INSTALLATION
MOUNTING

6

INSTALLATION

5.1

General

The unit should always be installed on a permanently
level, smooth and horizontal floor. The entire base
frame surface should thereby make close contact with
the floor in order to ensure adequate sound insulation
and to prevent water-carrying parts from cooling out.
If this is not the case, additional insulation measures
may become necessary. It must be possible to carry
out servicing work without any problems. This is
ensured if a clearance of 1.2 m to solid walls is
maintained.

The intake and discharge openings

must not be restricted nor obstructed.

5.2

Condensate Line

The condensation water that may collect during
operation must be drained in a place protected from
frost. The heat pump must be positioned horizontally
so that proper discharge can be ensured. The
condensation water pipe must have a minimum
diameter of 50 mm and should be discharged to the
sewer drain in a frost-proof location.

MOUNTING

6.1

General

The following connections need to be established
on the heat pump:

- supply/return flow of heating system
- supply/return flow of hot water circuit
- condensate drain
- control lead to the heat pump controller
- power supply

6.2

Heating and Hot Water Connection

The connections on the heating side of the heat
pump are provided with 1"external thread. The hoses
to be connected exit the unit through its bottom.  When
carrying out the connections, use a wrench to
counterhold at the transitions.

Before completing the heat pump connections on
the heating water side, the heating installation must
be flushed in order to remove any impurities that
may be present and to ensure trouble-free operation
of the heat pump. On systems equipped with heating
water flow shut-off devices such  as radiator or
thermostat valves, an overflow valve to be provided
by the customer needs to be installed behind the
heating pump  in a heating system bypass. This
guarantees a minimum heating water flow through
the heat pump and prevents any malfunctions from
occurring.

Once the installation on the heating side has been
completed, the heating system must be filled, de-
aerated and pressure-tested.

Frost Protection

As a precaution against frost, manual drain valves
should be provided. If the heat pump is placed out of
service or in the event of a power failure, the system
has to be drained at three points (see figure) and
blown out. In heat pump installations where a power
failure cannot be readily detected (holiday house),
the heating circuit must contain a suitable antifreeze
product.

 2

 1

 3

Wärmepumpe

5

CAUTION!

1,2 m

1,2 m

1,2 m

1,2 m

Heat pump

Summary of Contents for LA 16ASR

Page 1: ...CE MOUNTING and OPERATING MANUAL Reversible Air to Water Heat Pump for Outdoor Installation LA16ASR Order No 452158 66 21 FD 8507...

Page 2: ...N 6 5 1 General 5 2 Condensate Line 6 MOUNTING 6 7 6 1 General 6 2 Heating and Hot Water Connection 6 3 Electrical Connection 7 COMMISSIONING 7 8 7 1 General 7 2 Preparation 7 3 Procedure During Heati...

Page 3: ...oling system all relevant regulations have to be complied wit 1 3 Energy Efficient Use of the Heat Pump By purchasing this heat pump you contribute to the protection of the environment A prerequisite...

Page 4: ...us mode of operation a heating water return temperature of more than 18 C must be maintained in order to ensure proper defrosting of the evaporator The heat pump is not designed for any increased heat...

Page 5: ...vices The external temperature sensor to be mounted by the customer incl fastening hardware is shipped with the controller Method of functioning and operation of the heat pump controller are described...

Page 6: ...Heating and Hot Water Connection The connections on the heating side of the heat pump are provided with 1 external thread The hoses to be connected exit the unit through its bottom When carrying out t...

Page 7: ...service authorized by the manufacturer Only then can an extended warranty period of 3 years in total be granted cf Warranty service 7 2 Preparatory Steps Prior to commissioning the following items nee...

Page 8: ...ctions in the heat exchanger of the heat pump caused by dirt deposits care must be taken that the heat exchanger cannot become contaminated in the heating installation In the event that operating malf...

Page 9: ...l and reinstallation of the panel assemblies to be performed as described in Chapter 4 When cleaning do not use any sharp or hard objects so as to prevent any damage to the evaporator and the condensa...

Page 10: ...S 11 3 1 Heating Mode 13 11 3 2 Cooling Mode 14 11 4 WIRING DIAGRAMS 11 4 1 Control 15 11 4 2 Load 16 11 4 3 Terminal Diagram 17 11 4 4 Legend 18 11 5 HYDRAULIC BLOCK DIAGRAM 19 11 6 EC DECLARATION OF...

Page 11: ...11 Dimension Drawing APPENDIX 11 1 DIMENSION DRAWING...

Page 12: ...12 Equipment Data APPENDIX 11 2 EQUIPMENT DATA...

Page 13: ...13 11 3 1 Heating Mode APPENDIX 11 3 SCHEMATICS...

Page 14: ...14 11 3 2 Cooling Mode APPENDIX 11 3 SCHEMATICS...

Page 15: ...N D X 7 2 X 7 6 X 7 8 X 5 A l l e Q u e r s c h n i t t e 0 7 5 m m 2 2 4 2 4 2 4 1 3 5 4 6 2 2 2 1 2 2 E 4 A 1 C 4 P 2 B 1 8 X 2 1 4 X 2 7 X 2 8 X 2 8 X 2 8 X 2 1 1 X 2 1 2 X 2 1 3 X 2 1 0 X 2 1 0 X...

Page 16: ...n P E g e g n L 3 3 N e t z 2 1 L 2 L 1 4 3 2 1 L 3 L 1 L 2 X 1 P E P E V e r t e i l e r M 3 M 1 V U W 2 4 R S 6 T 1 3 5 F 2 3 1 2 3 M 2 M 4 3 N 3 K 1 1 4 2 1 6 K 2 1 5 5 A l l e Q u e r s c h n i t...

Page 17: ...mern Ader und Pinnummern X5 7 7 8 8 9 6 5 6 3 4 5 4 3 2 1 2 1 X4 X7 1 5 1 4 1 6 1 3 1 0 1 4 1 2 1 3 1 2 1 1 1 0 9 1 1 1 7 1 8 1 9 1 8 1 7 1 6 1 5 X5 X6 2 1 2 0 2 2 2 0 2 3 2 4 2 4 2 3 2 2 2 1 1 9 X6 7...

Page 18: ...1 Compressor M2 Fan N1 Heat pump controller N3 Soft start control R9 Frost protection sensor for heating water R10 Heating water return flow sensor R11 Coding resistor 5k6 X1 Terminal strip load termi...

Page 19: ...ation Absperrventil mit Entw sserung M N1 N2 AUF EV HUP HUPR HPN KW MAN MZN NKF SUP WE WUP WW WWF W rmepumpe Pufferspeicher Warmwasserspeicher Pufferspeicher f r Abw rme W rmepumpenregler Elektroverte...

Page 20: ...ents of the applicable EC directives This declaration becomes invalidated if any modifications are made to the product s without our prior authorization Designation of the product s EC Directives Air...

Page 21: ...Notes 21...

Page 22: ...Notes 22...

Page 23: ...Notes 23...

Page 24: ...KKW Kulmbacher Klimager te Werk GmbH Technical data subject to change without notice Gesch ftsbereich Dimplex Fax 49 0 92 21 709 589 Am Goldenen Feld 18 www dimplex de D 95326 Kulmbach...

Reviews: