WIH 120TU
Minimum heating water flow rate
The minimum heating water flow rate through the heat pump
must be assured in all operating states of the heating system.
This can be accomplished. for example, by installing a dual dif-
ferential pressureless manifold.
The frost protection function of the heat pump manager is active
whenever the heat pump manager and the heat circulating
pumps are ready for operation. The system must be drained if
the heat pump is taken out of service or in the event of a power
failure. If heat pump systems are implemented in buildings where
a power failure cannot be detected (holiday homes etc.), the
heating circuit should be operated with suitable frost protection.
7.3 Heat source connection
The following procedure must be observed when making the
connection:
Connect the well pipes to the heat pump's flow and return.
ATTENTION!
!!
It is essential that the dirt trap included in the accessories pack is
installed in the return (inlet).
ATTENTION!
!!
The well water must comply with the required water quality standards
(see see Cap. 9.4 on pag. 10).
The hydraulic integration diagram must be adhered to.
7.4 Temperature sensor
The following temperature sensors are already installed or must
be installed additionally:
Outside temperature sensor (R1) supplied (NTC-2)
Return temperature heating circuit (R2) installed (NTC-10)
Return temperature primary circuit (R24) installed (NTC-10)
Flow temperature heating circuit (R9) installed (NTC-10)
Flow temperature primary circuit (R6) installed (NTC-10)
7.4.1 Sensor characteristic curves
The temperature sensors to be connected to the heat pump man-
ager must correspond to the sensor characteristic curve illus-
trated in Fig. 7.2. The only exception is the outside temperature
sensor included in the scope of supply of the heat pump (see Fig.
7.3)
Fig. 7.2: Sensor characteristic curve NTC-10
Fig. 7.3:Sensor characteristic curve NTC-2 according to DIN 44574 Out-
side temperature sensor
Temperature in °C
-20
-15
-10
-5
0
5
10
NTC-2 in k
14.6
11.4
8.9
7.1
5.6
4.5
3.7
NTC-10 in k
67.7
53.4
42.3
33.9
27.3
22.1
18.0
15
20
25
30
35
40
45
50
55
60
2.9
2.4
2.0
1.7
1.4
1.1
1.0
0.8
0.7
0.6
14.9
12.1
10.0
8.4
7..0
5.9
5.0
4.2
3.6
3.1
0
10
20
30
40
50
60
70
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
External temperature in [°C]
Resistance value in
[kOhm]
0
2
4
6
8
10
12
14
16
18
20
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
External temperature in [°C]
Resistance value in
[kOhm]
Summary of Contents for WIH 120TU
Page 2: ......
Page 16: ...DE 14 452234 66 57 FD 9908 www gdts one Deutsch WIH 120TU ...
Page 42: ...FR 14 452234 66 57 FD 9908 www gdts one Français WIH 120TU ...
Page 58: ...A XVI 452234 66 57 FD 9908 www gdts one Anhang Appendix Annexes WIH 120TU ...
Page 59: ...www gdts one 452234 66 57 FD 9908 A XVII WIH 120TU Anhang Appendix Annexes ...