9.2 Heating Function

Start the heat pump by moving the switch (1) to the on position
(I). Preselect heating operation by moving the switch (2) to the
heating position ( ). Turn the rotary knob (4) to set the desired
return flow temperature. The potentiometer can be used to re-
quest a temperature in the range between a min. of 20 °C and a
max. of 55 °C. The actual temperature can be read from the indi-
cator (3) on the control panel. Once the set temperature is
reached, the heat pump switches off. The heat pump switches on
again when the return flow temperature falls to 4 Kelvin below
the set value. It is not possible to re-start the heat pump until after
a minimum pause time of 5 minutes. If the flow temperature is
higher than 60 °C or the brine temperature is too low, the heat
pump switches off.

9.3 Cooling Function

Start the heat pump by moving the switch (1) to the on position
(I). Preselect cooling operation by moving the switch (2) to the
cooling position ( ). Turn the rotary knob (4) to set the desired
return flow temperature. The potentiometer can be used to re-
quest a temperature in the range between a min. of 12 °C and a
max. of 25 °C. Once the set temperature is reached, the heat
pump switches off. The heat pump switches on again when the
return flow temperature rises to 4 Kelvin above the set value. It is
not possible to re-start the heat pump until after a minimum pe-
riod of 5 minutes. If the flow temperature is under 7 °C, the heat
pump switches off.
To prevent condensation from forming on the system’s cooling
surfaces, we recommend installing dew point monitors at vulner-
able points in the cooling distribution system. Connect them to
the terminal X1 (1,2). If condensation then forms, the cooling of
the system is interrupted.

9.4 Hot Water Function

This heat pump can also be used to heat hot water.
 Hot water preparation is requested via the terminal “X1-9” using
an external thermostat to be provided by the customer. This ther-
mostat simultaneously switches on the phase (L) to terminal
“X1-9” and the hot water circulating pump.
A suitable thermostat is available as an accessory.
Hot water preparation can also be requested even if neither heat-
ing and cooling have been requested.
If a request is pending, the heat circulating pump is switched off
by the control system. The cooling operation is interrupted and
the setpoint is raised to the maximum.
The external thermostat determines the hot water setpoint tem-
perature.
Set the temperature to approx. 10 K under the maximum flow
temperature of the heat pump to prevent the high-pressure con-
troller from initiating a switch-off.
When the preparation of hot water is concluded, the system will
continue working in the same function as before the request.

10 Maintenance and 

Cleaning 

10.1 Maintenance

The heat pump is maintenance-free. To prevent faults due to
sediment in the heat exchangers, care must be taken to ensure
that no impurities can enter either the heat source system or the
heating system. In the event that operating malfunctions due to
contamination occur nevertheless, the system should be cleaned
as described below.

10.2 Cleaning of Heating Side

The ingress of oxygen into the heating water circuit, in particular
if it contains steel components, may result in the formation of ox-
idation products (rust). These can enter the heating system via
valves, circulating pumps or plastic tubing. It is therefore impor-
tant - in particular with respect to the piping of underfloor heating
systems - that the installation be executed in a diffusion-proof
manner.

ATTENTION!

To prevent the accumulation of deposits (e.g. rust) we recommend using
a suitable corrosion protection system.

In the case of severe contamination leading to a reduction in the
performance of the condenser in the heat pump, the system must
be cleaned by a heating technician.
Based on current knowledge, we recommend cleaning with a 5%
phosphoric acid solution or, in the case that cleaning needs to be
performed more frequently, with a 5% formic acid solution.
In either case, the cleaning fluid should be at room temperature.
It is recommended that the heat exchanger be cleaned in the di-
rection opposite to the normal flow direction.
To prevent acidic cleaning agents from entering the circuit of the
heating installation we recommend that the flushing device be fit-
ted directly to the supply and return lines of the condenser of the
heat pump.
Thereafter the system must be thoroughly flushed using appro-
priate neutralising agents in order to prevent any damage caused
by cleaning agent residues that may still be present in the sys-
tem.
All acids must be used with great care, all relevant regulations of
the employers' liability insurance associations must be adhered
to.
If in doubt, contact the manufacturer of the chemicals!

10.3 Cleaning the Heat Source 

System

ATTENTION!

Insert a dirt trap in the heat source inlet of the heat pump to protect the
evaporator against the ingress of impurities.

Clean the dirt trap's filter screen one day after start-up and sub-
sequently at weekly intervals. If no more signs of contamination
are evident, the filter can be removed to reduce pressure drops.

Summary of Contents for SI 10 MR

Page 1: ...o Water Heat Pump for Indoor Installation Pompe à chaleur eau glycolée eau pour installation intérieure Montage und Gebrauchsanweisung Deutsch English Français Instructions d installation et d utilisation Installation and Operating Instructions Bestell Nr Order no No de commande 452233 66 02 FD 8806 ...

Page 2: ......

Page 3: ...lemissionen D 4 7 Montage D 5 7 1 Allgemein D 5 7 2 Heizungsseitiger Anschluss D 5 7 3 Wärmequellenseitiger Anschluss D 5 7 4 Elektrischer Anschluss D 5 8 Inbetriebnahme D 6 8 1 Allgemein D 6 8 2 Vorbereitung D 6 8 3 Vorgehensweise bei Inbetriebnahme D 6 9 Funktionsbeschreibung Steuerung D 6 9 1 Bedienelemente D 6 9 2 Funktion Heizen D 7 9 3 Funktion Kühlen D 7 9 4 Funktion Warmwasser D 7 10 Pfleg...

Page 4: ... Produktschriften Än derungen oder Umbauten am Gerät sind zu unterlassen 1 3 Gesetzliche Vorschriften und Richtlinien Die Wärmepumpe entspricht allen relevanten DIN VDE Vor schriften und EG Richtlinien Diese können der CE Erklärung im Anhang entnommen werden Der elektrische Anschluss der Wärmepumpe muss nach den gül tigen VDE EN und IEC Normen ausgeführt werden Zusätzlich sind die Anschlussbedingu...

Page 5: ...n wird größtenteils dem Kältemittel zugeführt Daraufhin gelangt das Kältemittel in den Verflüssiger und über trägt hier wiederum seine Wärmeenergie an das Heizwasser Abhängig vom Betriebspunkt erwärmt sich so das Heizwassser auf bis zu 60 C Kühlen In der Betriebsart Kühlen werden Verdampfer und Verflüssiger in ihrer Wirkungsweise umgekehrt Das Heizwasser gibt über den nun als Verdampfer arbeitende...

Page 6: ...e kann ein handelsübliches Rohr dienen ACHTUNG Gerät nicht an den Bohrungen in den Verkleidungsblechen anheben 6 Aufstellung 6 1 Allgemeine Hinweise Das Gerät ist grundsätzlich in Innenräumen auf einer ebenen glatten und waagerechten Fläche aufzustellen Dabei sollte der Rahmen rundum dicht am Boden anliegen um eine geeignete Schallabdichtung zu gewährleisten Ist dies nicht der Fall kön nen zusätzl...

Page 7: ...luss Folgende Vorgehensweise ist beim Anschluss einzuhalten Die Soleleitung am Vor und Rücklauf der Wärmepumpe an schließen ACHTUNG Im Wärmequelleneintritt der Wärmepumpe ist ein Schmutzfänger zu montieren um den Verdampfer gegen Verunreinigungen zu schützen Zusätzlich muss ein Entlüfter am höchsten Punkt der Wärme quellenanlage eingebaut werden Die Sole ist vor dem Befüllen der Anlage herzustelle...

Page 8: ...z B Bad Das Überströmventil ist so weit zu öffnen dass sich bei der aktu ellen Wärmequellentemperatur die in der unten stehenden Ta belle angegebene maximale Temperaturspreizung zwischen Heizungsvor und Rücklauf ergibt Die Temperaturspreizung ist möglichst nahe an der Wärmepumpe zu messen Bei monoener getischen Anlagen ist der Heizstab zu deaktivieren 9 Funktionsbeschreibung Steuerung 9 1 Bedienel...

Page 9: ...tur sollte ca 10 K unter der max Vor lauftemperatur der Wärmepumpe eingestellt werden um ein Ab schalten über den Hochdruckpressostaten zu verhindern Nach Beendigung der Warmwasserbereitung wird in der glei chen Funktion weitergearbeitet wie vor der Anforderung 10 Pflege Reinigung 10 1 Pflege Die Wärmepumpe arbeitet wartungsfrei Um Betriebsstörungen durch Schmutzablagerungen in den Wärmeaustausche...

Page 10: ... dürfen nur vom autorisierten und sachkundigen Kundendienst durchgeführt werden ACHTUNG Vor öffnen des Gerätes sind alle Stromkreise spannungsfrei zu schalten 12 Außerbetriebnahme Entsorgung Bevor die Wärmepumpe ausgebaut wird ist die Maschine span nungsfrei zu schalten und abzuschiebern Umweltrelevante An forderungen in Bezug auf Rückgewinnung Wiederverwendung und Entsorgung von Betriebsstoffen u...

Page 11: ... 11 4 5 5 11 6 5 7 11 4 5 5 bei B10 W18 kW 12 4 6 7 12 2 6 6 14 1 6 5 13 8 6 3 14 1 6 5 13 8 6 3 3 5 Schall Leistungspegel dB A 54 55 56 3 6 Heizwasserdurchfluss bei interner Druckdifferenz m h Pa 0 75 2300 1 55 9700 1 0 4100 1 95 16000 1 0 4100 1 95 16000 3 7 Freie Pressung Heizungsumwälzungspumpe max Stufe Pa 44700 41000 41000 3 8 Soledurchsatz bei interner Druckdifferenz Wärmequelle m h Pa 2 3 ...

Page 12: ...17 8 6 2 21 9 5 9 21 7 5 7 bei B10 W18 kW 17 4 7 1 17 1 6 9 21 5 7 3 21 3 7 1 27 7 7 1 27 5 6 9 3 5 Schall Leistungspegel dB A 56 56 56 3 6 Heizwasserdurchfluss bei interner Druckdifferenz m h Pa 1 3 4850 2 3 13000 1 5 4000 2 8 13000 1 6 3400 3 5 13000 3 7 Freie Pressung Heizungsumwälzungspumpe max Stufe Pa 34900 61700 61300 3 8 Soledurchsatz bei interner Druckdifferenz Wärmequelle m h Pa 3 5 1790...

Page 13: ...er bezogene Teile und Geräte Anlagenmängel die auf nicht vom Lieferer bezogene Teile zurückzuführen sind fallen nicht unter den Garantieanspruch Sofern der Mangel nicht beseitigt werden kann oder die Nach besserung von uns abgelehnt oder unzumutbar verzögert wird wird der Hersteller entweder kostenfreien Ersatz liefern oder den Minderwert vergüten Im Falle einer Ersatzlieferung behalten wir uns di...

Page 14: ...D 12 Deutsch 14 ...

Page 15: ...ions E 4 7 Installation E 5 7 1 General Information E 5 7 2 Heating System Connection E 5 7 3 Heat Source Connection E 5 7 4 Electrical Connection E 5 8 Start up E 6 8 1 General Information E 6 8 2 Preparation E 6 8 3 Start Up Procedure E 6 9 Description of the Control System Functions E 6 9 1 Operator Controls E 6 9 2 Heating Function E 7 9 3 Cooling Function E 7 9 4 Hot Water Function E 7 10 Mai...

Page 16: ...ding by the manufacturer s product brochures Please refrain from tampering with or altering the device 1 3 Legal Regulations and Directives This heat pump conforms to all relevant DIN VDE regulations and EU directives Refer to the EC Declaration of Conformity in the appendix for details The heat pump must be connected to the power supply in com pliance with all relevant VDE EN and IEC standards An...

Page 17: ...the refrigerant is passed through the condenser where it transfers its heat energy to the heating water Depend ing on the set operating point thermostat setting the heating water is thus heated up to a max of 60 C Cooling The functions of the evaporator and the liquifier are reversed in the Cooling operating mode The heating water gives up its heat to the refrigerant via the liqui fier which is no...

Page 18: ... Any commercially available length of pipe can be used as a carrying aid ATTENTION Do not use the holes in the panel assemblies for lifting the device 6 Installation 6 1 General Information The unit must be installed indoors on a level smooth and hori zontal surface The entire base of the frame should lie directly on the floor to ensure a good soundproof seal If this is not the case additional sou...

Page 19: ...g procedure must be observed when connecting the heat source Connect the brine pipe to the heat pump flow and return ATTENTION Insert a dirt trap in the heat source inlet of the heat pump to protect the evaporator against the ingress of impurities In addition a breather must be installed at the highest point in the heat source system The brine liquid must be produced prior to charging the system T...

Page 20: ...The overflow valve should be opened far enough to produce the maximum temperature spread between the heating flow and re turn flow listed in the table below for the current heat source tem perature The temperature spread should be measured as close as possible to the heat pump The heating element of mono en ergy systems should be disconnected 9 Description of the Control System Functions 9 1 Opera...

Page 21: ...o approx 10 K under the maximum flow temperature of the heat pump to prevent the high pressure con troller from initiating a switch off When the preparation of hot water is concluded the system will continue working in the same function as before the request 10 Maintenance and Cleaning 10 1 Maintenance The heat pump is maintenance free To prevent faults due to sediment in the heat exchangers care ...

Page 22: ...may only be performed by authorised and qualified after sales service technicians ATTENTION Disconnect all electrical circuits from the power source prior to opening the device 12 Decommissioning Disposal Before removing the heat pump disconnect it from the power source and close all valves Observe all environmentally relevant requirements regarding the recovery recycling and disposal of materials...

Page 23: ... 7 11 4 5 5 at B10 W18 kW 12 4 6 7 12 2 6 6 14 1 6 5 13 8 6 3 14 1 6 5 13 8 6 3 3 5 Sound power level dB A 54 55 56 3 6 Heating water flow with an internal pressure differential of m h Pa 0 75 2 300 1 55 9 700 1 0 4 100 1 95 16 000 1 0 4 100 1 95 16 000 3 7 Free compression of heat circulating pump level 3 Pa 44 700 41 000 41 000 3 8 Brine throughput with an internal pressure differential heat sou...

Page 24: ... 21 9 5 9 21 7 5 7 at B10 W18 kW 17 4 7 1 17 1 6 9 21 5 7 3 21 3 7 1 27 7 7 1 27 5 6 9 3 5 Sound power level dB A 56 56 56 3 6 Heating water flow with an internal pressure differential of m h Pa 1 3 4 850 2 3 13 000 1 5 4 000 2 8 13 000 1 6 3 400 3 5 13 000 3 7 Free compression of heat circulating pump level 3 Pa 34 900 61 700 61 300 3 8 Brine throughput with an internal pressure differential heat...

Page 25: ... F 5 7 1 Remarques d ordre général F 5 7 2 Branchement côté installation de chauffage F 5 7 3 Raccordement côté source de chaleur F 5 7 4 Branchement électrique F 5 8 Mise en service F 6 8 1 Remarques d ordre général F 6 8 2 Préparation F 6 8 3 Procédures à suivre à la mise en service F 6 9 Description fonctionnelle de la commande F 6 9 1 Organes de commande F 6 9 2 Fonction chauffage F 7 9 3 Fonc...

Page 26: ...ispositions légales et directives La pompe à chaleur est conforme à toutes les prescriptions DIN VDE et à toutes les directives CE afférentes Celles ci sont énon cées dans la déclaration de conformité CE en annexe Le branchement électrique de la pompe à chaleur doit être réa lisé selon les normes VDE EN et CEI en vigueur D autre part les prescriptions de branchement des fournisseurs d énergie doi ...

Page 27: ...ransférée au contraire en grande partie au fluide frigorigène Le fluide frigorigène arrive alors dans le condenseur où à son tour il transmet l énergie thermique à l eau de chauffage Ainsi l eau de chauffage chauffe et atteint des températures pouvant aller en fonction du point de fonctionnement jusqu à 60 C Refroidissement En mode refroidissement les modes de fonctionnement de l éva porateur et d...

Page 28: ...lage Pour vous aider à porter l appareil un tube quelconque fera l affaire ATTENTION Ne pas soulever l appareil en utilisant les orifices de l habillage 6 Choix de l emplacement 6 1 Généralités En règle générale l appareil doit être installé à l intérieur sur une surface plane lisse et horizontale Ici le châssis de la pompe à chaleur doit adhérer au sol sur toute sa circonférence afin de ga rantir...

Page 29: ... exactement comme indi qué ci après raccorder la conduite d eau glycolée aux circuits aller et retour de la pompe à chaleur ATTENTION Monter sur la pompe à chaleur un collecteur d impuretés dans l ouverture d admission de la source de chaleur afin de protéger l évaporateur des salissures Un purgeur d air doit en plus être monté au point le plus haut de l installation de source de chaleur Préparer ...

Page 30: ...faut ouvrir la soupape de trop plein jusqu à atteindre l étale ment maximal de température entre le circuit aller et retour du chauffage indiqué dans le tableau suivant en fonction de la tem pérature actuelle de la source de chaleur Il faut mesurer l étale ment de température le plus près possible de la pompe à cha leur La cartouche chauffante doit être désactivée pour des installations mono énerg...

Page 31: ...errompu et la valeur nominale réglée sur maximum si une demande survient La température de consigne de l eau est fixée par le thermostat externe La température devrait être réglée de manière à être d env 10 K inférieure à la température de départ afin d éviter un déclenche ment par le pressostat haute pression Le fonctionnement est de nouveau le même après la production d eau chaude que celui avan...

Page 32: ... facilement dans la plupart des cas Si vous n êtes pas en mesure de remédier vous même au dys fonctionnement veuillez vous adresser au service après vente compétent ATTENTION Les travaux sur la pompe à chaleur doivent être effectués uniquement par des techniciens qualifiés et agréés ATTENTION Avant d ouvrir l appareil assurez vous que tous les circuits électriques sont bien hors tension 12 Mise ho...

Page 33: ... 7 11 4 5 5 11 6 5 7 11 4 5 5 pour B10 W18 kW 12 4 6 7 12 2 6 6 14 1 6 5 13 8 6 3 14 1 6 5 13 8 6 3 3 5 Niveau de puissance sonore dB A 54 55 56 3 6 Débit d eau de chauffage avec diff de pression int m h Pa 0 75 2300 1 55 9700 1 0 4100 1 95 16000 1 0 4100 1 95 16000 3 7 Compression libre circulateur de chauffage niveau 3 Pa 44700 41000 41000 3 8 Débit eau glycolée avec pression diff int source cha...

Page 34: ... 17 8 6 2 21 9 5 9 21 7 5 7 pour B10 W18 kW 17 4 7 1 17 1 6 9 21 5 7 3 21 3 7 1 27 7 7 1 27 5 6 9 3 5 Niveau de puissance sonore dB A 56 56 56 3 6 Débit d eau de chauffage avec diff de pression int m h Pa 1 3 4850 2 3 13000 1 5 4000 2 8 13000 1 6 3400 3 5 13000 3 7 Compression libre circulateur de chauffage niveau 3 Pa 34900 61700 61300 3 8 Débit eau glycolée avec pression diff int source chaleur ...

Page 35: ...e de chauffage SI 20TR A XIII 2 12 Kühlbetrieb Cooling operation Mode de refroidissement SI 20TR A XIV 3 Stromlaufpläne Circuit diagrams Schémas électriques A XV 3 1 Last Load Charge SI 8MR SI 10MR A XV 3 2 Steuerung Control Commande SI 8MR SI 10MR A XVI 3 3 Legende Legend Légende SI 8MR SI 10MR A XVII 3 4 Last Load Charge SI 12TR SI 16TR A XVIII 3 5 Steuerung Control Commande SI 12TR SI 16TR A XI...

Page 36: ...OD 3 6 05 6 75 6 75 6 75 lUPHTXHOOH LQJDQJ LQ GLH 3 HDW VRXUFH HDW SXPS LQOHW 6RXUFH GH FKDOHXU QWUpH GDQV OD 3 6 05 6 75 6 75 6 75 HL XQJVYRUODXI XVJDQJ DXV GHU 3 X HQJHZLQGH HDWLQJ ZDWHU IORZ HDW SXPS RXWOHW H WHUQDO WKUHDG OOHU HDX GH FKDXIIDJH 6RUWLH GH OD 3 LOHWDJH H WpULHXU XVODXI hEHUGUXFN HL NUHLV 6FKODXFK 2YHUSUHVVXUH RXWOHW HDWLQJ FLUFXLWV KRVH FRXOHPHQW VXUSUHVVLRQ LUFXLW GH FKDXIIDJH 7...

Page 37: ... FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH...

Page 38: ...LV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVV...

Page 39: ... FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D ...

Page 40: ...ULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHV...

Page 41: ...H FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D...

Page 42: ...SULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUH...

Page 43: ... FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D ...

Page 44: ...LV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVV...

Page 45: ... FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D ...

Page 46: ...SULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUH...

Page 47: ...GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3...

Page 48: ...SULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH 6ROHHLQWULWWVWHPSHUDWXU LQ ULQH LQOHW WHPSHUDWXUH LQ 7HPSpUDWXUH G HQWUpH G HDX JO FROpH HQ HLVWXQJV DKO LQFO 3XPSHQOHLVWXQJVDQWHLO RHIILFLHQW RI SHUIRUPDQFH LQFO SRZHU LQSXW WR SXPS RHIILFLHQW GH SHUIRUPDQFH FRPSULV SDUW GH FRQVRPPDWLRQ GH OD SRPSH UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUHVVLRQ HQ 3D UXFNYHUOXVW LQ 3D 3UHVVXUH ORVV LQ 3D 3HUWH GH SUH...

Page 49: ...www dimplex de A XV Anhang Appendix Annexes 3 1 3 Stromlaufpläne Circuit diagrams Schémas électriques 3 1 Last Load Charge SI 8MR SI 10MR ...

Page 50: ...A XVI Anhang Appendix Annexes 3 2 3 2 Steuerung Control Commande SI 8MR SI 10MR ...

Page 51: ...ter Groupe commutateur eau chaude R2 Rücklauffühler Return flow sensor Sonde de retour R6 Eingefrierschutzfühler Sole Flow temperature limit sensor brine Sonde antigel eau glycolée R7 Kodierwiderstand Coding resistor Résistance de codage R8 Frostschutzfühler Kühlbetrieb Wasser Flow sensor for cooling operation water Capteur protection antigel mode refroidiss eau R10 Feuchtefühler Humidity sensor S...

Page 52: ...A XVIII Anhang Appendix Annexes 3 4 3 4 Last Load Charge SI 12TR SI 16TR 1HW Â 0DLQV Â 5pVHDX ...

Page 53: ...www dimplex de A XIX Anhang Appendix Annexes 3 5 3 5 Steuerung Control Commande SI 12TR SI 16TR ...

Page 54: ...rmwasser Switching assembly hot water Groupe commutateur eau chaude R2 Rücklauffühler Return flow sensor Sonde de retour R6 Eingefrierschutzfühler Sole Flow temperature limit sensor brine Sonde antigel eau glycolée R7 Kodierwiderstand Coding resistor Résistance de codage R8 Frostschutzfühler Kühlbetrieb Wasser Flow sensor for cooling operation water Capteur protection antigel mode refroidiss eau R...

Page 55: ...www dimplex de A XXI Anhang Appendix Annexes 3 7 3 7 Last Load Charge SI 20TR 1HW Â 0DLQV Â 5pVHDX ...

Page 56: ...A XXII Anhang Appendix Annexes 3 8 3 8 Steuerung Control Commande SI 20TR ...

Page 57: ...12 Steuerungsplatine Control PCB Platine de commande N13 Schaltgruppe Warmwasser Switching assembly hot water Groupe commutateur eau chaude R2 Rücklauffühler Return flow sensor Sonde de retour R6 Eingefrierschutzfühler Sole Flow temperature limit sensor brine Sonde antigel eau glycolée R7 Kodierwiderstand Coding resistor Résistance de codage R8 Frostschutzfühler Kühlbetrieb Wasser Flow sensor for ...

Page 58: ...V Anhang Appendix Annexes 4 4 Hydraulische Prinzipschemen Hydraulic block diagrams Schémas hydrauliques 4 1 Heizen und dynamische Kühlung Heating and dynamic cooling Chauffage et refroidissement hydrauliques ...

Page 59: ... A XXV Anhang Appendix Annexes 4 2 4 2 Heizen und dynamische Kühlung und Warmwasserbereitung Heating and dynamic cooling and hot water preparation Chauffage et refroidissement hydrauliques et production d eau chaude ...

Page 60: ...her Buffer tank Réservoir tampon Warmwasserspeicher Hot water cylinder Ballon d eau chaude Erdwärmesonden Borehole heat exchangers Sondes géothermiques Überdruck Heizung Overpressure of the heating system Surpression chauffage Überdruck Sole Overpressure of the brine Surpression eau glycolée EV Elektroverteilung Electrical distribution system Distributeur courant électrique KW Kaltwasser Cold wate...

Page 61: ...www dimplex de A XXVII Anhang Appendix Annexes 5 5 Konformitätserklärung Declaration of Conformity Déclaration de conformité ...

Page 62: ...A XXVIII Anhang Appendix Annexes 5 ...

Page 63: ...www dimplex de A XXIX Anhang Appendix Annexes 5 ...

Page 64: ...tschland GmbH Geschäftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrtümer und Änderungen vorbehalten Subject to alterations and errors Sous réserve d erreurs et modifications 49 0 9221 709 565 www dimplex de ...

Reviews: