To achieve optimum regulation, select as small a controlling
range as possible between the minimum and maximum return
temperature. Automatic operating mode switching makes it
possible to set an external temperature above which heating
operation is blocked.
Elimination of faults:
Start-up must be performed in accordance with the installation
and operating instructions of the heat pump manager.
Recommended settings for room set
temperature 22°C
Minimum return temperature
Maximum return temperature
Panel heating (35/28 °C)
(floor, wall, ceiling)
22 °C
30 °C
Low-temperature radiators (45/38 °C)
25 °C
40 °C
Radiators (55/45 °C)
30 °C
50 °C
Measure 1
Measure 2
Building too hot
Reduce room set temperature
Reduce minimum return temperature
Building is not heating up
Raise room set temperature,
increase volume flow
Raise maximum return temperature
Reference room is hot,
but individual rooms (e.g. bathroom) too cold
Carry out hydraulic equalisation (reduce
volume flow in the reference room)
Raise minimum return temperature.
This can lead to the room set temperature in
the reference room being periodically
overshot.
Reference room is not
reaching the room set temperature,
but individual rooms (e.g. bathroom) are hot
Carry out hydraulic equalisation (raise
volume flow in the reference room)
Raise maximum return temperature
Summary of Contents for RT Econ A
Page 2: ......
Page 10: ...DE 8 452114 66 73 FD 9306 Deutsch Smart RTC...
Page 18: ...EN 8 452114 66 73 FD 9306 Smart RTC English...
Page 26: ...FR 8 452114 66 73 FD 9306 Smart RTC Fran ais...
Page 30: ...A IV 452114 66 73 FD 9306 Anhang Appendix Annexes Smart RTC...
Page 31: ...452114 66 73 FD 9306 A V Anhang Appendix Annexes Smart RTC...