I N S TA L L AT I O N

8.  RUNNING YOUR SYSTEM

Page  8

TM

Run the system at fully open, maximum temperature for 1 hour, to expel any air in the system. Release any air that may be trapped at appropriate 

radiator  bleed  points  and  return  manifold  bleed  point.  Turn  off  TRV/flow  manifold  and  allow  to  cool.  Set  to  desired  room  setting  and  run 

normally.

NOTE

: DiscreteHeat recommend flushing the system with ThermaSkirt Cleanser TS3 or alternatively Scalemaster SM3 (check dosage 

carefully) and running  with  ThermaSkirt  corrosion  inhibitor  TS5  or  alternatively  Scalemaster  SM5 or SM10  (check  dosage  carefully)  to 

ensure  maximum  longevity and reliability. Hard water areas may require additional precautions. Chemically softened water must NOT be used. This is 

a standard precaution for ALL wet heating systems and a requirement of BS 7593:2006. Contact DiscreteHeat for specific application advice.

Failure to provide a suitable corrosion inhibitor will invalidate your warranty!

PROBLEM 

CAUSE 

SOLUTION

Leak at joint. 

Faulty / incorrect installation. 

Drain and replace fitting or ‘O” ring from spares kit.

Leak on ThemeSkirt pipes. 

No inhibitor fitted. 

Drain down, cleanse with TS3 and install inhibitor TS5.

 

Corrosion chemical/cleaner left in system 

Drain down, replace piece, cleanse with TS3 and refill.

ThermaSkirt not hot. 

Check boiler. 

Is heating ’ON’ and pressure OK?

 

Lockshield valve closed. 

Open Lockshield valve (      ).

 

TRV valve closed / off. 

Open TRV valve (      ).

 

Air trapped in pipework. 

See 10 below.

Water from return manifold  

Manifold not closed fully. 

Turn to ‘OFF’ position.

Noise - ticks & clicks when heat on 

Connectors & fittings rubbing on wall. 

Relieve plasterwork at Feed & Return and/or corner fittings.

Sudden ‘bangs’ 

ThermaSkirt length(s) cut too long, 

Check lengths & refit if necessary.

 

expanding and jumping off the bracket.

 

Internal corners clipped both sides.  

Check & remove/unclip unecessary clip. 

TRV Unit

Trapped air expelled through boiler

Auto vent recommended to ease bleeding

CLOSE

1. System with ThermaSkirt

®

 & Conventional Radiators.

2. New Installation with ThermaSkirt

®

 Only.

On installation, in a convenient place at the highest point 
of the system, ‘T’ off into a vertical leg 600mm high and 
install an automatic/manual air vent.
Following  the  procedure  above,  close  and  open  each 
ThermaSkirt

®

 system in turn.

Any air forced round the system will be expelled through 
the boiler or through the air vent.
Air  can  also  be  bled  from  the  bleed  screw  on  top  of  the 
return manifold (

A

).

As ThermaSkirt

®

 acts like a pipe, in normal operation air does not get trapped. However, on existing systems, to which ThermaSkirt  is added, air 

®

®

Trapped air expelled through boiler

600mm (min)

AV

A

9.  TROUBLE SHOOTING

10.  BLEEDING YOUR SYSTEM

may get trapped in the existing pipework to and from the skirting. Follow these simple steps if you discover cold sections of the ThermaSkirt

 which do not heat up.

Turn off all radiators and ThermaSkirt thermostatic and lockshield 
valves. Make sure your system is fully pressurised and the pump is 
set to max. Run the system for a few minutes, and, starting from 
the lowest 

point 

in 

the 

house, 

open 

each 

radiator/ThermaSkirt  system, one at a time. Run  for  a  further  2 
minutes  (approx)  ,  close  again  and move  to  the  next  Ther-
maSkirt   or  radiator,  moving upwards in the house.  Any air will 
be expelled through the boiler or trapped in a conventional 
radiator. Bleed the radiator as normal. 

CLOSE

Summary of Contents for ThermaSkirt

Page 1: ...t copies at www discreteheat co uk technical html TM 75mm 130mm FINISHED FLOOR LEVEL 35mm 90mm FLOW 15 16mm RETURN 15 16mm 45mm 100mm CLASSIC TS 6in 150mm THE SAME DIMENSIONS AND SPACINGS APPLY TO ANTI CLOCKWISE INSTALLATIONS ALL EXAMPLES SHOWN ARE CLOCKWISE RH INSTALLATIONS Remember to allow for carpet or tiles if NOT Finished Floor Level Your ThermaSkirt system must be cleansed and protected by ...

Page 2: ...TPI minimum PIPE CONNECTORS NEED TO BE SET INTO THE WALL FOR ALL TEMPLATESVISIT www discreteheat co uk technical html See pages 9 12 for pipe templates 130mm 65mm 120mm 90mm 60mm 95mm 100mm 45mm 65mm 130mm DOUBLE TRV INSTALLATION TEMPLATE Sheet 1 of 2 Through floor pipework Left and right feed DO NOT SCALE DRGWHEN PRINTING 75mm 0 20 40 mm CLOCKWISE SHOWN 150mm BI DIRECTIONAL TRV Relieve plasterwor...

Page 3: ...er and configuration of clips IMPORTANT ALL CUT ENDS MUST BE DEBURRED AS SHOWN BELOW IMPORTANT All cut ends MUST be deburred to preserve your warranty Remove all chaff and debris to preserve your warranty Problems may occur if not properly removed Internal corner External corner Return manifold Odd angle internal Odd angle external In line joint 6m walls Door architrave kit Non TRV feed return thr...

Page 4: ...RK TOP OF SKIRTING WITHOUT CAULKING STRIP OR SHOULDYOU NEED TO MOVE THE SKIRTING PEEL AWAY FROM BRACKETS AS SHOWN DO NOT TILT UP OR DOWN 100mm from end of skirting 600mm 700mm Insulating foil if required Part No INSRL LT INSRLTS or INSRL OG older solid walls without cavity 5mm 700mm approx 7mm Ø Gently push each piece back to the wall and assess wall straightness if there any gaps greater than 10m...

Page 5: ...ARE TO THE SKIRTING START WITH TRV AT FEED AND RETURN PIPE END O RINGS MUST BE GREASED O RINGS MUST BE GREASED GREASE SUPPLIED MUST BE USED ON ALL CONNECTORS TO AVOID DAMAGE ON ASSEMBLY AND PRESERVE YOUR WARRANTY O RINGS MUST BE GREASED CONTINUE ROUND THE ROOM REFERRING TO CORRECT CLIP SEQUENCE ON PAGE 3 4 INSTALLATION SEQUENCE 7mm Ø 60 1000mm apart ALL OTHER INFORMATION FOR SPACING BENDING ETC IS...

Page 6: ...p to retain the final section CHECKTHATTHE FINAL PIECE CANNOT COME OFF UNDER PRESSURE If a return manifold follows an internal corner double clips must be used FITTING FINAL SECTION 5 CORNERS AND COVERS ENSURE BOTH SIDES ARE LEVEL WITH EACH OTHER See separate instructions provided with Regency OG Deco PR 1 2 Mitre top gaskets before fitting corner cover TOP TIP Soak top gasket in warm soapy water ...

Page 7: ...em is recommended See part no TTEST OFF 2 1 Material Output per M dT50 C Feed Return Weight Capacity Corrosion Min Flow Surface Complies Recommended BTU W Pipe Kg per m Litres per m Resistance Rate Finish with Max OperatingTemp Unique Polymer TS LT 500BTU 150W 15mm 1 4kg LT 0 5 l m Excellent 10 c c per sec Epoxy Powder BS EN 75 C AluminiumAlloy OG 700BTU 210W 16mm to order 1 7kg OG See Section 8 0...

Page 8: ...position Noise ticks clicks when heat on Connectors fittings rubbing on wall Relieve plasterwork at Feed Return and or corner fittings Sudden bangs ThermaSkirt length s cut too long Check lengths refit if necessary expanding and jumping off the bracket Internal corners clipped both sides Check remove unclip unecessary clip TRV Unit Trapped air expelled through boiler Auto vent recommended to ease ...

Page 9: ...EL WALL FINISHED FLOOR LEVEL 0 20 40 mm Drill 2 x 18mm holes See sheet 2 for location 130mm 65mm 120mm 90mm 60mm 95mm 100mm 45mm Relieve plaster surface finish to a depth of 5mm in this shaded area to allow for Tectite fittings Relieve plaster surface finish to a depth of 25mm in this dark shaded area to allow feed pipe to go behind Tectite fitting 65mm 130mm DOUBLE TRV INSTALLATION TEMPLATE Sheet...

Page 10: ...END RH END WALL WALL FINISHED FLOOR LEVEL FINISHED FLOOR LEVEL WALL FINISHED FLOOR LEVEL 130mm OG 75mm OG 100mm LT 90mm PR 45mm LT 35mm PR Drill 2 x 18mm holes See sheet 2 for location 130mm 65mm 120mm 90mm 60mm 95mm 100mm 45mm Relieve plaster surface finish to a depth of 5mm in this shaded area to allow for Tectite fittings Relieve plaster surface finish to a depth of 25mm in this dark shaded are...

Page 11: ...m 95mm 100mm 45mm Relieve plaster rface finish to a pth of 5mm in is shaded area to allow for Tectite fittings Relieve plaster surface finish to a depth of 25mm in this dark shaded area to allow feed pipe to go behind Tectite fitting 65mm 130mm DOUBLE TRV INSTALLATION TEMPLATE Sheet 1 of 2 Through floor pipework Left and right feed DO NOT SCALE DRG WHEN PRINTING 75mm Cut fold along here for Urban ...

Page 12: ...plaster rface finish to a pth of 5mm in is shaded area to allow for Tectite fittings Relieve plaster surface finish to a depth of 25mm in this dark shaded area to allow feed pipe to go behind Tectite fitting 65mm 130mm DOUBLE TRV INSTALLATION TEMPLATE Sheet 1 of 2 Through floor pipework Left and right feed DO NOT SCALE DRG WHEN PRINTING 75mm Cut fold along here for Urban LT template Cut fold along...

Reviews: