DTK-DF120S12 (12 Circuit 120VAC 20A Series Surge Protective Device)

CAUTION:  Risk  of  Electric  Shock-Only  intended  for installation in accordance 

with National Electric Code, ANSI/NFPA-70, Article 398.

Warning: 

Turn  power  off  at  the  main circuit  breaker  panel  before beginning install.

Note:  Connect  this  device in series between the 120VAC power supply and the loads 

that require protection.   Use 12 AWG Stranded,  Cu only conductors with  a  3/8”  strip 

length when terminating the wires at the power lugs.  The conductors used  to connect 

the SPD, to the supply or buss and to ground, shall not be any longer than necessary 

and shall avoid unnecessary bends.

1. Remove (4) nylon screws securing the safety barrier, save screws. 

2. Remove safety barrier.

3. Connect a Ground (green or bare conductor) from the EARTH terminal at the bottom 

of the board to the multi-position grounding buss located at the bottom of the enclosure.

4. Connect the Grounds, (green or bare conductors) from the distribution panel to the 

multi-position grounding buss located at the top of the enclosure.

5. Connect the Neutral (white conductor) supply wire from the distribution panel to the 

NEUTRAL terminal at the 

N1 IN

 lug. 

6. Connect the Phase (black conductor) supply wire from the distribution panel  to the 

Phase terminal at the 

L1 IN

 lug.

Note: Circuit 1 must be connected first. The diagnostic circuits get their power from 

this input.

7. Connect the Neutral (white conductor) for the connected load to the 

N1 OUT

 lug. 

8. Connect the Phase (black conductor) for the connected load to the 

L1 OUT

 lug.

9. Connect the Grounds, (green or bare conductors) for the connected loads to the 

multi-position grounding buss located at the bottom of the enclosure.

10. Repeat the above steps for circuits 2 through 12

Note: Tightening torque for the 120VAC power connections is 20 in-lb.

11. Use 2” conduit fittings for the AC circuits and a 3/4” conduit fitting for dry contacts.

Best practice dictates the use of separate conduit feeds to isolate the unprotected “IN” 

wiring from protected “OUT” wiring  

12. After all connections have been made and no hazards exist, replace safety barrier 

and secure with screws. 

USE ONLY THE NYLON SCREWS PROVIDED! 

13. Insert DTK-DF120M surge modules, starting with circuit 1, then restore power.

L1

N1

IN

L1

N1

OUT

L2

N2

IN

L2

N2

OUT

Summary of Contents for DTK-DF120S12

Page 1: ...ker rated 120 volts minimum Convient a des circuits produisant au plus 10 000 A eff WARNING SHOCK HAZARD DO NOT OPEN AVERTISSEMENT RISQUE DE CHOC NE PAS OUVRIR C U R US DITEK Surge Protection MODULE STATUS DTK DF120M 120VAC R ENERGIZED GROUNDED GOOD REPLACE MADE IN USA DEFLECTOR SERIES Pat www diteksurgeprotection com patents Model DTK DF120M SPD TYPE 2CA Electrical Ratings 120VAC 20A 50 60 Hz Sin...

Page 2: ...DTK DF120S12 User Guide THIS PAGE LEFT INTENTIONALLY BLANK ...

Page 3: ...arizing keys insure that the correct voltage module will mate with its corresponding base WARNING When the DTK 120M module has gone end of life or is missing the base is susceptible to damage from surge energy Make sure you always have a spare module available No substitutions shall be permitted DITEK Surge Protection MODULE STATUS DTK DF120M 120VAC R ENERGIZED GROUNDED GOOD REPLACE MADE IN USA DE...

Page 4: ...the enclosure 5 Connect the Neutral white conductor supply wire from the distribution panel to the NEUTRAL terminal at the N1 IN lug 6 Connect the Phase black conductor supply wire from the distribution panel to the Phase terminal at the L1 IN lug Note Circuit 1 must be connected first The diagnostic circuits get their power from this input 7 Connect the Neutral white conductor for the connected l...

Page 5: ...XAMPLE MONITORING CIRCUIT DRY CONTACT CIRCUIT INFORMATION DTK DF120S12 Wiring Diagram EARTH Grounding Point This grounds the board to the chassis Use 12 AWG Str Cu only 3 8 strip 20 in lb torque Toggle Switch Center Normal Bypass Left or Right Multi Position Grounding Buss Load Side Multi Position Grounding Buss Supply Side Power Lugs Use 12 AWG Str Cu only 3 8 strip 20 in lb torque 240VAC Input O...

Page 6: ...uit breaker rated 120 volts minimum Convient a des circuits produisant au plus 10 000 A eff WARNING SHOCK HAZARD DO NOT OPEN AVERTISSEMENT RISQUE DE CHOC NE PAS OUVRIR C U R US DITEK Surge Protection MODULE STATUS DTK DF120M 120VAC R ENERGIZED GROUNDED GOOD REPLACE MADE IN USA DEFLECTOR SERIES Pat www diteksurgeprotection com patents Model DTK DF120M SPD TYPE 2CA Electrical Ratings 120VAC 20A 50 6...

Reviews: