7.3 Heat Source Connection

The following procedure must be observed when connecting the
heat source:
Connect the brine pipe to the heat pump flow and return.
The hydraulic plumbing diagram must be adhered to.

ATTENTION!

The supplied dirt trap must be inserted in the heat source inlet of the heat
pump to protect the evaporator against the ingress of impurities.

In addition, a micro bubble air separator must be installed in the
heat source system.
The brine liquid must be produced prior to charging the system.
The liquid must have an antifreeze concentration of at least 25 %
to ensure frost protection down to -14 °C.
Only monoethylene glycol or propylene glycol-based antifreeze
may be used.
The heat source system must be de-aerated and checked for
leaks.

ATTENTION!

The brine solution must contain at least a 25 % concentration of a
monoethylene glycol or propylene glycol-based antifreeze, which must
be mixed before filling. 

7.4 Electrical Connection

The following electrical connections must be established on the
heat pump:

„

Connection of the control line to the control panel of the heat
pump via terminal X1: L/N/PE.

„

Connection of the mains cable to the control panel of the
heat pump via terminal X6: L1/L2/L3/PE.

„

Connection of the brine circulating pump (to be provided by
the customer) to the control panel of the heat pump via ter-
minal X1: PE and pump contactor K5: 2/4/6.

All electrical components required for the operation of the heat
pump are located on the control panel.
For detailed instructions on how to connect the heat pump con-
troller and how it functions (e.g. external wall sensor included in
the scope of supply), please refer to the operating manual sup-
plied with the controller.
An all-pole disconnecting device with a contact gap of at least
3 mm (e.g. utility blocking contactor or power contactor) as well
as a 3-pole circuit breaker with common tripping for all external
conductors have to be provided by the customer. The required
conductor cross-section is to be selected according to the power
consumption of the heat pump, the technical connection require-
ments of the respective utility company as well as all applicable
regulations. Details on the power consumption of the heat pump
are listed on both the product information sheet and the type
plate. The connection terminals are designed for a max. conduc-
tor cross-section of 10 mm².

ATTENTION!

Observe the clockwise rotating field when connecting the mains cable (if
rotating field is not clockwise, the heat pump will not work properly and
will be very noisy).

8 Start-UP

8.1 General Information

To ensure that start-up is performed correctly, it should only be
carried out by an after-sales service technician authorised by the
manufacturer. This may be a condition for extending the guaran-
tee (see Warranty Service).

8.2 Preparation

The following items need to be checked prior to start-up:

„

The heat pump must be fully connected, as described in
Chapter 7.

„

The heat source system and the heating circuit must have
been filled and checked.

„

The dirt trap must have been inserted in the brine inlet of the
heat pump.

„

All valves that could impair proper flow in the brine and heat-
ing circuits must be open.

„

The heat pump controller must be adapted to the heating
system in accordance with the controller's operating instruc-
tions.

8.3 Start-Up Procedure

The heat pump is started up via the heat pump controller.

ATTENTION!

The heat pump must be started up in accordance with the installation and
operating instructions of the heat pump controller.

If an overflow valve is fitted to maintain the minimum heating
water flow rate, the valve must be adapted to the requirements of
the heating system. Incorrect adjustment can lead to faulty oper-
ation and increased energy consumption. We recommend carry-
ing out the following procedure to correctly adjust the overflow
valve:
Close all of the heating circuits that may also be closed during
operation so that the most unfavourable operating state - with re-
spect to the water flow rate - is achieved. This normally means
the heating circuits of the rooms on the south and west sides of
the building. At least one heating circuit must remain open (e.g.
bathroom).
The overflow valve should be opened far enough to produce the
maximum temperature spread between the heating flow and re-
turn flow listed in the table below for the current heat source tem-
perature. The temperature spread should be measured as close
as possible to the heat pump. The heating element of mono en-
ergy systems should be disconnected.

Any faults occurring during operation are displayed on the heat
pump controller and can be corrected as described in the heat
pump controller's operating instructions.

Heat source
temperature

Max. temperature spread

between heating flow and return 

flow

From

To

-5° C

0° C

10 K

1° C

5° C

11 K

6° C

9° C

12 K

10° C

14° C

13 K

15° C

20° C

14 K

21° C

25° C

15 K

Summary of Contents for SI 11BS

Page 1: ...er Heat Pump for Indoor Installation Pompe à chaleur eau glycolée eau pour installation intérieure Montage und Gebrauchsanweisung Deutsch English Français Instructions d installation et d utilisation Installation and Operating Instructions Bestell Nr Order no No de commande 452232 66 07 FD 8607 ...

Page 2: ......

Page 3: ...Aufstellung D 4 6 1 Allgemeine Hinweise D 4 6 2 Schallemissionen D 4 7 Montage D 4 7 1 Allgemein D 4 7 2 Heizungsseitiger Anschluss D 4 7 3 Wärmequellenseitiger Anschluss D 4 7 4 Elektrischer Anschluss D 5 8 Inbetriebnahme D 5 8 1 Allgemein D 5 8 2 Vorbereitung D 5 8 3 Vorgehensweise bei Inbetriebnahme D 5 9 Pflege Reinigung D 6 9 1 Pflege D 6 9 2 Reinigung Heizungsseite D 6 9 3 Reinigung Wärmeque...

Page 4: ...e ist entsprechend den einschlägigen Vorschrif ten in die Wärmequellen und Heizungsanlage einzubinden 1 3 Energiesparende Handhabung der Wärmepumpe Durch das Betreiben dieser Wärmepumpe tragen Sie zur Scho nung unserer Umwelt bei Für den effizienten Betrieb ist eine sorgfältige Bemessung der Heizungsanlage und der Wärme quelle sehr wichtig Dabei ist besonderes Augenmerk auf mög lichst niedrige Was...

Page 5: ...en 1 Verflüssiger 2 Verdichter 3 Schaltblech 4 Verdampfer 4 Zubehör 4 1 Soleverteiler Der Soleverteiler vereinigt die Kollektorschleifen der Wärmequel lenanlage zu einer Hauptleitung welche an die Wärmepumpe angeschlossen wird Mittels der integrierten Kugelhähne können zum Entlüften einzelne Solekreise abgesperrt werden 5 Transport Zum Transport auf ebenem Untergrund eignet sich ein Hubwa gen Muss...

Page 6: ...ngsseitiger Installation ist die Heizungsan lage zu füllen zu entlüften und abzudrücken Die im Schaltkasten angeschlossenen und lose eingelegten Füh ler müssen wie im Prinzipschema dargestellt angebracht und isoliert werden Mindestheizwasserdurchsatz Der Mindestheizwasserdurchsatz der Wärmepumpe ist in jedem Betriebszustand der Heizungsanlage sicherzustellen Dieses kann z B durch Installation eine...

Page 7: ...ung Vor der Inbetriebnahme müssen folgende Punkte geprüft wer den Alle Anschlüsse der Wärmepumpe müssen wie in Kapitel 7 beschrieben montiert sein Die Wärmequellenanlage und der Heizkreis müssen gefüllt und geprüft sein Der Schmutzfänger muss im Soleeintritt der Wärmepumpe eingebaut sein Im Sole und Heizkreislauf müssen alle Schieber die den korrekten Fluss behindern könnten geöffnet sein Der Wärm...

Page 8: ...sigers anzuschlie ßen Danach muss mit geeigneten neutralisierenden Mitteln gründlich nachgespült werden um Beschädigungen durch even tuell im System verbliebene Reinigungsmittelreste zu verhin dern Die Säuren sind mit Vorsicht anzuwenden und es sind die Vor schriften der Berufsgenossenschaften einzuhalten Im Zweifelsfall ist mit dem Hersteller des Reinigungsmittels Rücksprache zu halten 9 3 Reinig...

Page 9: ...6 56 56 3 5 Heizwasserdurchfluss bei interner Druckdifferenz m h Pa 0 45 1900 0 6 3300 0 75 2300 1 0 4100 1 3 4800 3 6 Soledurchsatz bei interner Druckdifferenz Wärmequelle m h Pa 1 2 16000 1 7 29500 2 3 25000 3 0 24000 3 5 20000 3 7 Kältemittel Gesamt Füllgewicht Typ kg R407C 1 0 R407C 0 9 R407C 1 3 R407C 1 4 R407C 1 7 4 Abmessungen Anschlüsse und Gewicht 4 1 Geräteabmessungen ohne Anschlüsse 2 H...

Page 10: ...ene Teile und Geräte Anlagenmängel die auf nicht vom Lieferer bezogene Teile zurückzuführen sind fallen nicht unter den Garantieanspruch Sofern der Mangel nicht beseitigt werden kann oder die Nach besserung von uns abgelehnt oder unzumutbar verzögert wird wird der Hersteller entweder kostenfreien Ersatz liefern oder den Minderwert vergüten Im Falle einer Ersatzlieferung behalten wir uns die Gelten...

Page 11: ...rt E 3 6 Set UP E 4 6 1 General information E 4 6 2 Acoustic Emissions E 4 7 Installation E 4 7 1 General Information E 4 7 2 Heating System Connection E 4 7 3 Heat Source Connection E 5 7 4 Electrical Connection E 5 8 Start UP E 5 8 1 General Information E 5 8 2 Preparation E 5 8 3 Start Up Procedure E 5 9 Maintenance and Cleaning E 6 9 1 Maintenance E 6 9 2 Cleaning the Heating System E 6 9 3 Cl...

Page 12: ... be observed The heat pump is to be connected to the heat source system and the heating system in accordance with all applicable regulations 1 3 Energy Efficient Use of the Heat Pump By operating this heat pump you are helping to protect our envi ronment Both the heating system and the heat source must be properly designed and dimensioned to ensure efficient operation It is particularly important ...

Page 13: ... the collector and the brine cir cuit manifold 1 Liquifier 2 Compressor 3 Control panel 4 Evaporator 4 Accessories 4 1 Brine circuit manifold The brine circuit manifold merges the individual collector loops of the heat source system into a single main pipe which is con nected to the heat pump Integrated ball valves allow the individ ual brine circuits to be shut off for de aeration purposes 5 Tran...

Page 14: ...m prior to connecting the heat pump Before connecting the heating water system to the heat pump the heating system must be flushed to remove any impurities residue from sealants etc Any accumulation of deposits in the liquifier could cause the heat pump to completely break down Once the heating system has been installed it must be filled de aerated and pressure tested The sensors which are deliver...

Page 15: ...for a max conduc tor cross section of 10 mm ATTENTION Observe the clockwise rotating field when connecting the mains cable if rotating field is not clockwise the heat pump will not work properly and will be very noisy 8 Start UP 8 1 General Information To ensure that start up is performed correctly it should only be carried out by an after sales service technician authorised by the manufacturer Th...

Page 16: ...m circuit we recommend connecting the flushing device di rectly to the flow and return flow of the liquifier It is important that the system be thoroughly flushed using appropriate neutralising agents to prevent any damage from being caused by cleaning agent residue remaining in the system Acids must be used with great care and all relevant regulations of the employers liability insurance associat...

Page 17: ... flow with an internal pressure differential of m h Pa 0 45 1900 0 6 3300 0 75 2300 1 0 4100 1 3 4800 3 6 Brine throughput with an internal pressure differential heat source of m h Pa 1 2 16000 1 7 29500 2 3 25000 3 0 24000 3 5 20000 3 7 Refrigerant total filling weight type kg R407C 1 0 R407C 0 9 R407C 1 3 R407C 1 4 R407C 1 7 4 Dimensions connections and weight 4 1 Device dimensions without conne...

Page 18: ...F 4 6 1 Généralités F 4 6 2 Emissions sonores F 4 7 Installation F 4 7 1 Remarques d ordre général F 4 7 2 Branchement côté installation de chauffage F 4 7 3 Raccordement côté source de chaleur F 4 7 4 Branchements électriques F 5 8 Mise en service F 5 8 1 Remarques d ordre général F 5 8 2 Préparation F 5 8 3 Procédures à suivre à la mise en service F 5 9 Entretien nettoyage F 6 9 1 Entretien F 6 ...

Page 19: ... de chauf fage et de source de chaleur en conformité avec les prescrip tions afférentes 1 3 Utilisation de la pompe à chaleur pour économiser de l énergie En utilisant cette pompe à chaleur vous contribuez à préserver l environnement Pour obtenir un fonctionnement efficace il est très important de dimensionner précisément l installation de chauffage et la source de chaleur Dans cette optique en mo...

Page 20: ...enseur 2 Compresseur 3 Panneau de commande 4 Evaporateur 4 Accessoires 4 1 Distributeur d eau glycolée Le distributeur d eau glycolée réunit les boucles du collecteur de l installation de source de chaleur pour former une conduite prin cipale qui elle est raccordée à la pompe à chaleur Les robinets à boisseau sphérique intégrés permettent de couper chaque cir cuit d eau glycolée pour permettre une...

Page 21: ...s des ma tériaux d étanchéité ou autres Une accumulation de dépôts di vers dans le condenseur est susceptible d entraîner une dé faillance totale de la pompe à chaleur Une fois le montage côté chauffage terminé l installation de chauffage devra être remplie purgée et éprouvée à la pression Les sondes livrées dans le boîtier de commande doivent être fixées et isolées selon le schéma de principe en ...

Page 22: ...ise en service en règle cette dernière doit être effectuée par un service après vente agréé par le construc teur Ceci permet de prolonger la garantie sous certaines condi tions 8 2 Préparation Avant la mise en service il est impératif de procéder aux vérifica tions suivantes tous les raccordements de la pompe à chaleur doivent être réalisés comme décrit au chapitre 7 l installation de source de ch...

Page 23: ...e départ et le retour du condenseur de la pompe à chaleur Il faut ensuite soigneusement rincer à l aide de produits neutralisants adé quats afin d éviter tous dommages provoqués par d éventuels restes de produits de nettoyage dans le système Les acides doivent être utilisés avec précaution et les prescrip tions des caisses de prévoyance des accidents doivent être res pectées En cas de doute prendr...

Page 24: ... 56 56 56 3 5 Débit d eau de chauffage avec pression diff int m h Pa 0 45 1900 0 6 3300 0 75 2300 1 0 4100 1 3 4800 3 6 Débit eau glycolée avec pression diff int source chaleur m h Pa 1 2 16000 1 7 29500 2 3 25000 3 0 24000 3 5 20000 3 7 Fluide frigorigène poids au remplissage total type kg R407C 1 0 R407C 0 9 R407C 1 3 R407C 1 4 R407C 1 7 4 Dimensions raccordements et poids 4 1 Dimensions de l ap...

Page 25: ...cteristic Curves Courbes caractéristiques SI 11BS A VI 2 5 Kennlinien Characteristic Curves Courbes caractéristiques SI 14BS A VII 3 Stromlaufpläne Circuit Diagrams Schémas électriques A VIII 3 1 Steuerung Control Commande A VIII 3 2 Last Load Charge A IX 3 3 Anschlussplan Circuit Diagram Schéma électrique A X 3 4 Legende Legend Légende A XI 4 Hydraulisches Prinzipschema Hydraulic Plumbing Diagram...

Page 26: ...pOHFWULTXHV FD DSSUR HQY lUPHTXHOOH XVJDQJ DXV 3 X HQJHZLQGH HDW VRXUFH HDW SXPS RXWOHW H WHUQDO WKUHDG 6RXUFH GH FKDOHXU 6RUWLH GH OD 3 LOHWDJH H WpULHXU HL XQJVYRUODXI XVJDQJ DXV 3 X HQJHZLQGH HDWLQJ ZDWHU IORZ HDW SXPS RXWOHW H WHUQDO WKUHDG OOHU HDX GH FKDXIIDJH 6RUWLH GH OD 3 LOHWDJH H WpULHXU HL XQJVU FNODXI LQJDQJ LQ 3 X HQJHZLQGH HDWLQJ ZDWHU UHWXUQ IORZ HDW SXPS LQOHW H WHUQDO WKUHDG 5HWR...

Page 27: ...H SUHVVLRQ HQ 3D UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ 6ROHGXUFKIOXVV LQ P K ULQH IORZ UDWH LQ P K pELW G HDX JO FROpH HQ P K HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH ...

Page 28: ...OXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ 6ROHGXUFKIOXVV LQ P K ULQH IORZ UDWH LQ P K pELW G HDX JO FROpH HQ P K HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU ...

Page 29: ...UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ 6ROHGXUFKIOXVV LQ P K ULQH IORZ UDWH LQ P K pELW G HDX JO FROpH HQ P K HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPS...

Page 30: ...UOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ 6ROHGXUFKIOXVV LQ P K ULQH IORZ UDWH LQ P K pELW G HDX JO FROpH HQ P K HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU...

Page 31: ...D UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ 6ROHGXUFKIOXVV LQ P K ULQH IORZ UDWH LQ P K pELW G HDX JO FROpH HQ P K HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWH...

Page 32: ...A VIII Anhang Appendix Annexes 3 3 Stromlaufpläne Circuit Diagrams Schémas électriques 3 1 Steuerung Control Commande 1HW 0DLQV 5pVHDX ...

Page 33: ... Â 0DLQV Â 5pVHDX 6DQIWDQODVVHU QLFKW YRUKDQGHQ LQ 6 6 XQG 6 6 1R VRIW VWDUWHU SUHVHQW LQ 6 6 DQG 6 6 H GpPDUUHXU SURJUHVVLI Q HVW SDV GLVSRQLEOH SRXU OHV YHUVLRQV 6 6 HW 6 6 9RU GHP LQNOHPPHQ GHV 0 0RWRUVFKXW HV GLH UDKWEU FNH HQWIHUQHQ LVW GLH U FNH 6W UXQJ 0 5HPRYH ZLUH MXPSHU EHIRUH LQVWDOOLQJ WKH 0 PRWRU SURWHFWLRQ LV WKH 0 IDXOW EULGJH QOHYHU OH SRQW j ILO DYDQW GH UDFFRUGHU OD SURWHFWLRQ GH...

Page 34: ...HG E FXVWRPHU WR EH FRQQHFWHG DV UHTXLUHG UDFFRUGHU VL EHVRLQ HVW SDU OH SURSULpWDLUH RQWDNW RIIHQ 3 JHVSHUUW RQWDFW RSHQ 3 GLVDEOHG RQWDFW RXYHUW 3 EORTXpH LH XQNWLRQ YRQ LVW ZlKOEDU 7KH IXQFWLRQ RI FDQ EH VHOHFWHG 3RVVLELOLWp GH VpOHFWLRQHHU OD IRQFWLRQ GH WHU 6SHUUHLQJDQJ RQWDNW RIIHQ 3 JHVSHUUW U FNH EHL HGDUI HQWIHUQHQ QG GLVDEOH LQSXW RQWDFW RSHQ 3 GLVDEOHG ULGJH FDQ EH UHPRYHG DFFRUGLQJ WR ...

Page 35: ... sur N11 K20 Schütz 2 Wärmeerzeuger Contactor for heat generator 2 Contacteur 2e générateur de chaleur K21 Schütz Tauchheizkörper Warmwasser Contactor for immersion heater hot water Contacteur du thermoplongeur eau chaude K22 EVU Sperrschütz Utility blocking contactor Contacteur de coupure du fournisseur d énergie K23 SPR Hilfsrelais SPR auxiliary relay Relais auxiliaire SPR M1 Verdichter Compress...

Page 36: ...A XII Anhang Appendix Annexes 4 4 Hydraulisches Prinzipschema Hydraulic Plumbing Diagram Schéma hydraulique 4 1 Darstellung Schematic View Représentation ...

Page 37: ...eur Pufferspeicher Buffer tank Réservoir tampon Wärmepumpenregler Heat pump controller Régulateur de pompe à chaleur Elektroverteilung Electrical distribution system Distributeur courant électrique Warmwasserspeicher Hot water cylinder Ballon d eau chaude Erdreichkollektoren Erdwärmesonden Ground heat collectors Borehole heat exchangers Collecteurs géothermiques Sondes géothermiques Soleverteiler ...

Page 38: ...A XIV Anhang Appendix Annexes 5 5 Konformitätserklärung Declaration of Conformity Déclaration de conformité ...

Page 39: ...www dimplex de A XV Anhang Appendix Annexes 5 ...

Page 40: ...tschland GmbH Geschäftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrtümer und Änderungen vorbehalten Subject to alterations and errors Sous réserve d erreurs et modifications 49 0 9221 709 565 www dimplex de ...

Reviews: