SIH 90TU
English
12 Device information
1
Type and order code
SIH 90TU
2
Design
Heat source
Brine
2.1
Model
Universal
2.2
Controller
integrated
2.3
Thermal energy meter
Integrated
2.4
Installation location
Indoors
2.5
Performance levels
2
3
Operating limits
3.1
Heating water flow
°C
20 to 70 ±2
1
3.2
Brine (heat source)
°C
-5 to +25
3.3
Antifreeze
Monoethylene glycol
3.4
Minimum brine concentration (-13 °C freezing temperature)
25%
4
Flow / sound
4.1
Heating water flow / free compression
Nominal flow in accordance with EN 14511at B0...-3 / W35...30
m³/h / Pa
15.4 / 64800
at B0...-3 / W45...40
m³/h / Pa
15.1 / 66700
at B0...-3 / W55...47
m³/h / Pa
9.2 / 96100
at B0...-3 / W65...55
m³/h / Pa
7.5 / 103200
Minimum heating water flow
m³/h / Pa
7.5 / 103200
4.2
Brine flow / free compression
Nominal flow in accordance with EN 14511at B0...-3 / W35...30
m³/h / Pa
20.7 / 70000
at B0...-3 / W45...40
m³/h / Pa
19.6 / 74800
at B0...-3 / W55...47
m³/h / Pa
17.0 / 86400
at B0...-3 / W65...55
m³/h / Pa
15.5 / 93400
Minimum brine flow rate
m³/h / Pa
15.5 / 93400
4.3
Sound power level according to EN 12102
dB(A)
70
4.4
Sound pressure level at a distance of 1m
2
dB(A)
55
5
Dimensions, weight and filling quantity
5.1
Device dimensions
3
H x W x L mm
1890 x 1350 x 750
5.2
Weight of the transportable unit(s) incl. packaging
kg
807
5.3
Device connections for heating
inches
Rp 2''
5.4
Device connections for heat source
Inches
Rp 3''
5.5
Refrigerant / total filling weight
type/kg
R134a / 24.5
5.6
GWP value / CO
2
equivalent
--- / t
1430 / 35
5.7
Refrigeration circuit hermetically sealed
yes
5.8
Lubricant / total filling quantity
type/litres
Polyolester (POE)/16.0
5.9
Volume of heating water in device
Litres
22.9
5.10 Volume of heat transfer medium in device
Litres
23.8
6
Electrical connection
6.1
Supply voltage / fuse protection
3~/PE 400 V (50 Hz) / C 100A
6.2
Control voltage / fuse protection
1~/N/PE 230 V (50 Hz) / C 13A
6.3
Degree of protection according to EN 60 529
IP 21
6.4
Starting current with soft starter
A
120
6.5
Nominal power consumption B0 W35 / max. power consumption
4
kW
20.4 / 45.0
6.6
Nominal current B0 W35 / cos
A / ---
45.5 / 0.64
6.7
Max. power consumption of compressor protection
(per compressor)
W
130 / thermostatically controlled
6.8
Power consumption of pumps
kW
up to 1.3