ETERNALUX

 LED Light Bar

 INSTALLATION GUIDE

ETERNALUX

 LED LIGHT BAR

INSTALLATION GUIDE

Wire 

Gauge

10 W

.42 A

20 W

.83 A

30 W

1.3 A

40 W

1.7 A

50 W

2.1 A

60 W

2.5 A

70 W

2.9 A

80 W

3.3 A

100 W

4. 2 A

22 AWG

53 ft.

27 ft.

17 ft.

13 ft.

11 ft.

9 ft.

8 ft.

7 ft.

6 ft.

18 AWG

134 ft.

68 ft.

45 ft.

33 ft.

27 ft. 

22 ft. 

19 ft.

17 ft.

14 ft.

16 AWG

215 ft.

109 ft.

72 ft.

54 ft.

43 ft.

36 ft.

31 ft.

27 ft.

22 ft.

14 AWG

345 ft. 

174 ft.

115 ft.

86 ft. 

69 ft.

57 ft.

49 ft.

43 ft. 

36 ft.

12 AWG

539 ft.

272 ft.

181 ft.

135 ft.

108 ft. 

90 ft.

77 ft.

68 ft.

56 ft.

10 AWG

784 

ft.

397 ft.

263 ft.

197 ft.

158 ft.

131 ft.

112 ft.

98 ft.

82 ft.

24V Voltage Drop & Wire Length Distance Chart

VOLTAGE DROP CHARTS

For best performance and lumen output, ensure proper wire gauge is installed to compensate for voltage drop of low voltage circuits. 

Determine load size. Let’s assume load 

is 55 W. Round up to nearest load.

1

Determine distance from driver to load. 

Let’s assume the distance is 20 ft.

2

It’s recommended to install 18 AWG to 

eliminate excess voltage drop.

3

Voltage Drop Chart Guide