background image

21

!

10.5 Level Set Point

10.6.1 Reprogramming Water Level Sensor - Loading Program

10.6.2 Regular Operation: To Start Typhoon Central Dust Collector

10.6.3 Regular Operation: To Stop Typhoon Central Dust Collector

10.7.1 Reprogramming Water Level Sensor - Loading Program

This should only be done in consultation with an authorized Diversitech technician! 
The following steps have been done at the factory and should not need adjustment.

CAUTION

Initial Set Point Adjustment if the PLC has been factory reset 

 

• At the initial start-up, the set point will be at 0.

 

• To set the running water level, the machine has to be powered and “on”. Once on, the button #1 can be pressed to enter the manual set 

point entry. Then, use the button #2 and #3 to modify the set point value. If no key is pressed within 5 seconds, the interface will go back to 
the main screen. The other way would be to fill the machine to the desired level (start between 7 to 7.5 inches of water) and then press the 
button #4 for 5 seconds to teach the set point.

 

• The machine is ready to start.

 

• Since the water level has to be higher while stopped, the running set point has to be set once the water has reached turbulent levels. To set 

the “Running Set Point” press button 4 for 5 seconds or until the display shows the current level=running level. Note the refill sequence has 
been set to start when the current level is 4 below the running level for at least 30 seconds.

Level alarms:

 

• To set the level upper limit, the button #2 can be pressed. Then, use the button #2 and #3 to modify the set point value. If no key is pressed 

within 5 seconds, the interface will go back to the main screen.

 

• To set the level lower limit, the button #3 can be pressed. Then, use the button #2 and #3 to modify the set point value. If no key is pressed 

within 5 seconds, the interface will go back to the main screen.

Be certain the drain valve in the Typhoon Central Dust Collector hopper is closed. 
Open the Fill Valve and add water until it reaches a point 2 inches below the running level in the water level control box glass sight. This level is 
marked on the outside of the control box on the glass sight.
When filling for the first time:

 

• First bring water level to the entering edge of the impeller, see Figure 1, and check that the Typhoon Central Dust Collector was properly 

leveled during erection. 

Pour one gallon of water down the control box drain pipe to make an air seal at the bottom of the pipe. 
Close control box cover so the ultrasonic sensor can read the water level.

Check the control box cover and be certain it is tight. Check water supply valve is open. 
Press start button for the Typhoon Central Dust Collector. Solenoid valve in the water supply line should be interlocked to the water level sensor to 
open if water is required and will automatically fill the system to the correct water level. Once the correct water level is achieved the blower will start.

Press the stop button for the Typhoon Central Dust Collector exhauster. The solenoid valve in the water supply should be interlocked to close.

Load program if it isn’t already loaded

1.  Push menu/ok key
2.  Select stop program using up down keys
3.  Push menu/ok
4.  Push menu/ok button and scroll to transfer
5.  Press menu/okPush menu/ok key

Summary of Contents for Typhoon TY-10000

Page 1: ...intenance Manual TYPHOON CENTRAL DUST COLLECTOR Visit our Website for more information on this product www diversitech air com www diversitech ca 1200 55th Avenue Montreal Quebec H8T 3J8 Tel 1 800 361...

Page 2: ...rk Installation 18 SECTION 9 WATER LEVEL CONTROL OPTIONS 19 SECTION 10 START UP OPERATION 19 10 1 Principles of Operation 19 10 2 Controls 19 10 3 Water Level Monitoring 20 10 4 Alarms 20 10 5 Level S...

Page 3: ...and comply with NFPA 654 Standard for the Prevention of Fire and Dust Explosions from the Manufacturing Processing and Handling of Combustible Particulate Solids and those other documents referenced t...

Page 4: ...r incorporates a fan which is close coupled and installed on top of the Typhoon Central Dust Collector or installed separately typically ground mounted and ducted to the outlet of the Typhoon Central...

Page 5: ...non metallic materials that may not present an explosion hazard As mentioned the Typhoon Central Dust Collector is primarily particularly effective for the collection of dust generated by the working...

Page 6: ...he make up water connection or by electrical controls that automatically add water as needed to compensate for evaporation and water lost as the collected dust is removed from the unit The Diversitech...

Page 7: ...the load and strapping it to the handling device Care shall be taken to ensure that the equipment is not dropped or subjected to any impact loads Any missing goods should be noted on the delivery rece...

Page 8: ...ppropriate hoisting procedure should be followed according to 5 3 Rigging and Hoisting Instructions 5 6 Middle Section Hoisting Hoisting must be done from the hoist mounts Appropriate hoisting procedu...

Page 9: ...Appropriate hoisting procedure should be followed according to 5 3 Rigging and Hoisting Instructions 5 8 Motor Blower Hoisting Hoisting must be done from the hoist mounts Appropriate hoisting procedur...

Page 10: ...ations and anchor bolts When locating the Typhoon Central Dust Collector the design engineer shall consider the many factors associated with site selection including but not limited to seismic design...

Page 11: ...Top section Blower and Motor assembly 8 2 Foundation Installation and Levelling Prepare the foundation by drilling anchor bolt holes according to the supplied dimensional drawings Install the Typhoon...

Page 12: ...hoisting instructions from Section 6 Field assembly of these sections will be as follows If the baffles of the middle section were shipped separately they will need to be installed prior to mounting...

Page 13: ...flange to create a gasket with the middle section Lower the middle section carefully onto the flange of the hopper section watching for interference between intermediate sheets and baffles Set the cle...

Page 14: ...g the flange between the Typhoon Central Dust Collector middle section and the clean air transition section Locate the middle section top flange and wipe clean Place sealant tape or a thick constant b...

Page 15: ...er and motor can be installed As previously noted see section 8 3 the motor and blower supplied for Typhoon Central Dust Collector ships separately for installation at the jobsite With the clean air s...

Page 16: ...ill be provided with the Typhoon Central Dust Collector and will need to be installed on site Connect water inlet L piping Connect the water inlet solenoid Connect the blue pressure hose to the water...

Page 17: ...e and green wires in accordance with wiring diagram Run water level sensor wire cable to the control box and see section 8 8 for electrical connection Secure the electrical cable to body with cable cl...

Page 18: ...yphoon Central Dust Collector to the customer s drain line or sewer The customer s drain or sewer line MUST be equal to or larger in size to the drain from the Typhoon Central Dust Collector For the f...

Page 19: ...uct is designed to capture potentially combustible dust particulate from certain industrial applications using a wet filtration process When operating air and dust is drawn into the table passes throu...

Page 20: ...el will be heard When one of these alarms is present the machine will lock down and will not allow to be started Motor Overload if the main motor overload is tripped The alarm will remain until the si...

Page 21: ...3 to modify the set point value If no key is pressed within 5 seconds the interface will go back to the main screen To set the level lower limit the button 3 can be pressed Then use the button 2 and 3...

Page 22: ...cket within 20 seconds 8 Wait until the sensor flashes and changes color 9 Reinstall probe on sensor box 1 Press button 2 2 Using up down keys set the alarm to 95 3 Wait 5 seconds for the reading to b...

Page 23: ...e in your application turn the unit ON and perform a function test To do so 1 Turn switch to ON position 2 LOOK Is the unit level stable and that nothing is obstructing the extraction path Is there ad...

Page 24: ...Water Level Control Box see Section 11 2 Pre Use Checklist Every 1 Month or Specific Cleaning Cycle Exchange Water 1 Remove the water using the drain outlet considering 2 Drained material should be k...

Page 25: ...he static pressure directly upstream of the inlet of the Typhoon Central Dust Collector from the static pressure directly downstream of the exhaust plenum between the Typhoon Central Dust Collector an...

Page 26: ...26 12 4 Troubleshooting Procedure...

Page 27: ...maintenance on unit including filter inspection The input power to this unit is high voltage and touching any live electrical parts can cause fatal shocks or severe burns Do not touch live electrical...

Page 28: ...bicolor LED D rapidly flashes green 5 Releases the button The bicolor LED continues to flash green 6 Within 30s insert an object into position 1 then push and release the setup button The bicolor LED...

Page 29: ...29 NOTES...

Page 30: ...are integrated with any products equipment units connections and or systems of a third party Third Party Products we hereby expressly exclude all of the following warranties express or implied namely...

Page 31: ...Order is for a customized product including without limitation any custom engineered product and b an event set forth at Section 5 2 hereof occurs you will be responsible for payment of the entire amo...

Page 32: ...An Absolent Group Company 1200 55th Avenue Montreal Quebec H8T 3J8 Email info diversitech ca For full product support visit our website https bit ly 2P6CGBX Scan above on mobile...

Reviews: