Distech LonWorks ECL-203 Series Installation Manual Download Page 7

7 / 16

Input Wiring

Before connecting a sensor to the controller, refer to the installation guide of the equipment manufacturer.

£

For a wire length less than 75’ (23m), either a shielded or unshielded 18AWG wire may be used.

£

For a wire up to 200’ (61m) long, a shielded 18AWG wire is recommended.

£

The shield of the wire should be grounded on the controller side only and shield length should be kept as short as possible.

Table 1 shows the ECL-203, ECL-300, ECL-400, and ECL-600 Series controller pulse and current input jumper support. Table 2 shows the available uni-
versal input (UIx) wiring methods.

Controller

Fast and Slow Pulse Inputs support

Current Input Jumper support:

0 to 10VDC / 0 to 20mA

50Hz: 10ms minimum ON/OFF

(Fast Pulse)

1Hz: 500ms minimum ON/OFF

(Slow Pulse)

ECB‑203

None

UI1 to UI6

None

ECB‑300

UI1 to UI4

UI5 to UI10

Yes; see

 Table 2

ECB-400 Series

UI1 to UI4

UI5 to UI12

ECB-600 Series

UI1 to UI4

UI5 to UI16

Table 1: Controller Input Support

Sensor Input Type

Input Connection Diagram

£

Dry Contact input.

UIx

COM

To Digital 

Input

Digital Dry Contact

NO-NC

£

RTD input (for example, 1000Ω).

£

Thermistor Input (for example, 10kΩ type II and III).

UIx

COM

To Analog-

To-Digital 

Converter

RTD/

Thermistor   

£

Resistive input, (for example, use with 10kΩ and 100kΩ potentiometers).

UIx

COM

To Analog-

To-Digital 

Converter

Potentiometer

10kΩ

ECL-203 Series:

£

0 to 20mA input used with a 2-wire, 0 to 20mA sensor powered by the controller’s internal
15VDC power supply.

+

Sensor

0-20mA

UIx

COM

+15VDC

To Controller’s 

Analog-To-Digital 

Converter

249

Ω / ¼W

ECL-203 Series:

£

0  to  20mA  input  used  with  a  2-wire,  0  to  20mA  sensor  powered  by  an  external  24VDC
power supply.

-

+

0-20mA

Sensor

UIx

COM

To Analog-

To-Digital 

Converter

24VDC

249

Ω 

¼W

ECL-203 Series:

£

0  to  20mA  input  used  with  a  3-wire,  0  to  20mA  sensor  powered  by  an  external  24VAC
power supply.

AC

+

Common

0-20mA

Sensor

UIx

COM

To Analog-

To-Digital 

Converter

24VAC

249

Ω 

¼W

ECL-203 Series:

£

0 to 20mA input used with a sensor powered by its own power source.

+

-

0-20mA

Sensor

UIx

COM

To Analog-

To-Digital 

Converter

249

Ω 

¼W

Summary of Contents for LonWorks ECL-203 Series

Page 1: ...of the device pay special attention to the following recommendations It is recommended that the controller s be kept at room temperature for at least 24 hours before installation to allow any condensa...

Page 2: ...e Hardware Installation Guide Alternating Current Direct Current General Wiring Recommendations Risk of Electric Shock Turn off power before any kind of servicing to avoid electric shock All wiring mu...

Page 3: ...3 16 Controller Dimensions Components Figure 2 Rear view of large enclosure Figure 3 Rear view of small enclosure Figure 4 Side view of large and small enclosure...

Page 4: ...orientation must be horizontal with controller s back attached to a vertical wall surface Figure 5 Permitted Mounting Positions DIN Rail Mounted Installation 1 Ensure the DIN rail is properly mounted...

Page 5: ...the secondary side of the transformer Connecting the power source to Electrical System Ground is not a requirement for proper system operation However it is good installation practice to do so in ord...

Page 6: ...e 0 20 mA Enable LONWORKS Network Board Net to Subnet Settings Enabled Disabled Figure 9 ECL 300 Controller Jumper Locations Factory default positions LONWORKS Network Board Universal Outputs UO 0 10V...

Page 7: ...6 Table 1 Controller Input Support Sensor Input Type Input Connection Diagram Dry Contact input UIx COM To Digital Input Digital Dry Contact NO NC RTD input for example 1000 Thermistor Input for examp...

Page 8: ...24VAC Voltage input used with a 0 to 10VDC or 0 to 5VDC sensor powered by its own power source 0 10V Sensor UIx COM To Analog To Digital Converter Slow Pulse Internal supply 2 wire pulse meter for ECL...

Page 9: ...WM output controlling a 12VDC relay Maximum 60 mA minimum load resistance 200 UOx From Digital Output 12VDC Relay A1 A2 UOx COM Current 0 to 20mA universal output jumper configuration For ECL 300 ECL...

Page 10: ...e Protect the controller s connector from being pulled on when a cable to the Allure Series is connected Create a strain relief by looping the cable and attaching it to a solid object with a nylon tie...

Page 11: ...o the Troubleshooting Guide The Cat5e cable length is restricted by the maximum allowable subnetwork bus length see the Allure EC Smart Vue Hardware Installation Guide for more information Controller...

Page 12: ...sed to relieve tension on the wiring and conceal the controllers wire terminals Strain reliefs and terminal block covers are optional and are sold as peripherals Prior to connecting all wires it is re...

Page 13: ...its are designed to provide reasonable protection against harmful interference in a residential and commercial installation This equipment generates uses and can radiate radio frequency energy and if...

Page 14: ...ormer 24VAC 4A Fuse Fast Acting EOL Enabled at the last sensor at the end of the Bus From Previous Device To Next Device L ON W ORKS Network 249 ohm resistor built in for inputs configured as 4 20mA E...

Page 15: ...Overloaded power transformer Verify that the transformer used is powerful enough to supply all controllers See Power Wiring Network not wired properly Double check that the wire connections are corre...

Page 16: ...t Short Short blink 800ms On 300ms Off 150ms On 300ms Off 150ms On 300ms Off 150ms On The controller is in bypass mode Appropriate action Set the controller Online Short Short Long blink 150ms On 300m...

Reviews: