COMMISSIONING
CLEANING / MAINTENANCE

f)

Once all heating circuit are fully open and a
heating water temperature of approx. 25 

°

C is

maintained in the buffer tank, the minimum flow
rate must be set on the overflow valve and the
heating circulating pump.

g)

New buildings have an increased heat demand
due to the energy required for structural drying.
This increased heat demand may result in
insufficiently dimensioned heating installations
not attaining the desired room temperature at
a l l   t i m e s .   I n   t h i s   c a s e   i t   i s   t h e r e f o r e
recommended  that the second heat generator
be kept ready for operation in the first heating
season. The limit temperature on the heat pump
controller should therefore be raised to  15

°

C.

7.4

Procedure During Cooling Season

In this case, all heating circuits can be fully opened.

The setting described in 7.3 f) must be carried out
during the heating season.

CLEANING /
MAINTENANCE

8.1

Maintenance

To protect the paint finish, avoid placing objects
against or on the unit. The external parts of the heat
p u m p   c a n   b e   w i p e d   w i t h   a   d a m p   c l o t h   a n d
commercially available cleaning agents.

Do not use any cleaning agents

containing sand, soda, acid or chloride as these may
damage the surface.

To prevent malfunctions in the heat exchanger of the
heat pump caused by dirt deposits, care must be
taken that the heat exchanger cannot become
contaminated in the heating installation. In the event
that operating malfunctions due to contamination
occur nevertheless, the system should be cleaned
as described below.

8.2

Cleaning of Heating Side

The ingress of oxygen into the heating water may
result in the formation of oxidation products. An ad-
ditional contamination of the heating water caused
by residues of lubricating and sealing agents occurs
in many cases.

Both of the above causes may lead to a reduction in
the performance of the heat pump condenser. In
t h e s e   c a s e s   t h e   i n s t a l l e r   n e e d s   t o   c l e a n   t h e
condenser. Based on information known to date

 

we

recommend cleaning with a 5% phosphoric acid
solution or, in the case that cleaning needs to be
performed more frequently, with a 5% formic acid
solution. In both cases the

cleaning fluid should be at room temperature.
Thorough flushing is necessary to ensure that all
cleaning agent residues are removed from the
system. It is recommended that the heat exchanger
is cleaned in the direction opposite to the normal
flow direction. Owing to their acid content flushing
agents must be used with caution. To prevent acidic
flushing agents from entering the heating installation
when cleaning the condenser, we recommend that
the flushing device should be mounted directly to

8

CAUTION!

Summary of Contents for LA 16ASR

Page 1: ...CE MOUNTING and OPERATING MANUAL Reversible Air to Water Heat Pump for Outdoor Installation LA16ASR Order No 452158 66 21 FD 8507...

Page 2: ...N 6 5 1 General 5 2 Condensate Line 6 MOUNTING 6 7 6 1 General 6 2 Heating and Hot Water Connection 6 3 Electrical Connection 7 COMMISSIONING 7 8 7 1 General 7 2 Preparation 7 3 Procedure During Heati...

Page 3: ...oling system all relevant regulations have to be complied wit 1 3 Energy Efficient Use of the Heat Pump By purchasing this heat pump you contribute to the protection of the environment A prerequisite...

Page 4: ...us mode of operation a heating water return temperature of more than 18 C must be maintained in order to ensure proper defrosting of the evaporator The heat pump is not designed for any increased heat...

Page 5: ...vices The external temperature sensor to be mounted by the customer incl fastening hardware is shipped with the controller Method of functioning and operation of the heat pump controller are described...

Page 6: ...Heating and Hot Water Connection The connections on the heating side of the heat pump are provided with 1 external thread The hoses to be connected exit the unit through its bottom When carrying out t...

Page 7: ...service authorized by the manufacturer Only then can an extended warranty period of 3 years in total be granted cf Warranty service 7 2 Preparatory Steps Prior to commissioning the following items nee...

Page 8: ...ctions in the heat exchanger of the heat pump caused by dirt deposits care must be taken that the heat exchanger cannot become contaminated in the heating installation In the event that operating malf...

Page 9: ...l and reinstallation of the panel assemblies to be performed as described in Chapter 4 When cleaning do not use any sharp or hard objects so as to prevent any damage to the evaporator and the condensa...

Page 10: ...S 11 3 1 Heating Mode 13 11 3 2 Cooling Mode 14 11 4 WIRING DIAGRAMS 11 4 1 Control 15 11 4 2 Load 16 11 4 3 Terminal Diagram 17 11 4 4 Legend 18 11 5 HYDRAULIC BLOCK DIAGRAM 19 11 6 EC DECLARATION OF...

Page 11: ...11 Dimension Drawing APPENDIX 11 1 DIMENSION DRAWING...

Page 12: ...12 Equipment Data APPENDIX 11 2 EQUIPMENT DATA...

Page 13: ...13 11 3 1 Heating Mode APPENDIX 11 3 SCHEMATICS...

Page 14: ...14 11 3 2 Cooling Mode APPENDIX 11 3 SCHEMATICS...

Page 15: ...N D X 7 2 X 7 6 X 7 8 X 5 A l l e Q u e r s c h n i t t e 0 7 5 m m 2 2 4 2 4 2 4 1 3 5 4 6 2 2 2 1 2 2 E 4 A 1 C 4 P 2 B 1 8 X 2 1 4 X 2 7 X 2 8 X 2 8 X 2 8 X 2 1 1 X 2 1 2 X 2 1 3 X 2 1 0 X 2 1 0 X...

Page 16: ...n P E g e g n L 3 3 N e t z 2 1 L 2 L 1 4 3 2 1 L 3 L 1 L 2 X 1 P E P E V e r t e i l e r M 3 M 1 V U W 2 4 R S 6 T 1 3 5 F 2 3 1 2 3 M 2 M 4 3 N 3 K 1 1 4 2 1 6 K 2 1 5 5 A l l e Q u e r s c h n i t...

Page 17: ...mern Ader und Pinnummern X5 7 7 8 8 9 6 5 6 3 4 5 4 3 2 1 2 1 X4 X7 1 5 1 4 1 6 1 3 1 0 1 4 1 2 1 3 1 2 1 1 1 0 9 1 1 1 7 1 8 1 9 1 8 1 7 1 6 1 5 X5 X6 2 1 2 0 2 2 2 0 2 3 2 4 2 4 2 3 2 2 2 1 1 9 X6 7...

Page 18: ...1 Compressor M2 Fan N1 Heat pump controller N3 Soft start control R9 Frost protection sensor for heating water R10 Heating water return flow sensor R11 Coding resistor 5k6 X1 Terminal strip load termi...

Page 19: ...ation Absperrventil mit Entw sserung M N1 N2 AUF EV HUP HUPR HPN KW MAN MZN NKF SUP WE WUP WW WWF W rmepumpe Pufferspeicher Warmwasserspeicher Pufferspeicher f r Abw rme W rmepumpenregler Elektroverte...

Page 20: ...ents of the applicable EC directives This declaration becomes invalidated if any modifications are made to the product s without our prior authorization Designation of the product s EC Directives Air...

Page 21: ...Notes 21...

Page 22: ...Notes 22...

Page 23: ...Notes 23...

Page 24: ...KKW Kulmbacher Klimager te Werk GmbH Technical data subject to change without notice Gesch ftsbereich Dimplex Fax 49 0 92 21 709 589 Am Goldenen Feld 18 www dimplex de D 95326 Kulmbach...

Reviews: