ETERNALUX
™
LED Light Bar
INSTALLATION GUIDE
ETERNALUX
™
LED LIGHT BAR
INSTALLATION GUIDE
Wire
Gauge
10 W
.42 A
20 W
.83 A
30 W
1.3 A
40 W
1.7 A
50 W
2.1 A
60 W
2.5 A
70 W
2.9 A
80 W
3.3 A
100 W
4. 2 A
22 AWG
53 ft.
27 ft.
17 ft.
13 ft.
11 ft.
9 ft.
8 ft.
7 ft.
6 ft.
18 AWG
134 ft.
68 ft.
45 ft.
33 ft.
27 ft.
22 ft.
19 ft.
17 ft.
14 ft.
16 AWG
215 ft.
109 ft.
72 ft.
54 ft.
43 ft.
36 ft.
31 ft.
27 ft.
22 ft.
14 AWG
345 ft.
174 ft.
115 ft.
86 ft.
69 ft.
57 ft.
49 ft.
43 ft.
36 ft.
12 AWG
539 ft.
272 ft.
181 ft.
135 ft.
108 ft.
90 ft.
77 ft.
68 ft.
56 ft.
10 AWG
784
ft.
397 ft.
263 ft.
197 ft.
158 ft.
131 ft.
112 ft.
98 ft.
82 ft.
24V Voltage Drop & Wire Length Distance Chart
VOLTAGE DROP CHARTS
For best performance and lumen output, ensure proper wire gauge is installed to compensate for voltage drop of low voltage circuits.
Determine load size. Let’s assume load
is 55 W. Round up to nearest load.
1
Determine distance from driver to load.
Let’s assume the distance is 20 ft.
2
It’s recommended to install 18 AWG to
eliminate excess voltage drop.
3
Voltage Drop Chart Guide