EN-12
452234.66.57 · FD 9908
www.gdts.one
English
WIH 120TU
7
Complies with the European safety regulations
4
8
Additional model features
8.1
Water in device is protected against freezing
5
Yes
8.2
Max. operating overpressure (heat source/heat sink)
bar
3.0
9
Heat output / COP
9.1
Heat output / coefficient of performance (COP)
6
EN 14511
Performance level
1
2
at W10 / W65
kW / ---
58.0 / 3.0
114.2 / 3.0
at W10 / W55
kW / ---
62.1 / 3.8
117.8 / 3.7
at W10 / W45
kW / ---
65.6 / 4.7
121.1 / 4.4
at W10 / W35
kW / ---
70.5 / 5.9
126.6 / 5.5
1. The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation at 35 °C flow temperature.
The specified sound pressure level represents the free sound area level. The measured value can deviate by up to 16 dB(A), depending on the installation location.
2. Note that additional space is required for pipe connections, operation and maintenance.
3. These data indicate the size and capacity of the system according to EN 14511. For an analysis of the economic and energy efficiency of the system. the bivalence point and
regulation should be taken into consideration. These specifications can only be achieved with clean heat exchangers. Information on maintenance, commissioning and opera-
tion can be found in the respective sections of the installation and operating instructions. The specified values, e.g. W10 / W55, have the following meaning: Heat source tem-
perature 10 °C and heating water flow temperature 55 °C.
4. See CE declaration of conformity
5. The heat circulating pump and the heat pump manager must always be ready for operation.
6. The coefficients of performance are valid with the circulating pump(s) included in the scope of supply.
Summary of Contents for WIH 120TU
Page 2: ......
Page 16: ...DE 14 452234 66 57 FD 9908 www gdts one Deutsch WIH 120TU ...
Page 42: ...FR 14 452234 66 57 FD 9908 www gdts one Français WIH 120TU ...
Page 58: ...A XVI 452234 66 57 FD 9908 www gdts one Anhang Appendix Annexes WIH 120TU ...
Page 59: ...www gdts one 452234 66 57 FD 9908 A XVII WIH 120TU Anhang Appendix Annexes ...