Output Wiring

Before  connecting  an  output  device  (actuator,  relay,  etc.)  to  the  controller,  refer  to  the  datasheet  and  installation
guide of the equipment manufacturer.

£

For a wire length less than 75’ (23m) long, either a shielded or unshielded 18AWG wire may be used.

£

For a wire length up to 200’ (61m) long, a shielded 18AWG wire is recommended.

£

The shield of the wire should be grounded on the controller side and the shield length should be kept as short
as possible.

£

For relay outputs (DOx); select appropriately-sized wiring suitable to the current load.

£

To measure the state of a triac output, an external load must be connected.

Table 3 shows the ECL-203, ECL-300, ECL-400, and ECL-600 Series controller Output and Jumper support. Table 4 shows the available output wiring
methods.

Controller

Digital (Triac) Outputs

Universal Outputs

Jumper

0 to 10VDC/0 to 20mA

ECL‑203

5

3

ECL‑300

0

8

ECL‑4x0 Series

0

12

ECL‑4x3 Series

8

4

ECL‑600 Series

0

12

Table 3: Controller Output Support

Control Output Type

Output Designation

Output Connection Diagram

£

Discrete 0 or 12VDC digital, Pulse, or PWM output controlling
a  12VDC  relay.  Maximum  60  mA  (minimum  load  resistance
200Ω).

UOx

From 

Digital 

Output

12VDC Relay

A1

A2

UOx

COM

£

Current 0 to 20mA universal output & jumper configuration

£

For ECL-300, ECL-400, and ECL-600 Series only

£

For jumper location, see 

Jumper Identification and Configura-

tion [pg. 6]

.

UOx

0-20mA

Common

From Digital-To-

Analog Output

UOx

COM

JUMPER

SETTING

0-10V

0-20mA

£

Linear 0 to 10VDC digital to analog output.

UOx

0-10V

Common

From Digital-

To-Analog 

Output

UOx

COM

£

0 to 10VDC voltage output controlling an analog actuator that
is powered by an external 24VAC power source.

UOx

0-10V

~ or +

From Digital-

To-Analog 

Output

UOx

COM

Actuator

or -

24VAC

£

24VAC  externally-powered  triac  output  controlling  a  floating
actuator

1

.

£

Ensure that the external power supply is grounded as shown.

DOx

Actuator

~

~

24VAC

DOy

Cx

DOx

Cy

£

24VAC controller-powered triac output controlling a relay

1

 with

line and neutral switching.

£

Ensure  that  the  transformer’s  secondary  winding  is  grounded
as shown.

DOx

DOx

Cx

24VAC Relay

A2

A1

      Transformer

24VAC

24VCOM

AC

Electrical 
System Ground

Fuse: 4A Max.

Fast Acting

Controller

24VAC

Load

DOx

Cx

24VAC Relay

A2

A1

      Transformer

24VAC

24VCOM

AC

Electrical 
System Ground

Fuse: 4A Max.

Fast Acting

Controller

24VAC

Load

Line Switching

Neutral Switching

Summary of Contents for LonWorks ECL-203 Series

Page 1: ...of the device pay special attention to the following recommendations It is recommended that the controller s be kept at room temperature for at least 24 hours before installation to allow any condensa...

Page 2: ...e Hardware Installation Guide Alternating Current Direct Current General Wiring Recommendations Risk of Electric Shock Turn off power before any kind of servicing to avoid electric shock All wiring mu...

Page 3: ...3 16 Controller Dimensions Components Figure 2 Rear view of large enclosure Figure 3 Rear view of small enclosure Figure 4 Side view of large and small enclosure...

Page 4: ...orientation must be horizontal with controller s back attached to a vertical wall surface Figure 5 Permitted Mounting Positions DIN Rail Mounted Installation 1 Ensure the DIN rail is properly mounted...

Page 5: ...the secondary side of the transformer Connecting the power source to Electrical System Ground is not a requirement for proper system operation However it is good installation practice to do so in ord...

Page 6: ...e 0 20 mA Enable LONWORKS Network Board Net to Subnet Settings Enabled Disabled Figure 9 ECL 300 Controller Jumper Locations Factory default positions LONWORKS Network Board Universal Outputs UO 0 10V...

Page 7: ...6 Table 1 Controller Input Support Sensor Input Type Input Connection Diagram Dry Contact input UIx COM To Digital Input Digital Dry Contact NO NC RTD input for example 1000 Thermistor Input for examp...

Page 8: ...24VAC Voltage input used with a 0 to 10VDC or 0 to 5VDC sensor powered by its own power source 0 10V Sensor UIx COM To Analog To Digital Converter Slow Pulse Internal supply 2 wire pulse meter for ECL...

Page 9: ...WM output controlling a 12VDC relay Maximum 60 mA minimum load resistance 200 UOx From Digital Output 12VDC Relay A1 A2 UOx COM Current 0 to 20mA universal output jumper configuration For ECL 300 ECL...

Page 10: ...e Protect the controller s connector from being pulled on when a cable to the Allure Series is connected Create a strain relief by looping the cable and attaching it to a solid object with a nylon tie...

Page 11: ...o the Troubleshooting Guide The Cat5e cable length is restricted by the maximum allowable subnetwork bus length see the Allure EC Smart Vue Hardware Installation Guide for more information Controller...

Page 12: ...sed to relieve tension on the wiring and conceal the controllers wire terminals Strain reliefs and terminal block covers are optional and are sold as peripherals Prior to connecting all wires it is re...

Page 13: ...its are designed to provide reasonable protection against harmful interference in a residential and commercial installation This equipment generates uses and can radiate radio frequency energy and if...

Page 14: ...ormer 24VAC 4A Fuse Fast Acting EOL Enabled at the last sensor at the end of the Bus From Previous Device To Next Device L ON W ORKS Network 249 ohm resistor built in for inputs configured as 4 20mA E...

Page 15: ...Overloaded power transformer Verify that the transformer used is powerful enough to supply all controllers See Power Wiring Network not wired properly Double check that the wire connections are corre...

Page 16: ...t Short Short blink 800ms On 300ms Off 150ms On 300ms Off 150ms On 300ms Off 150ms On The controller is in bypass mode Appropriate action Set the controller Online Short Short Long blink 150ms On 300m...

Reviews: