background image

Rev 1.3        22.07.09

Dingo Reference Manual

40

BOST         EQUL         ABSB         FLOT 

Program 4 Menu System 

(For adjustable settings) 

Set 

time 

Set 

battery 

voltage 

TIME  VOLT  PROG  REG  MODE  EVNT 

VMAX  VMIN 

TEMP  SOLV  HIST 

BMAX 
EMAX 

ETIM 

EFRQ 

ABSV 

ATIM 

FLTV 
HYST 
BRTN 

Set max boost voltage 
Set max equalisation voltage 
Set equalisation time 
Set # days between eq.cycles 
Set absorbtion voltage 
Set absorbtion time 
Set float voltage 
Set hysteresis 
Set boost return voltage 

CLIM

Set charge current limit 

BFRQ 

Set max days to between boost cycles 

TCMP 

Set temp compensation profile 

FTIM 

DAY1  IN  OUT  VMAX  VMIN  FTIM  SOC  NEXT  BACK  EXIT 

DAY 2  IN  OUT  VMAX  VMIN 

VMIN 

VMIN 

FTIM 

FTIM 

FTIM 

SOC 

SOC 

SOC 

NEXT 

NEXT 

NEXT 

BACK 

BACK 

BACK 

EXIT 

DAY2 

DAY2 

DAY99  DATA 

DATA 

DATA 

EXIT 

EXIT 

IN 

IN 

OUT 

OUT 

VMAX 

VMAX 

DAY 3 

DAY 3 

DAY99 

DAY 4 

DAY 1 

SOC 

BATV 

Set 

program 

CHRG 

LOAD 

IN 

OUT 

DATA 

SET 

Toggle function status on/off 
Set generator control mode 

G ON 

GOFF 
GDEL 

GEXD 
GRUN 

GDAY 

G ON 

GOFF 
GDEL 

GEXD 
GRUN 

GDAY 

SOC% 

1 or 5 

G OFF 

GEXD 
GRUN 

GDAY 

SOC% 

G ON 

CINT  External 

GSET 
GMOD 

2 or 6 

0 or 4 

GRUN 

Set V/SOC% to start generator 
Set SOC% to stop generator 
Set V to stop generator 
Set delay before on/off change 
State of Charge (SOC) Long push to adjust
Set days between generator exercises 
Set length of generator exercise 
View/change # of days since last exercise 

(or run time GTIM if generator exercising )

LINT 

External 

LSET 
LOFF 

L ON 

LDEL 

Toggle low battery disconnect status on/off 
Set voltage at which load disconnects 
Set voltage at which load reconnects 
Set delay before switching 

INT 

External 

Clear 

Clear 

INT 

External 

Clear 

Clear 

Toggle setting lockout 

('A' showing means  

 settings adjustable) 

LSET 

Set function of LOAD terminal 

GSET 

Set function of general purpose terminal (G) 

BSET 

Set function of B- input 

BAT2 

Set Regulation voltage for 2nd battery control 

PWM 

Set which terminals use Pulse width Modulation 

BCAP 

Set amp Hour capacity of the battery 

ALRM 

Set voltage at which to activate alarm 

RSET 

Reset system (losing today's data and time) 

STRT 

(Setting) 

STOP 

(Setting) 

EMOD 
TMOD 

(Setting) 

EOFF /  EON 

Set what determines start of Event 
Set value which goes with STRT 
Set what stops Event 
Set value which goes with STOP 
Set second condition for Event 
Set third condition for Event 
Set value which goes with TMOD 
View current state of Event Controller 

adjust

DATA 

     Note: GSET will not toggle if clock is  

 

between 9pm -> 9am (Quiet  

 

time) unless GMOD is set to  

 

4, 5 or 6 (no-Quiet time) 

Thin arrow = short push 

Thick arrow = long push 

(Explained in User Guide p6) 

DAY1  DAY98 

1. 

2. 

3. 

4. 

5. 

6. 

7. 

Section: 

ESET 

Select which internal function controls an external switch* 

DFLT 

Return settings to factory defaults 

set to 

current BATV 

* ESET Submenu not shown for clarity

See section 7.5.2

A

Summary of Contents for D Series

Page 1: ...Rev 1 3 22 07 09 Dingo Reference Manual 1 D Series Dingo Reference Manual Advanced Solar Charge Controller ...

Page 2: ...Equalise optional 7 1 3 ABSB Absorption 7 1 4 FLOT Float 7 2 0 CHRG Menu 8 CHRG 8 CINT 8 CEXT 8 Generator Control 8 GSET 9 GMOD 9 GEXD Generator Exercise 9 GDEL Generator changeover delay 10 Generator Example 10 3 0 LOAD Menu 12 LOAD 12 LINT 12 LEXT 12 Low Battery Disconnect LSET LOFF LON LDEL 12 4 0 IN Menu 13 IN 13 IN INT 13 IN EXT 13 5 0 OUT Menu 13 OUT 13 OUT INT 13 OUT EXT 13 6 0 DATA Menu Re...

Page 3: ...a Temperature Sensor 21 7 5 MODE Menu Adjusting Configuration Settings 22 7 5 1 LSET GSET Controlling the load and G outputs 22 7 5 2 ESET Controlling external switches 24 7 5 3 BSET Configuring B Sense Input 24 7 5 4 BAT2 Second battery control 26 7 5 5 PWM and Slow Switching 27 7 5 6 BCAP Setting battery capacity 28 7 5 7 ALRM Setting an alarm point 28 7 5 8 RSET DFLT Reseting and setting factor...

Page 4: ...llation Notes Ensure that you have followed the installation instructions on pages 3 5 of the User Guide The Dingo can be used for system voltages up to 48V It is safe to connect the power before setting the system voltage even with a 48 volt battery Always mount the Dingo vertically with clear airflow around the bottom and top of the case In hot conditions do not put it in a sealed enclosure as t...

Page 5: ...ith a computer modem Using an external current shunt attached to a remote current sensor DSA allows the controller to see other current flows in the system The Dingo can control larger systems by adding external switch blocks attached to the serial bus The DUSB or D232 interfaces allows remote monitoring and adjustment Custom settings can be stored on a computer and uploaded into the controller Da...

Page 6: ...rge cycle to repeat the Dingo must return to the boost state There are three ways that it can do this a Low Battery Voltage If the battery voltage falls below the boost return voltage BRTN for more than 10 minutes then the Dingo will switch back into the boost state The delay is necessary to prevent large short term loads causing unnecessary returns to Boost b Programmed boost cycles optional The ...

Page 7: ...ay If ETIM is 0 then equalisation will not occur To prevent the controller being trapped in equalise mode for a long time because there is inadequate charge current to reach the equalise voltage the Dingo terminates equalise after 4 days 1 3 ABSB Absorption In this state the Dingo tries to keep the battery voltage constant while the last part of the battery charging occurs This prevents excessive ...

Page 8: ...rs So 10 is A 11 is b and 12 is C This list also allows the user to check that the Dingo has found or discovered all the external devices attached to the bus This discovery process is automatic If a device is not on the list and should be then refer to section 8 4 for troubleshooting advice Generator Control The Dingo has a comprehensive generator controller built in It works in a similar way to t...

Page 9: ...6 5V GOFF Set SOC to stop generator 1 125 GDEL Set delay before on off change 1 15 min SOC Current SOC Long push to adjust 0 127 GEXD Set days between generator exercise 2 60 days GRUN Set length of generator exercise 0 4 0 hrs GDAY View change of days since last exercise 2 60 days Active Parameter for relevant generator mode GMOD M Manual GMOD GMOD Settings Mode Description 0 Turn on when battery...

Page 10: ...D 5 SOC ON Voltage OFF no quiet time CHRG menu Set GON GOFF GDEL GEXD GRUN as required SET REG Check these settings are correct for your battery type Mode menu GSET 2 or LSET 2 GSET if using G terminal for generator control LSET if using LOAD terminal for generator control Note when changing from prog 0 3 to program 4 the user can load the default settings for program 1 into the Dingo using the DF...

Page 11: ...ergised Be careful with automotive relays because they can often be poor relays requiring large coil currents Use relays from the electronics industry which generally have lower drive power The G relay terminals do not need a catch diode across the relay coil to protect from the flyback voltage This protection is built into the G terminal It can be difficult to determine what current is required t...

Page 12: ...SET menu see Figure 3A Name Description Range LOFF Set voltage at which load disconnects 10 0 12 5 V LON Set voltage at which load reconnects 11 0 16 0 V LDEL Set delay before switching on off 0 15 min BATV CHRG LOAD IN OUT DATA SET LINT External LSET Toggle low battery LOFF Set voltage at which L ON Set voltage at which LDEL Set delay before load disconnects load reconnects disconnect status on o...

Page 13: ...ched to the bus The sense of its operation can also be reversed i e it can turn on the terminal when the function decides the load should be disconnected This can then be used as a low battery alarm or to drive a relay to turn off other loads The connection to real switches is set up in the MODE menu See section 7 5 for details DO NOT CONNECT AN INVERTER OR ANOTHER BATTERY TO THE LOAD TERMINAL Thi...

Page 14: ...n vs amp hours out The SOC display shows this balance as a percentage of the battery size Note that all system currents must be monitored by the regulator and the battery capacity must be entered by the installer at the BCAP setting before SOC will be meaningful Over time a pure amp hour balance counter will drift out of line with the real battery state of charge To keep the counter better aligned...

Page 15: ...ll and changes with battery age 6 5 TEMP Display External Battery Temperature and Setting Lockout This screen displays the external battery temperature sensor reading if attached or if it s not It is also used to adjust Setting Lockout see figure 6 A 6 Setting Lockout In some cases it is desirable to restrict the ability to adjust settings so as to prevent unwanted tampering To disable settings lo...

Page 16: ...t day or the next day s value Short pushes move between figures for the same day NEXT goes to the next day BACK goes to the previous day The day numbers wrap around when they reach the end A short push on the EXIT screen will take you back to the beginning of that day s record A long push will exit back to the DATA screen 6 Thin arrow short push Thick arrow long push BATV CHRG LOAD IN OUT DATA SET...

Page 17: ...ct PROG 4 Enables customised adjustment of all settings Installation instructions for programs 0 3 are on pages 8 9 of the User Guide Set time Set battery voltage TIME VOLT PROG REG MODE EVNT Set program BATV CHRG LOAD IN OUT DATA SET Fig 7A The SET Menu NOTE Removing power to the regulator i e turning it off will reset the system time to 10 0hrs 10 00 AM The time must be set whenever the regulato...

Page 18: ...ODE Allows the user to adjust other configuration options EVNT Settings for the event controller CHRG Setting for program number Parameter 0 1 2 3 GMOD 0 G ON V 11 5 GOFF V 13 8 GDEL Min 10 GEXD Day 30 GRUN Hr 1 0 LOAD Setting for program number Parameter 0 1 2 3 LOFF V 11 3 L ON V 12 8 LDEL Min 10 SET REG Setting for program number Parameter 0 1 2 3 BMAX V 15 0 14 2 15 0 14 2 EMAX V 16 0 14 0 16 ...

Page 19: ... DATA SET TIME VOLT PROG REG MODE EVNT BMAX EMAX ETIM EFRQ ABSV ATIM FLTV HYST BRTN CLIM BFRQ TCMP Set max boost voltage Set max equalisation voltage Set equalisation time Set days between eq cycles Set absorbtion voltage Set absorbtion time Set float voltage Set hysteresis Set boost return voltage Set charge current limit Set max days to between boost cycles Set temp compensation profile Fig 7 4A...

Page 20: ...e Dingo has a built in charge current limit If the charge current exceeds the CLIM setting the charge duty cycle will be reduced to limit the average charge current This allows the Dingo to protect itself from overheating due to excessive charge current The maximum charge current can also be limited for small batteries where the full array current might be too much for the battery This is useful f...

Page 21: ... stripe goes to T terminal The wires may be extended if necessary without affecting the accuracy Note The DTB bolt on metal lug has no electrical connection to metal lug housing so it can be connected to either the negative or positive battery terminal 7 Temperature C V Cell TEMPERATURE COMPENSATION CURVES Normalisedto2 25V cell 20 00 10 00 0 00 10 00 20 00 30 00 40 00 50 00 60 00 2 45 2 05 2 1 2 ...

Page 22: ...e LSET and GSET screens described in Section 2 and 3 The six internal control functions are a Low battery disconnect This also controls the LOAD indicator at the bottom of the screen b Run the backup generator This also controls the GEN indicator at the bottom of the screen c Charge a second battery Indicates when the solar input can be diverted to a 2nd battery d Battery voltage alarm output Prov...

Page 23: ...ct the shunt load ON for regulation 11 Shunt control PWM must not be set to 2 or 3 on when function wants to disconnect shunt load OFF for regulation Don t use LSET 11 with PWM as design does not allow inversion of PWM signal SET MODE GSET Function Terminal is 0 Low battery disconnect on when function wants to disconnect battery 1 Low battery disconnect off when function wants to disconnect batter...

Page 24: ...ured in the LSET and GSET screens see above Regulating Wind Hydro Shunt control is appropriate for wind generators or microhydro systems which require a constant load on the charging source so the generator doesn t overspeed and destroy itself In this case the charging source must remain connected to the battery at all times Shunt control also referred to as diversion control refers to the techniq...

Page 25: ... Button Light Fig 7 5 3B Push button connection 7 If the B input is not being used for this then it can be used for sensing the voltage on a second battery being charged or for providing a voltage input for the event controller VEXT Some inverter chargers such as the SP PRO can communicate to the charge controller when they want to export power to the grid Selecting BSET 3 enables this Push Button...

Page 26: ...n external switching device such as a changeover relay will be required to switch the positive of the solar panel s from the SOL terminal of the Dingo to the positive terminal on the second battery see fig 7 5 4A Use either the Load terminal or G relay for switching the changeover relay the G relay max current is only 300mA but this should be enough to drive most relays The following settings will...

Page 27: ...Only Selection Function 0 No PWM used 1 PWM on SOL terminal only 2 PWM on LOAD terminal only 3 PWM on both cause some ringing on turn off Keep wiring as short as possible and panel cable pairs together cable tie On long wiring runs at higher voltages some damping may be necessary and possibly some external clamping of transients With highly inductive wiring the transients may be large enough to da...

Page 28: ...cted to the LOAD or G terminal There is no audible alarm built into the Dingo It can send a signal or power to an external alarm of some kind The reverse function could be used to turn off a low priority load when the battery voltage is getting low System R1 Value 12V 1K 1 4W 5 24V 2K2 1 2W 5 48V 4K7 1W 5 Higher wattage resistors may be used R1 values are calculated to give adequate LED brightness...

Page 29: ...he block This prevents an event being immediately retriggered when it finishes STRT Setting STOP Setting EMOD TMOD Setting EOFF EON BATV CHRG LOAD IN OUT DATA SET TIME VOLT PROG REG MODE EVNT Set what determines start of Event Set value which goes with STRT Set what stops Event Set value which goes with STOP Set second condition for Event Set third condition for Event Set value which goes with TMO...

Page 30: ...e a switch or other contact closure device between the B sense terminal green terminal block and the BAT terminal and select BSET 2 Step 4 Select a STOP setting in this table to tell the Dingo what signifies the end of the event After setting the STOP value a short push will move you to the associated setting For example if you set STOP to 1 you will see TIME Once started the event will then conti...

Page 31: ...te External D will come from a bus accessory For settings 0 to 7 the low battery disconnect LBD function will override the EMOD condition and make EMOD inactive if the load should be disconnected This makes it possible to disable an event if the battery voltage is too low Settings 8 15 are the same as 0 7 but without the LBD overide SET EVNT TMOD Selection Summary The TMOD setting provides an extr...

Page 32: ...s have the effect of making STRT and STOP irrelevant The STRT condition will always be on and the STOP Whether EMOD is on 1 or off 0 if EOFF Whether STRT is on 1 or off 0 if E ON Whether STOP is on 1 or off 0 Whether TMOD is on 1 or off 0 Whether event is on E ON or off EOFF EOFF 001 Fig 7 7A Event State condition will never happen In practice the EMOD condition will determine whether the event is...

Page 33: ...ad displays In the case of an external generator the charge display would show the generator current and the load display would always be zero In the case of an inverter charger the current could either be in either direction and either the load or charge will be non zero depending on direction 8 2 Controlling external switches An external switch device must be controlled by something The Dingo al...

Page 34: ...ugh each device either using the two sockets on the device or using a double adaptor for single socket devices 8 4 Troubleshooting If a current measuring device does not appear in the external list of devices then check the following things a If the device address selection is set to manual check that two devices are not assigned to the same address number b Check the cabling to the device If the ...

Page 35: ...om the Dingo side This is a quick way to load settings into the Dingo or extract performance data All of the data is remotely accessible and all settings can be adjusted Software is available for IBM compatibles to make this easy Data can then be loaded into a spreadsheet or other applications Modem Serial Interface D232 The serial interface is also available in a version designed for remote acces...

Page 36: ...internal temperature The ability of the Dingo to operate without reducing the charge current depends on five factors the ambient temperature the load current the time that it has been hot the battery voltage and the number of external devices attached to the serial bus For example it takes about 1 hour for the Dingo internal temperature to reach equilibrium under fully loaded conditions It is diff...

Page 37: ... SOL BAT LOAD PUSH BUTTON POWER SUPPLY MICRO CONTROLLER G RELAY BATTERY SENSE B SENSE SHUNT SHUNT REVERSE BLOCKING FET SWITCH FET SWITCH A T S B L S B L BATTERY SOLAR BATTERY LOAD G Terminals Sensor T Temperature T B Sense LOAD SOLAR G Terminals Serial Port Test terminal Block diagram and terminal layout ...

Page 38: ...ur liability under the guarantee is limited by the following conditions Limitations 1 We reserve the right to repair or replace The decision to replace is only to be made by us or one of our authorised agents 2 We are not responsible for costs incured by the user or installer in retrieving or reinstating a faulty unit 3 We will not pay the cost of freighting faulty units to us or being returned fr...

Page 39: ...Y2 DAY99 DATA DATA DATA EXIT EXIT IN IN OUT OUT VMAX VMAX DAY 3 DAY 3 DAY99 DAY 4 DAY 1 SOC BATV Set program CHRG LOAD IN OUT DATA SET Toggle function status on off GRUN GDAY CINT External GSET Set length of generator exercise View change of days since last exercise or run time if generator running LINT External LSET Toggle low battery disconnect status on off INT External Clear Clear INT External...

Page 40: ...erator exercise View change of days since last exercise or run time GTIM if generator exercising LINT External LSET LOFF L ON LDEL Toggle low battery disconnect status on off Set voltage at which load disconnects Set voltage at which load reconnects Set delay before switching INT External Clear Clear INT External Clear Clear Toggle setting lockout A showing means settings adjustable LSET Set funct...

Page 41: ...age of panels ____________________________ Total solar input watts ________________________ STRT Setting STOP Setting EMOD TMOD Setting EOFF EON Other Comments ___________________________________________________________________________ ___________________________________________________________________________________________ ________________________________________________________________________...

Page 42: ...cs com au DAY No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 Date 30 days ago Comments yesterday IN Ah OUT Ah VMAX V VMIN V FTIM h SOC Customer History Data The following is the first 30 days of data stored each day in the history section of the DATA menu ...

Reviews: