EN-6 452161.66.02 · FD 9601
www.dimplex.de
English
LI 9TES
5 Transport
ATTENTION!
When transporting the heat pump, ensure that it is not tilted more than
45° (in any direction).
Use a pallet for transporting the heat pump to the final installation
location. The basic device can be transported with a lift truck,
hand truck or by means of 3/4" pipes fed through the holes in the
base plate or frame.
ATTENTION!
The heat pump and transport pallet are only joined by the packing film.
Before using the transport holes in the frame, it is necessary to
remove the lower side panel assemblies. This is done by loosen-
ing each of the two screws at the base and then withdrawing the
panels by unhooking them from above. Rehang the panels by
gently pushing them in an upwards direction.
Be careful not to damage any components when inserting the
pipes through the frame.
ATTENTION!
The transport securing device is to be removed prior to commissioning.
6 Set-UP
6.1 General Information
The heat pump is designed for installation in a corner. Other in-
stallation locations are also possible in combination with an air
duct (available as an accessory) on the air outlet side.
The air-to-water heat pump must be installed in a frost-free,
dry room on an even, smooth and horizontal surface. The entire
base of the frame should lie directly on the floor to ensure an ad-
equate soundproof seal. If this is not the case, additional sound
insulation measures may be necessary. If the device is installed
on top of a built-under buffer tank, a surface that fully supports
the base is required. The heat pump must be installed so that
maintenance work can be carried out without being hindered.
This can be ensured by maintaining a clearance of 1 m in front
and to the left of the heat pump. The side panel assemblies must
not be covered by connecting pipes.
Never install the device in rooms subject to high humidity. Con-
densation can form on the heat pump and air circuit if the humid-
ity exceeds 50 % and the external temperature is below 0 °C.
Neither frost nor temperatures higher than 35 °C must occur in
the installation location at any time of the year.
If the heat pump is installed on an upper storey, the load-bearing
capacity of the ceiling should be checked. On account of the
acoustics, measures for isolating possible vibrations should also
be very carefully planned in advance as well. Installation on a
wooden floor is not recommended.
6.2 Condensed Water Pipe
Condensate that forms during operation must be drained off
frost-free. To ensure proper drainage, the heat pump must be
mounted horizontally. The condensate pipe must have a mini-
mum diameter of 50 mm and must be fed into a sewer in such a
way that it is safe from frost. Do not discharge the condensate di-
rectly into clearing tanks or cesspits, as aggressive vapours or a
condensed water pipe which has not been laid in a frost-free
manner could destroy the evaporator.
6.3 Sound
To prevent solid-borne sound from being transmitted to the heat-
ing system, we recommend connecting the heat pump to the
heating system using a flexible hose.
Installed air ducts should be sound-isolated from the heat pump
to prevent the transmission of solid-borne sound to the ducts.
If both air openings are connected directly to a wall opening, the
ventilator terminals can be reversed from a delta to a star con-
nection (see information in the ventilator terminal box).
Opening the cover
Closing the cover
5HPRYHVFUHZLQ
WUDQVSRUWORFN
P
P
Summary of Contents for LI 9TES
Page 2: ......
Page 34: ...EN 16 452161 66 02 FD 9601 www dimplex de English LI 9TES ...
Page 50: ...FR 16 452161 66 02 FD 9601 www dimplex de Français LI 9TES ...
Page 66: ...A XVI 452161 66 02 FD 9601 www dimplex de Anhang Appendix Annexes LI 9TES ...
Page 67: ...www dimplex de 452161 66 02 FD 9601 A XVII Anhang Appendix Annexes LI 9TES ...