2 / 8
Maintenance and Cleaning
Gently clean the device with a soft, lint-free cloth slightly moistened with a solution of mild liquid dish soap and warm water or disinfect the device with a
soft cloth slightly moistened with a 70% isopropyl alcohol.
Do not directly spray any liquid or disinfecting solution on the device. Do not clean with any other chemicals products.
Mounting Instructions
The Allure ECW-Sensor has been specially designed for easy installation. However, certain conditions apply when choosing a suitable location for the
device:
£
Install the device in a location of average temperature approximately 5 ft (1.5 m) above the floor
£
The device should not be installed on an exterior wall.
£
The device should not be installed near a heat source.
£
The device should not be installed near an air discharge grill.
£
The device should not be installed in a place where it can be affected by the sun.
£
Install the device in an area that provides proper device ventilation. Nothing must restrain air circulation to the device.
The Allure ECW-Sensor has not been designed for outdoor use.
The Allure ECW-Sensor can be mounted on a wall using screws or double-sided adhesive tape.
Before installation, verify that local communication regulations allow the operation of wireless devices that communicate at a frequency of
902 or 868MHz. For more information on transmission norms in different countries, refer to the Open-to-Wireless™ Application Guide.
For the 868MHz model only:
£
Center frequency: 868.3MHz
£
Occupied frequency band: 868.0 - 868.6MHz
£
Maximum transmission power: 3dBm
For the 902MHz model only:
£
Center frequency: 902.875MHz
£
Occupied frequency band: 902.7-903.0MHz
£
Maximum transmission power: 1dBm
Wall Mounting with Tape
The Allure ECW-Sensor can be mounted on almost any type of surface using double-sided adhesive tape. Simply apply the tape to the back of the de-
vice first and then stick it to the desired spot on the wall.
Figure 2: Mounting using double-sided adhesive tape
Wall Mounting with Wall Screws
The Allure ECW-Sensor can also be mounted using wall screws:
1. Open the sensor by separating its front and back plates.
2. Use the mounting holes on the back plate to mark the location of the holes that need to be drilled.
3. Remove the back plate and drill the holes.
4. Clean the newly drilled holes, insert some wall anchors, and then fasten the back plate using the appropriate screws.
5. Re-attach the sensor to the back plate.