6

5

•  Manually operated switching device that also automatically opens or breaks the circuit in the event of an over current 

(circuit breaker) for each string.

•  Same number of batteries for each string.
•  Same heat or temperature potential for each string.
•  Always connect the individual series strings first and then check that the different strings are at the same potential before 

connecting them in parallel.

3.5 Series Connections

Discover

®

 Solar Dry Cell may be connected in series to increase system voltage.  In the case of each series 

connected string, only use batteries of the same voltage, capacity, design and age.

•  Same cables or connector bar resistance for each string e.g. same cross-section, same length and 

same conductor type (copper, aluminum)

•  Disconnect capabilities (breakers) on each string for maintenance and safety.

3.6 Series/Parallel Connections

To increase both voltage and capacity, Discover Solar Dry Cell may be connected in series and parallel. 
Refer to diagram for series/parallel connections. Battery cables must be sized to the specifications 
required by the inverter charger and must be installed in accordance with the standards set by the 
authority having local jurisdiction.

3.7 Electrical Connections

Battery cables must be sized to the specifications required by the inverter charger and must be installed 
in accordance with the standards set by the authority having local jurisdiction.

•  Ensure that the battery is installed and connected in the correct polarity
•  If the battery circuit has a disconnect - open the disconnect to isolate battery
•  Check that all contact surfaces are clean. If required, clean poles/terminals with a brass brush/pad.
•  When using a washer to connect a battery cable to a battery terminal, it is very important to 

ensure the battery cable is contacting the lead surface of the terminal and that the washer is 
placed on top of the cable. Do not place the washer between the battery terminal and the battery 
cable, this creates high resistance and can cause terminal meltdown. 

•  Do not ground the terminals to any metal mounting, fixture, or body part
•  Connect battery cables. Connect the ground cable last to avoid sparking
•  Tighten terminal screws using the terminal torque values as in the table below and thinly coat connections and terminals 

with dielectric grease or silicone to prevent corrosion 

•  If the battery circuit has a disconnect - close disconnect to reconnect the battery

Terminal Type

Terminal Torque

(F10) M8 Button Terminal

7 ft-lbs / 10 NM

(F10) M10 Button Terminal

12 ft-lbs / 16 NM

AM Dual Terminal (AP and 5/16” threaded stud)

9 ft-lbs / 13 NM

AT Dual Terminal (AP and 3/8” threaded stud)

10 ft-lbs / 14 NM

 NOTE

All cable ends must be connected to battery terminals without 

any washers between terminal bushing and cable ends.

4. Operation 

▲ 

CAUTION!

Review operating limits - see datasheets.

Before charging the battery make sure to read and understand the instructions that come with the Power Conversion device. Never 
attempt to charge a battery without first reviewing and understanding the instructions for the Power Conversion device being used.

Series/Parallel Connection

Series Connection

Summary of Contents for DRY CELL

Page 1: ...Stability 5 3 4 Parallel Connections 5 3 5 Series Connections 6 3 6 Series Parallel Connections 6 3 7 Electrical Connections 6 4 Operation 6 4 1 Charging 7 4 1 1 Charge Curve 7 4 1 2 Commissioning Ch...

Page 2: ...rtain configuration installations service and operating tasks should only be performed by qualified personnel in consultation with local utilities and or authorized dealers Qualified personnel should...

Page 3: ...l information concerning important procedures and features of the battery Read all the instructions before installation operation and maintenance This product must be recycled and is made of recycled...

Page 4: ...for integrity and electrolyte leakage Record receipt date and inspection data results and notify your servicing dealer of any damage Take photographs if necessary 2 2 Storage Store in a dry clean vent...

Page 5: ...atteries Be sure to provide adequate space and lighting for inspection maintenance testing and battery replacement Space should also be provided to allow the operation of lifting equipment and for tak...

Page 6: ...nected in the correct polarity If the battery circuit has a disconnect open the disconnect to isolate battery Check that all contact surfaces are clean If required clean poles terminals with a brass b...

Page 7: ...oat charge recharge can be terminated based on time this will need to be determined as it will vary with depth of discharge and charge current or percentage recharge 105 108 NOTE Acceptable charging A...

Page 8: ...its With traditional stationary and renewable energy systems Depth of Discharge DOD is set to operate between 20 and 50 to maximize the life of the batteries By default this may be set by power conver...

Page 9: ...following Inspect racks cabinets for corrosion or loss of integrity Check record if ventilation is sufficient Check record battery room temperature Check battery for cracks Check ground connections 6...

Page 10: ...K This is often an indication of sulphated batteries which can be confirmed by completing a load test An increase in Absorption time may be necessary to sufficiently charge the battery to full SOC WHY...

Page 11: ...d prior to storage The self discharge rate of fully charged batteries is very low in these conditions and they will not require charging for many months However if your batteries do freeze they may no...

Reviews: