10 Maintenance and 

Cleaning 

10.1 Maintenance

To prevent faults due to sediment in the heat exchangers, care
must be taken to ensure that no impurities can enter either the
heat source system or the heating system. In the event that op-
erating malfunctions due to contamination occur nevertheless,
the system should be cleaned as described below. 

10.2 Cleaning the Heating System

The ingress of oxygen into the heating water circuit may result in
the formation of oxidation products (rust), particularly if steel
components are used. This oxygen enters the heating system via
the valves, the circulating pumps and/or plastic pipes. It is there-
fore essential - in particular with respect to the piping of under-
floor heating systems - that only diffusion-proof materials are
used.

ATTENTION!

We recommend the installation of a suitable corrosion protection system
to prevent the formation of deposits (e.g. rust) in the condenser of the
heat pump. We recommend equipping diffusion-open heating systems
with an electrophysical anti-corrosion system (e.g. ELYSATOR system).

Residue from lubricants and sealants may also contaminate the
heating water.
In the case of severe contamination leading to a reduction in the
performance of the liquifier in the heat pump, the system must be
cleaned by a heating technician.
According to today’s state of knowledge, we recommend using a
5 % phosphoric acid solution for cleaning purposes. However, if
cleaning needs to be performed more frequently, a 5 % formic
acid solution should be used. 
In either case, the cleaning fluid should be at room temperature.
We recommend flushing the heat exchanger in the direction op-
posite to the normal flow direction.
To prevent acidic cleaning agents from entering the heating sys-
tem circuit, we recommend connecting the flushing device di-
rectly to the flow and return flow of the liquifier. It is important that
the system be thoroughly flushed using appropriate neutralising
agents to prevent any damage from being caused by cleaning
agent residue remaining in the system.
Acids must be used with great care and all relevant regulations of
the employers’ liability insurance associations must be adhered
to.
If in doubt, contact the manufacturer of the chemicals!

10.3 Cleaning the Heat Source 

System

A dirt trap is inserted in the heat source inlet of the heat pump to
protect the evaporator against the ingress of impurities. When
the system is first put into operation, the filter screen of the dirt
trap should be cleaned in relatively short intervals. These inter-
vals can be prolonged once the amount of impurities decreases.

10.4 Water Quality Requirements 

The ground water should not contain any substances that could
form deposits. The limit values for iron (< 0.2 mg/l) and manga-
nese (< 0.1 mg/l) must be adhered to prevent iron ochre sedi-
mentation in the heat pump system.
The use of surface water or water containing salt is not permissi-
ble. Your local water utility can provide you with general informa-
tion regarding the possible use of ground water. Water analyses
are carried out by specially-equipped laboratories. 
It is not necessary to carry out a water analysis with regard to
evaporator corrosion if the annual mean temperature of the
ground water does not exceed 
13 °C). In this case, the limit values for iron and manganese must
be adhered to (iron ochre sedimentation).

11 Faults / Trouble-

Shooting

This heat pump is a quality product and is designed for trouble-
free operation. In the event that a fault should occur, it will be
shown on the heat pump manager display. Simply consult the
Faults and Trouble-Shooting page in the operating instructions of
the heat pump manager.
If you cannot correct the fault yourself, please contact your after-
sales service technician.

ATTENTION!

Any work on the heat pump may only be performed by authorised and
qualified after-sales service technicians.

ATTENTION!

Disconnect all electrical circuits from the power source prior to opening
the device.

12 Decommissioning / 

Disposal

Before removing the heat pump, disconnect it from the power
source and close all valves. Observe all environmentally-relevant
requirements regarding the recovery, recycling and disposal of
materials and components in accordance with all applicable
standards. Particular attention should be paid to the proper dis-
posal of refrigerants and refrigeration oils.

Summary of Contents for WI 14 TE

Page 1: ...to Water Heat Pump for Indoor Installation Pompe chaleur eau eau pour installation int rieure Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation Insta...

Page 2: ......

Page 3: ...nen DE 5 7 Montage DE 5 7 1 Allgemein DE 5 7 2 Heizungsseitiger Anschluss DE 5 7 3 W rmequellenseitiger Anschluss DE 6 7 4 Elektrischer Anschluss DE 6 8 Anschluss W rmepumpenmanager DE 6 8 1 Allgemein...

Page 4: ...nenrichtlinie f r den Gebrauch im h uslichen Umfeld bestimmt und unterliegt damit den Anforde rungen der EG Richtlinie 2006 95 EC Niederspannungsrichtli nie Sie ist damit ebenfalls f r die Benutzung d...

Page 5: ...ng zugef hrte elektrische Antriebs leistung geht nicht verloren sondern wird gr tenteils ebenfalls dem K ltemittel zugef hrt Daraufhin gelangt das K ltemittel in den Verfl ssiger und ber tr gt hier wi...

Page 6: ...enmanager sind folgende Netzwerkverbin dungen m glich Modbus EIB KNX Ethernet 5 Transport Zum Transport auf ebenem Untergrund eignet sich ein Hubwa gen Muss die W rmepumpe auf unebenem Untergrund oder...

Page 7: ...l der W rmepumpe f hren Nach erstellter heizungsseitiger Installation ist die Heizungsan lage zu f llen zu entl ften und abzudr cken Beim F llen der Anlage ist folgendes zu beachten unbehandeltes F ll...

Page 8: ...ch den einschl gigen Vorschriften zu w hlen Die Leistungsaufnahme der W rmepumpe entnehmen Sie der Pro duktinformation oder dem Typschild Die Anschlussklemmen sind f r max 10 mm2 Leiterquerschnitt aus...

Page 9: ...gler 8 2 3 Montage der Anlegef hler Die Montage der Anlegef hler ist nur notwendig falls diese im Lieferumfang der W rmepumpe enthalten aber nicht eingebaut sind Die Anlegef hler k nnen als Rohranlege...

Page 10: ...E10 ist bei monoenergetischen Anlagen 2 WE entsprechend der Heizk rperleistung auszulegen und bauseits beizustellen Die Ansteuerung 230VAC erfolgt aus dem W rmepumpenmanager ber die Klemmen N und N1...

Page 11: ...ndern k nnten ge ffnet sein Der W rmepumpenmanager muss gem seiner Ge brauchsanweisung auf die Heizungsanlage abgestimmt sein 9 3 Vorgehensweise bei Inbetriebnahme Die Inbetriebnahme der W rmepumpe er...

Page 12: ...ssenschaften einzuhalten Im Zweifelsfall ist mit dem Hersteller des Reinigungsmittels R cksprache zu halten 10 3 Reinigung W rmequellenseite Im W rmequelleneintritt der W rmepumpe ist ein Schmutzf n g...

Page 13: ...uckdifferenz W rmequelle m h Pa 2 0 6200 1 9 5600 3 3 19000 3 2 13000 4 0 12000 3 6 9500 5 0 20000 4 8 17900 7 0 16000 6 7 14900 3 7 K ltemittel Gesamt F llgewicht Typ kg R407C 1 7 R407C 1 9 R407C 3 5...

Page 14: ...ne Teile und Ger te Anlagenm ngel die auf nicht vom Lieferer bezogene Teile zur ckzuf hren sind fallen nicht unter den Garantieanspruch Sofern der Mangel nicht beseitigt werden kann oder die Nach bess...

Page 15: ...ns EN 5 7 Installation EN 5 7 1 General Information EN 5 7 2 Heating System Connection EN 5 7 3 Heat Source Connection EN 6 7 4 Electrical Connection EN 6 8 Heat pump manager connection EN 6 8 1 Gener...

Page 16: ...domestic environment according to Article 1 Paragraph 2 k of EC directive 2006 42 EC machinery directive and is thus subject to the requirements of EC directive 2006 95 EC low voltage directive It is...

Page 17: ...not lost in this process Most of it is absorbed by the refrigerant as well Subsequently the refrigerant is passed through the condenser where it transfers its heat energy to the heating water Dependin...

Page 18: ...lowing network connections can be made on the heat pump manager Modbus EIB KNX Ethernet 5 Transport A lift truck is suited for transporting the unit on a level surface Carrying straps may be used if t...

Page 19: ...system has been installed it must be filled de aerated and pressure tested Consideration must be given to the following when filling the sys tem Untreated filling water and make up water must be of d...

Page 20: ...actor as well as a 3 pole circuit breaker with common tripping for all external conductors have to be provided by the customer The required conductor cross section is to be selected according to the p...

Page 21: ...sensor The temperature sensor must be mounted in such a way that all weather conditions are taken into consideration and the meas ured value is not falsified Installation On the external wall of a he...

Page 22: ...led in the power supply for the heat pump tripping current and characteristic in com pliance with the device information 2 The three core supply cable for the heat pump manager heating controller N1 i...

Page 23: ...it should only be carried out by an after sales service technician authorised by the manufacturer This may be a condition for extending the guaran tee see Warranty Service 9 2 Preparation The followin...

Page 24: ...t care and all relevant regulations of the employers liability insurance associations must be adhered to If in doubt contact the manufacturer of the chemicals 10 3 Cleaning the Heat Source System A di...

Page 25: ...Pa 2 0 6200 1 9 5600 3 3 19000 3 2 13000 4 0 12000 3 6 9500 5 0 20000 4 8 17900 7 0 16000 6 7 14900 3 7 Refrigerant total filling weight type kg R407C 1 7 R407C 1 9 R407C 3 5 R407C 3 2 R407C 4 5 3 8 L...

Page 26: ...EN 12 English 13...

Page 27: ...ge FR 5 7 1 Remarques d ordre g n ral FR 5 7 2 Branchement c t installation de chauffage FR 5 7 3 Raccordement c t source de chaleur FR 6 7 4 Branchements lectriques FR 6 8 Raccordement gestionnaire d...

Page 28: ...article 1 paragraphe 2 k de la directive CE 2006 42 CE directive relative aux machines et est ainsi soumise aux exigences de la directive CE 2006 95 CE directive Basse Tension Elle est donc galement...

Page 29: ...nsf r e au contraire galement en grande partie au fluide frigorig ne Le fluide frigorig ne arrive alors dans le condenseur o son tour il transmet l nergie thermique l eau de chauffage Ainsi l eau de c...

Page 30: ...tes sont possibles pour le gestionnaire de pompes chaleur Modbus EIB KNX Etherne 5 Transport Le transport par chariot l vateur convient bien un d place ment sur surface plane Si la pompe chaleur doit...

Page 31: ...hauffage doit tre rinc e pour liminer d ventuelles impuret s et les restes ventuels des ma t riaux d tanch it ou autres Une accumulation de d p ts di vers dans le condenseur est susceptible d entra ne...

Page 32: ...de pompe chaleur par exemple sonde mur ext rieur vous sont fournies dans les instructions d utilisation du gestionnaire de pompe chaleur jointes la machine Il faut pr voir une d branchement avec au mo...

Page 33: ...emp rature ext rieure La sonde de temp rature doit tre plac e de telle sorte qu elle puisse d tecter la plupart des influences atmosph riques sans que les valeurs mesur es ne soient fauss es Montage s...

Page 34: ...issance de la pompe chaleur pr voir une coupure omnipolaire avec au moins 3 mm d carte ment d ouverture de contact p ex contacteur de blocage de la soci t d lectricit ou contacteur de puissance ainsi...

Page 35: ...on du mode ac tuel de la pompe chaleur chauffage eau chaude sanitaire eau de piscine additionne la quantit de chaleur en kWh et affiche le r sultat dans les menus caract ristiques d exploitation et hi...

Page 36: ...p ts dans les changeurs thermiques de la pompe chaleur il faut veiller ce qu aucune sorte de d p t ne puisse s introduire dans les installa tions de chauffage et de source de chaleur Si des dysfonctio...

Page 37: ...sse pas une temp rature moyenne annuelle de 13 C Dans ce cas il suffit de respecter les valeurs limites de fer et de mangan se d p t d ocre 11 D faillances recherche de pannes Cette pompe chaleur est...

Page 38: ...m h Pa 2 0 6200 1 9 5600 3 3 19000 3 2 13000 4 0 12000 3 6 9500 5 0 20000 4 8 17900 7 0 16000 6 7 14900 3 7 Fluide frigorig ne poids au remplissage total type kg R407C 1 7 R407C 1 9 R407C 3 5 R407C 3...

Page 39: ...s WI 9TE WI 22TE A X 3 4 Legende Legend L gende WI 9TE WI 22TE A XI 3 5 Steuerung Control Commande WI 27TE A XII 3 6 Last Load Charge WI 27TE A XIII 3 7 Klemmenanschlussplan Terminal Connection Plan S...

Page 40: ...GH 7 H WHUQDO WKUHDG RQQHFWLRQV RQ WKH KHDW VRXUFH VLGH 7 H WHUQDO WKUHDG DWHU ILOWHU ZLWK H WHUQDO WKUHDG 7 H WHUQDO WKUHDG DWHU ILOWHU ZLWK H WHUQDO WKUHDG 5DFFRUGV F Wp FKDXIIDJH 7 LOHWDJH H WpULHX...

Page 41: ...VVLRQ HQ 3D UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D DOWZDVVHUHLQWULWWVWHPSHUDWXU LQ ROG ZDWHU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX IURLGH HQ DOWZDVVHUGXUFKIOXVV LQ P K...

Page 42: ...LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D DOWZDVVHUHLQWULWWVWHPSHUDWXU LQ ROG ZDWHU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX IURLGH HQ DOWZDVVHUGXUFKIOXVV LQ P K ROG ZDWHU IORZ UDWH LQ...

Page 43: ...HUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D DOWZDVVHUHLQWULWWVWHPSHUDWXU LQ ROG ZDWHU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX IURLGH HQ DOWZDVVHUGXUFKIOXVV LQ P K ROG ZDWHU IORZ U...

Page 44: ...LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D DOWZDVVHUHLQWULWWVWHPSHUDWXU LQ ROG ZDWHU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX IURLGH HQ DOWZDVVHUGXUFKIOXVV LQ P K ROG ZDWHU IORZ UDWH LQ...

Page 45: ...YHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D DOWZDVVHUHLQWULWWVWHPSHUDWXU LQ ROG ZDWHU LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX IURLGH HQ DOWZDVVHUGXUFKIOXVV LQ P K ROG ZDWHU IORZ...

Page 46: ...A VIII Anhang Appendix Annexes 3 3 Stromlaufpl ne Circuit Diagrams Sch mas lectriques 3 1 Steuerung Control Commande WI 9TE WI 22TE 1HW 0DLQV 5pVHDX...

Page 47: ...VRFLpWp GLVWULEXWULFH G pOHFWULFLWp 1HW 0DLQV 5pVHDX 9HUGUDKWXQJ lQGHUQ Q QODJHQ RKQH 98 6SHUUH NDQQ GLH GLUHNWH LQVSHLVXQJ I U GLH UXQQHQSXPSH HQWIDOOHQ KDQJH ZLULQJ 6 VWHPV ZLWKRXW XWLOLW EORFN GR Q...

Page 48: ...RX HL VWDE PPHUVLRQ KHDWHU 7KHUPRSORQJHXU RQWDNW RIIHQ 3 JHVSHUUW RQWDFW RSHQ 3 GLVDEOHG RQWDFW RXYHUW 3 EORTXpH LH XQNWLRQ YRQ LVW ZlKOEDU 7KH IXQFWLRQ RI FDQ EH VHOHFWHG 3RVVLELOLWp GH VpOHFWLRQHHU...

Page 49: ...teur pour E9 K22 EVU Sperrsch tz Utility blocking contactor Contacteur de coupure du fournisseur d nergie K23 SPR Hilfsrelais SPR auxiliary relay Relais auxiliaire SPR M1 Verdichter Compressor Compres...

Page 50: ...A XII Anhang Appendix Annexes 3 5 3 5 Steuerung Control Commande WI 27TE 1HW 0DLQV 5pVHDX...

Page 51: ...ZLWKRXW XWLOLW EORFN GR QRW UHTXLUH D GLUHFW LQIHHG IRU WKH ZHOO SXPS 0RGLILHU OH FkEODJH O DOLPHQWDWLRQ GLUHFWH GH OD SRPSH GH SXLWV Q HVW SDV REOLJDWRLUHPHQW QpFHVVDLUH SRXU OHV LQVWDOODWLRQV VDQV...

Page 52: ...X HL VWDE PPHUVLRQ KHDWHU 7KHUPRSORQJHXU LH XQNWLRQ YRQ LVW ZlKOEDU 7KH IXQFWLRQ RI FDQ EH VHOHFWHG 3RVVLELOLWp GH VpOHFWLRQHHU OD IRQFWLRQ GH WHU 6SHUUHLQJDQJ RQWDNW RIIHQ 3 JHVSHUUW U FNH EHL HGDUI...

Page 53: ...pump Circulateur de chauffage M15 2 Heizkreisumw lzpumpe 2nd heating circuit circulating pump 2e circulateur circuit de chauffage M16 Zusatzumw lzpumpe Auxiliary circulating pump Circulateur suppl me...

Page 54: ...es Prinzipschema Hydraulic Plumbing Diagram Sch ma hydraulique 4 1 Monovalente W rmepumpenanlage mit einem Heizkreisen Monovalent heat pump system with one heating circuits Installation monovalente de...

Page 55: ...e W rmepumpenanlage mit einem Heizkreisen und Warmwasserbereitung Monovalent heat pump system with one heating circuits and domestic hot water preparation Installation monovalente de pompe chaleur ave...

Page 56: ...lexible connection hose Tuyau de raccord flexible R ckschlagklappe Check valve Clapet anti retour Wasser Wasser W rmepumpe Water to water heat pump Pompe chaleur eau eau Reihen Pufferspeicher Buffer t...

Page 57: ...EMV Richtlinie 2004 108 EG Druckger terichtlinie 97 23 EG EC Directives Low voltage directive 2006 95 EC EMC directive 2004 108 EC Pressure equipment directive 97 23 EC Directives CEE Directive Basse...

Page 58: ...A XX Anhang Appendix Annexes 5...

Page 59: ...www dimplex de A XXI Anhang Appendix Annexes 5...

Page 60: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Reviews: