background image

discoverbattery.com

8

7

6 VDC

12 VDC

24 VDC

48 VDC

Bulk & Absorption Charge Voltage U2

7.2V

14.4V

28.8V

57.6V

Recommended Charge Current I1

I1 = Min 10% C20 to Max 25% C20

Float Voltage U3

6.8V

13.5V

27.0V

54.0V

Table 2: Voltage Regulated Charger - Charge settings at 25°C (77°F)

4.1.2 Commissioning Charge

Batteries lose charge while in transit or during storage. For this reason, a refresh charge should be given before putting 
the battery into service. Allow the charger to go through a full charge cycle before they are used.

During commission, measure the battery voltage and after commissioning, measure the battery voltage and surface 
temperature of each battery and log this data. Discover Commissioning Logs are online available online.

4.2 Discharging

No restriction on the discharge current up to the maximum allowable is required as long as the connections are properly sized and 
the battery temperature stays within the allowable limits. 

With traditional stationary and renewable energy systems, Depth of Discharge (DOD) is set to operate between 20% and 50% to 
maximize the life of the batteries. By default, this may be set by  power conversion manufacturer at 1.75 volts per cell (Vpc). Discover 
Dry Cell batteries deliver 50% of its rated capacity above 2.05 Vpc, this is also the recommended LVD to optimize battery runtime and 
longevity.  Preventing batteries to operate at low voltages will increase cycle life expectancy. Standard RE warranty is reduced on 
system designs that continuously exceed  50% DoD. 

6 VDC

12 VDC

24 VDC

48 VDC

Reference LVD / I10

20% DOD

6.30V

12.60V

25.20V

50.40V

50% DOD

6.15V

12.30V

24.60V

49.20V

Table 3: Reference Low-Voltage-Disconnect / I10 

4.3 Temperature Limits

The battery is designed to perform optimally at temperatures between 15-25°C. At lower temperatures the battery capacity is lower 

IUU CHARGE PROFILE

BULK

ABSORPTION

FLOAT

8 HRS

14 HRS

NO TIME LIMIT

I1 = 0.25C20 (max)

       0.10C20 (min)

U2 = 2.40VPC

(+/-0.015VPC)

U3 = 2.25VPC

Maximum Charge Time (Must be Limited to 24 hrs)

105%-108% recharge

Figure 1: Voltage Regulated Charge profile (IUU charger) at 25°C (77°F)

Summary of Contents for DRY CELL

Page 1: ...Stability 5 3 4 Parallel Connections 5 3 5 Series Connections 6 3 6 Series Parallel Connections 6 3 7 Electrical Connections 6 4 Operation 6 4 1 Charging 7 4 1 1 Charge Curve 7 4 1 2 Commissioning Ch...

Page 2: ...rtain configuration installations service and operating tasks should only be performed by qualified personnel in consultation with local utilities and or authorized dealers Qualified personnel should...

Page 3: ...l information concerning important procedures and features of the battery Read all the instructions before installation operation and maintenance This product must be recycled and is made of recycled...

Page 4: ...for integrity and electrolyte leakage Record receipt date and inspection data results and notify your servicing dealer of any damage Take photographs if necessary 2 2 Storage Store in a dry clean vent...

Page 5: ...atteries Be sure to provide adequate space and lighting for inspection maintenance testing and battery replacement Space should also be provided to allow the operation of lifting equipment and for tak...

Page 6: ...nected in the correct polarity If the battery circuit has a disconnect open the disconnect to isolate battery Check that all contact surfaces are clean If required clean poles terminals with a brass b...

Page 7: ...oat charge recharge can be terminated based on time this will need to be determined as it will vary with depth of discharge and charge current or percentage recharge 105 108 NOTE Acceptable charging A...

Page 8: ...its With traditional stationary and renewable energy systems Depth of Discharge DOD is set to operate between 20 and 50 to maximize the life of the batteries By default this may be set by power conver...

Page 9: ...following Inspect racks cabinets for corrosion or loss of integrity Check record if ventilation is sufficient Check record battery room temperature Check battery for cracks Check ground connections 6...

Page 10: ...K This is often an indication of sulphated batteries which can be confirmed by completing a load test An increase in Absorption time may be necessary to sufficiently charge the battery to full SOC WHY...

Page 11: ...d prior to storage The self discharge rate of fully charged batteries is very low in these conditions and they will not require charging for many months However if your batteries do freeze they may no...

Reviews: