SIH 90TU
English
13 Product information as per
Regulation (EU) No 813/
2013, Annex II, Table 2
Information requirements for heat pump space heaters and heat pump combination heaters
Item
Symbol
Value
Unit
Item
Symbol
Value
Unit
Tj = - 7°C
P
dh
85,3
kW
Tj = - 7°C
COP
d
3,03
-
Tj = + 2°C
P
dh
86,6
kW
Tj = + 2°C
COP
d
3,44
-
Tj = + 7°C
P
dh
87,4
kW
Tj = + 7°C
COP
d
3,75
-
Tj = + 12°C
P
dh
88,2
kW
Tj = + 12°C
COP
d
4,11
-
Tj = bivalent temperature
P
dh
84,9
kW
Tj = bivalent temperature
COP
d
2,93
-
Tj = operation limit temperature
P
dh
84,9
kW
Tj = operation limit temperature
COP
d
2,93
-
For air-to-water heat pumps
For air-to-water heat pumps:
Tj = -15°C (if TOL < -20°C)
P
dh
84,9
kW
Tj = -15°C (if TOL < -20°C)
COP
d
2,93
-
Bivalent temperature
T
biv
-10
°C
For air-to-water heat pumps:
Operation limit temperature
TOL
-10
°C
Cycling interval capacity for heating
P
cych
-
kW
Cycling interval efficiency
COP
cyc
-
-
Degradation co-efficient (**)
C
dh
0,90
-
Heating water operating limit
temperature
WTOL
70
°C
Power consumption in modes other than active mode
Supplementary heater
Off mode
P
OFF
0,015
kW
Rated heat output (*)
P
sup
0
kW
Thermostat-off mode
P
TO
0,020
kW
Type of energy input
eletrical
Standby mode
P
SB
0,015
kW
Crankcase heater mode
P
CK
0,130
kW
Other items
Capacity control
fixed
-
--
m³ /h
Sound power level, indoors/ outdoors
L
WA
70/--
dB
-
15,5
m³ /h
Emissions of nitrogen oxides
NO
x
-
mg/kWh
Declared load profile
--
Water heating energy efficiency
η
wh
--
%
Daily electricity consumption
Q
elec
--
kWh
Daily fuel consumption
Q
fuel
--
kWh
Contact details
(**) If C
dh
is not determined by measurement nthen the default degradation is C
dh
= 0,9
(--) not applicable
Model
SIH 90TU
Air-to-water heat pump
no
Water-to-water heat pump
no
Brine-to-water heat pump
yes
Low-temperature heat pump
no
Equipped with a supplementary heater
no
130
%
Heat pump combination heater
no
Parameters shall be declared for medium-temperature application, except for low-temperature heat pumps. For low- temperature heat pumps, parameters
shall be declared for low-temperature application.
Rated heat output (*)
Prated
85
kW
Seasonal space heating energy
efficiency
η
s
Parameters shall be declared for average climate conditions:
For air-to-water heat pumps: Rated
air flow rate, outdoors
For water-/brine-to-water heat
pumps: Rated brine or water flow
rate, outdoor heat exchanger
Declared capacity for heating foer part load at indoor temperature 20°C and
outdoor temperature T
j
Declared coefficient of performance or primary energy ratio for part load at
indoor temperature 20 °C and outdoor temperature T
j
For heat pump combination heater:
Glen Dimplex Deutschland GmbH, Am Goldenen Feld 18, 95326 Kulmbach
(*) For heat pump space heaters and heat pump combination heaters, the rated output P
rated
is equal to the design load for heating P
designh
, and the rated
heat output of a supplementary capacity for heating sup(
Tj
).