL INFORMATION This document is confidential and is the property of Divex It may not be distributed to persons or organizations other than the intended recipient without the pri...

Page 12: ...x Confidential Information KI OM 523 R2 Intentionally Blank...

Page 13: ...y transportation on site accommodation and subsistence expenses Divex may dispatch personnel to perform on site repairs The product specification and warranty terms are subject to alteration without p...

Page 14: ...xii Warranty KI OM 523 R2 Intentionally Blank...

Page 15: ...ph of Temperature Loss vs Umbilical Length 18 Fig 3 2 General Arrangement 20 Fig A 1 MHE 02 General Arrangement Isometric View 35 Fig A 2 MHE 02 General Arrangement Side View 36 Fig A 3 MHE 02 General...

Page 16: ...xiv List of Tables and Figures KI OM 523 R2 Intentionally Blank...

Page 17: ...SCRIPTION The MHE 02 assembly Includes a motor pump heater tank pipework and a control panel These components are mounted into a robust stainless steel frame The system requires a constant supply of s...

Page 18: ...ired temperature rise through the unit would be 36 C The heater selection table shown in Table 3 1 indicates that heater banks 1 2 and 3 should be used for the required temperature rise through the un...

Page 19: ...ing hand valves on the inlet and outlet of each filter Only one filter should be used under normal operation with the other on standby and ready to be put into operation These filters clean input wate...

Page 20: ...e same way as the automatic control valve and is provided to control outlet temperature if automatic control is inactive The pump supply is directly coupled to the level control tank The pump is a pos...

Page 21: ...LOGIC AND COMPONENT IDENTIFICATION The main isolator located in the electrical panel is used to switch the main power of the unit on and off As detailed in the heater power circuit in APPENDIX D power...

Page 22: ...equential switching of the banks reducing the instantaneous load on the supply As heater banks have separate control circuits and protection the failure of any single bank of heaters will not effect t...

Page 23: ...he amount of fluid dumped is controlled by an electronic controller that operates the actuator on the control valve The amount to which the valve is opened is determined by the controller based on fee...

Page 24: ...eater Bank On L2 L4 LED indication of heater bank power on Supply to heater contactor coil Run Light White Control Power On L5 LED indicating 24 VDC power to control circuit Fault Light Red Pump Trip...

Page 25: ...ontact of the float switch This arrangement is used to reduce nuisance faults attributed to level switch vibration or bouncing The normally open contact R2 1 is used in the safety circuit to remove po...

Page 26: ...latched with a twist release Switch Fault Reset S6 The fault rest switch unlatches the over temperature and low level fault interlock circuits and allows normal function Switch Float FS The float swit...

Page 27: ...lative 3 4 NPT penetrator of the unit Flexible hoses with suitable connections may also be used to facilitate the integration of the unit into an installation The maximum acceptable water inlet pressu...

Page 28: ...m should be fitted to the bottom right hand side of the stainless steel electrical enclosure The mains power cable should be installed through a suitable gland and correctly grounded to the armour Mai...

Page 29: ...n the heater tank 7 To complete priming shut the vent valve and supply valve s 2 2 2 START UP AND FUNCTION CHECK After installation is complete the MHE 02 must be thoroughly checked prior to being put...

Page 30: ...roller display indicates the Measured Value PV Set Value SV and run indication for the Auto tuning AT Output 1 and 2 OUT1 OUT2 and Alarm 1 and 2 ALM1 ALM2 The display is used during setting to show pa...

Page 31: ...e Table 3 1 mounted on the panel door to determine which heater banks should be used to achieve calculated temperature rise Switch on the required heater bank switches sequentially Refer to trouble sh...

Page 32: ...selection and supplies it will deliver water heated to within 1 C of the controller set point Confirm that the unit controls the process as specified CAUTION SYSTEM FLUSHING When the system is not in...

Page 33: ...e determining this capacity Approximate length of umbilical in water LU Approximate operating temperature of fluid desired at bottom Tb Inlet water temperature Tin Step 1 Determine total outlet temper...

Page 34: ...d To determine the required temperature rise Trise through the unit subtract the inlet temperature Tin from the required total outlet temperature calculated in Step 1 Step 3 Heater bank selection Afte...

Page 35: ...0 5 0 9 13 5 5 10 9 18 27 0 10 15 18 27 40 5 15 22 27 39 54 0 22 29 39 51 67 5 29 35 51 62 81 0 35 42 62 74 94 5 IMPORTANT The required temperature rise shown in Table 3 1 indicates the differential b...

Page 36: ...d switches for heater bank selection The MHE 02 is also equipped with several analogue gauges displaying fluid temperature and pressure throughout the system The layout of the operator interface is sh...

Page 37: ...n optimum performance 3 Check inlet water temperature and determine required temperature settings See Section 3 1 4 Press the pump start button The pump should start and no the fault indicator lights...

Page 38: ...uate flushing of the system pipe work with fresh water 5 Shut fresh water valve off Open the drain valve and tank vent valve and allow water to drain from the system IMPORTANT During the flushing proc...

Page 39: ...rs The inlet water filter elements should be checked following the first few hours of operation in a new installation and after long periods spent out of service Under normal working conditions the fi...

Page 40: ...he CAT pump on the MHE 02 unit should be carried out by an approved CAT service agent or Divex regional office Filter Inspection The most common cause of low pump pressure is damage due to foreign mat...

Page 41: ...r 7 to 155 bar Inlet Pressure Range 1 4 to 4 bar 1 4 to 4 bar Speed Maximum Allowable 767 rev min 1150 rev min Max Maximum Fluid Temperature 71 C 71 C Crankcase Capacity 1 26 ltr 1 26 ltr Inlet Ports...

Page 42: ...26 Chapter 4 KI OM 523 R2 Intentionally Blank...

Page 43: ...f valve check for worn and dirty valve seats Replace worn parts Inlet filter clogged or improperly size Clean Use 50 micron filter element Check more frequently Worn packing Abrasives in pumped fluid...

Page 44: ...seals Oil leaking at the rear portion of the crankcase Damaged or improperly installed oil gauge or crankcase rear cover o ring and drain plug o ring Replace oil gauge or cover o ring and drain plug...

Page 45: ...expected As the system s output depends upon the flow resistance if there is low resistance the pressure will be low but the flow rate will be maintained Water will not heat Circuit breakers tripped...

Page 46: ...gulator malfunction Clean regulator and reassemble If unit will not regulate pressure on pump to between 2 5 and 4 bar replace regulator EMERGENCY CORRECTIVE ACTION Bypassing the regulator will allow...

Page 47: ...justment Readjust over temperature controls whichever one is turning the system off if temperature of water is low Faulty over temperature switch Determine which over temperature switch is open circui...

Page 48: ...ghts are on If any fault lights are on remedy fault Example low water Water to system shut off and float switch will open thus keeping system off Main power switch not turned on Turn switch on Control...

Page 49: ...out fault light Replace Faulty fault relays R1 and R2 Replace No 24 VDC control power Control transformer faulty Check output of power supply If it is not 24 V on the feed with 380 V on the supply re...

Page 50: ...34 Chapter 5 KI OM 523 R2 Intentionally Blank...

Page 51: ...2 HP Hose Assembly DO 06035 3 Ball Valve NPT Heater Tank Bleed Valve XV500P 8 02 4 Ball Valve Brass Fresh Water Inlet Shut off Valve XV500P 12 02 5 Check Valve DO 02780 6 Sea Water In Manifold DO 059...

Page 52: ...2 02 13 Ball Valve NPT Filter Isolation Valves XV500P 12 02 14 Filter Housing NPT With 50 Filter Element DSA No DO 04793 DO 04768 15 Motor 4kW 4 pole DO 06051 16 Accumulator CAT S S DO 02724 17 Pump C...

Page 53: ...63BB02QJ2A 23 Sea Water Inlet Connection NPT 24 Gauge Temp 0 100 C Swivel Brkt Inlet Water Temperature Gauge DO 06068 25 Gauge Pressure 0 100 bar Back Entry Outlet Water Pressure Gauge PBBV63BB02QJ3A...

Page 54: ...2889 32 Emergency Stop DO 03260 DO 02891 DO 04827 33 Start Stop Switch Pump DO 04823 DO 02891 DO 02889 DO 06033 34 Heater Bank Rotary Selector Switchs 3 off DO 06031 DO 02889 DO 06032 35 Belt SPB x 12...

Page 55: ...lve Pressure Regulator 1 DO 02723 Item 18 Fig A 2 Valve 2 Way Proportional Actuated NPT 1 DO 02788 Item 19 Fig A 2 Gauge Temp 0 100 CDial Every Angle 1 DO 06068 Item 21 24 Fig A 2 Gauge Pressure 0 10...

Page 56: ...02304 Valve Globe NPT Brass 1 DO 03326 Oil Divex CAT Pump Lubeb litres 0 5 DO 03764 Circuit Breaker Miniature 50A 6kA 3pole 2 DO 05934 Circuit Breaker Miniature 20A 6kA 3pole 2 DO 05932 Circuit Breake...

Page 57: ...CZ121 DO 05957 Item 8 Fig A 1 Manifold MHE 2 Dump CZ121 DO 05956 Item 9 Fig A 1 Filter Housing NPT DO 04768 Item 14 Fig A 2 Actuator E Stop Latching Mushroom RED DO 03260 Item 32 Fig A 3 Legend Emerge...

Page 58: ...42 APPENDIX B KI OM 523 R2 Intentionally Blank...

Page 59: ...V500P 12 02 Oil Divex CAT Pump Lubeb litres DO 03764 Valve Check Brass Euro Stop DO 02780 Circuit Breaker Minia ture 50A 6kA 3pole DO 05934 Valve Pressure Reduc ing Brass DO 02359 Circuit Breaker Mini...

Page 60: ...r Housing NPT DO 04768 Indicator LED Module White 18 30 VAC DC DO 06033 Actuator E Stop Latch ing Mushroom RED DO 03260 Switch Selector Illumi nated GRN DO 06031 Legend Emergency Stop DO 04827 Indicat...

Page 61: ...45 KI OM 523 R2 APPENDIX D APPENDIX D WIRING DIAGRAMS...

Page 62: ......

Page 63: ......

Page 64: ......

Page 65: ...46 KI OM 523 R2 APPENDIX E APPENDIX E PIPING AND FLOW SCHEMATIC...

Page 66: ......

Page 67: ...47 KI OM 523 R2 APPENDIX F APPENDIX F RKC CB100 DIGITAL CONTROLLER MANUAL...

Page 68: ...ntenance is required for safe and proper operation of this instrument Some components have a limited service life or characteristics that change over time Every effort has been made to ensure accuracy...

Page 69: ...a case loosen the screw once and tighten it again until the instrument is firmly fixed 6 The other mounting bracket should be installed in the same way as described in 3 to 5 When the instrument is m...

Page 70: ...ire of 0 25 to 1 65 mm2 Make sure that during field wiring parts of conductors can not come into contact with adjacent conductive parts 3 2 Terminal Configuration Alarm output Power supply Control out...

Page 71: ...0 Voltage 0 to 5 V DC 1 to 5 V DC 0 to 10 V DC Z 1010 Current 0 to 20 mA DC 4 to 20 mA DC Sampling cycle 0 5 seconds Input range Refer to Input range table Control method PID control ON OFF P PI or PD...

Page 72: ...Input type symbol Input range high Input range low Automatically Power ON PV SV Display Mode The controller will display the Measured value PV and the Set value SV The controller can be switched to RU...

Page 73: ...or PID control is performed Heat Cool PID action Proportional band setting on the heat side ON OFF action differential gap TC RTD inputs 2 0 2 C F Voltage Current inputs 0 2 of Input span TC RTD input...

Page 74: ...should be lengthened If setting time is not correct the LBA will malfunction by turning on or off at inappropriate times or not turning on at all 3 LBA deadband function The LBA may malfunction due t...

Page 75: ...y returns to PID control Requirements for AT cancellation The Autotuning is canceled if any of the following conditions exist When the Set value SV is changed When the PV bias value is changed When th...

Page 76: ...limiter high Refer to P 11 0001 SLL Setting limiter low Refer to P 11 PGdP Decimal point position Refer to P 11 7 2 Exit Initialization Mode When any parameter setting is changed in the Initializatio...

Page 77: ...function is not provided with the instrument when shipped from the factory no alarm output is available by changing SL4 and or SL5 SL4 is set to 0000 in the following cases When the instrument does no...

Page 78: ...C 0 to SLH C SLL to 3308 F 0 to SLH F TC E SLL to 1000 C 0 to SLH C SLL to 1832 F 0 to SLH F N SLL to 1300 C 0 to SLH C SLL to 2372 F 0 to SLH F T SLL to 400 0 C 199 9 to SLH C SLL to 752 0 F 199 9 t...

Page 79: ...iring take the following steps Apply pressure very carefully when removing internal assembly to avoid damage to the frame To conform to IEC61010 1 requirements for protection from electric shock the i...

Page 80: ...48 KI OM 523 R2 APPENDIX G APPENDIX G BELIMO CONTROL VALVE MANUAL...

Page 81: ......

Page 82: ......

Page 83: ......

Page 84: ......

Page 85: ......

Page 86: ......

Page 87: ...49 KI OM 523 R2 APPENDIX H APPENDIX H WATER PRESSURE REDUCING VALVE...

Page 88: ...I...

Page 89: ...bar bar bar bar...

Page 90: ......

Page 91: ...Nominal flow rates...

Page 92: ......

Page 93: ......

Page 94: ...50 KI OM 523 R2 APPENDIX I APPENDIX I CAT TRIPLEX PUMP MANUAL MODEL 1050...

Page 95: ......

Page 96: ......

Page 97: ......

Page 98: ......

Page 99: ......

Page 100: ......

Page 101: ......

Page 102: ......

Page 103: ......

Page 104: ......

Page 105: ......

Page 106: ......

Page 107: ...51 KI OM 523 R2 APPENDIX J APPENDIX J PULSATION DAMPENER...

Page 108: ......

Page 109: ......

Page 110: ...52 KI OM 523 R2 APPENDIX K APPENDIX K PRESSURE REGULATOR...

Page 111: ......

Page 112: ......

Page 113: ......

Page 114: ......

Page 115: ...53 KI OM 523 R2 APPENDIX L APPENDIX L FLOAT SWITCH...

Page 116: ......

Page 117: ......

Page 118: ......

Page 119: ......

Reviews: