background image

L1

N1

IN

L1

N1

OUT

L2

N2

IN

L2

N2

OUT

L3

N3

IN

L3

N3

OUT

L4

N4

IN

L4

N4

OUT

EARTH

L5

N5

IN

L5

N5

OUT

L6

N6

IN

L6

N6

OUT

L9

N9

IN

L9

N1

OUT

L10

IN

N10

L10

OUT

N10

L7

N7

IN

L7

N7

OUT

L8

N8

IN

L8

N8

OUT

L11

IN

N11

L11

OUT

N11

L12

IN

N12

L12

OUT

N12

NO   C   NC

NO   C   NC

TB1

TB2

SWI00

C31

C32

BUZZER

+

-

NO         C          NC

DRY CONTACT

(+)

(-)

LOAD: 120VAC, 1AMP (MAX)

                30VDC, 2AMP (MAX)

EXAMPLE MONITORING CIRCUIT

DRY CONTACT CIRCUIT INFORMATION

           DTK-DF120S12

         (Wiring Diagram)

EARTH Grounding Point:

This grounds the board 

to the chassis.

Use 12 AWG Str, 

Cu only, 3/8” strip.

20 in-lb torque

Toggle Switch:

Center = Normal

Bypass = Left or Right

Multi-Position

Grounding Buss

Load Side

Multi-Position

Grounding Buss

Supply Side

Power Lugs:

Use 12 AWG Str, 

Cu only, 3/8” strip.

20 in-lb torque

240VAC Input/Output

See *NOTE below.

*NOTE: Best practice dictates the use of separate conduit feeds to 

isolate the unprotected “IN” wiring from the protected “OUT” wiring!

Summary of Contents for DTK-DF120S12

Page 1: ...ker rated 120 volts minimum Convient a des circuits produisant au plus 10 000 A eff WARNING SHOCK HAZARD DO NOT OPEN AVERTISSEMENT RISQUE DE CHOC NE PAS OUVRIR C U R US DITEK Surge Protection MODULE STATUS DTK DF120M 120VAC R ENERGIZED GROUNDED GOOD REPLACE MADE IN USA DEFLECTOR SERIES Pat www diteksurgeprotection com patents Model DTK DF120M SPD TYPE 2CA Electrical Ratings 120VAC 20A 50 60 Hz Sin...

Page 2: ...DTK DF120S12 User Guide THIS PAGE LEFT INTENTIONALLY BLANK ...

Page 3: ...arizing keys insure that the correct voltage module will mate with its corresponding base WARNING When the DTK 120M module has gone end of life or is missing the base is susceptible to damage from surge energy Make sure you always have a spare module available No substitutions shall be permitted DITEK Surge Protection MODULE STATUS DTK DF120M 120VAC R ENERGIZED GROUNDED GOOD REPLACE MADE IN USA DE...

Page 4: ...the enclosure 5 Connect the Neutral white conductor supply wire from the distribution panel to the NEUTRAL terminal at the N1 IN lug 6 Connect the Phase black conductor supply wire from the distribution panel to the Phase terminal at the L1 IN lug Note Circuit 1 must be connected first The diagnostic circuits get their power from this input 7 Connect the Neutral white conductor for the connected l...

Page 5: ...XAMPLE MONITORING CIRCUIT DRY CONTACT CIRCUIT INFORMATION DTK DF120S12 Wiring Diagram EARTH Grounding Point This grounds the board to the chassis Use 12 AWG Str Cu only 3 8 strip 20 in lb torque Toggle Switch Center Normal Bypass Left or Right Multi Position Grounding Buss Load Side Multi Position Grounding Buss Supply Side Power Lugs Use 12 AWG Str Cu only 3 8 strip 20 in lb torque 240VAC Input O...

Page 6: ...uit breaker rated 120 volts minimum Convient a des circuits produisant au plus 10 000 A eff WARNING SHOCK HAZARD DO NOT OPEN AVERTISSEMENT RISQUE DE CHOC NE PAS OUVRIR C U R US DITEK Surge Protection MODULE STATUS DTK DF120M 120VAC R ENERGIZED GROUNDED GOOD REPLACE MADE IN USA DEFLECTOR SERIES Pat www diteksurgeprotection com patents Model DTK DF120M SPD TYPE 2CA Electrical Ratings 120VAC 20A 50 6...

Reviews: