The heat pump operates over a large air temperature 

range (from -7°C to 35°C) using energy from outdoor 

air. It is essential to correctly design and install the air 

ducting system to ensure the product operates properly 

and complies with regulations.

The air supply to and from the Edel heat pump water 

heater must NOT extract air from the living space of the 

dwelling. The air must be supplied to the appliance di-

rectly from the outside or from another source outside 

the thermal envelop of the living space.

The ducting used to connect the air intake and exhaust 

must  be  sufficiently  insulated  to  prevent  condensation 

forming. Condensation may result in damage to the ap-

pliance and/or building fabric. 

Dimplex does not take any responsibil-

ity for issues caused by poor ducting 

design or installation.

Figure 7 provides an example of how the ducting inlet 

and outlet connections should be installed.

 

Installation

It  is  essential  to  maintain  a  minimum  air  flow  rate 

through the ducting for correct operation of the appli-

ance. The nominal mass flow rate must be maintained 

above 320m

3

/hr.

For the fan to operate in Fan speed 1, the maximum sys-

tem pressure drop across the ducting connections must 

not exceed 100Pa and for Fan speed 2 the maximum 

pressure drop must not exceed 220Pa

6.7  Ducting Design

6.6   Air Connection

Figure 7: Examples of air connection to the water heater

 

Item

Qty

∆P [Pa]

Total [Pa]

Air Intake

2m straight

X 5

4.8

24.0

90°bend

X 3

12.5

37.5

External terminal

X 1

51.0

51.0

Air Exhaust

2m straight

X 4

4.8

19.2

90°bend

X 2

12.5

25.0

External terminal

X 1

51.0

51.0

Total System Calculated Pressure Drop @ 320m3

/

hr

207.7 Pa

6.7.1 Worked Example

-  The pressure drop information provided is for 

160mm semi rigid Ubbink ducting, other ducting 

manufacturers components may be used howev-

er the total maximum pressure drop must not ex-

ceed the stated values.

Figure 6: Air intake and Air discharge

 

A ducting system with the following; 

Note: 

-

The calculated worked example includes all the 

necessary ducting components to complete the 

installation and has resulted in a total system 

pressure drop of 207.7 Pa at 320m

3

/hr mass air 

flow rate. This is acceptable as the pressure drop 

is below the maximum permissible allowed.

NOTE: The system reliability and efficiency will be 

compromised should the mass air flow rate 

drop below 320m

3

/hr.

During the product specification stage, it is essential that 

the system designer calculated the required total 

quantity of ducting connections, lengths, bends and 

terminations to establish an accurate value for total 

system pressure drop based on the system air flow 

Table 3: Worked example

Fan speed 1 will operate when the 

system pressure drop is minimal as a 

result of very short duct runs. System 

efficiency will be slightly increased and 

the noise level slightly reduced.

i

Dimplex does not take responsibility 

for installation and the operating effi

-

ciency of the appliance when installed 

outside the scope of the guidelines 

provided in this document.

i

i

Figure 5: Wiring diagram for Immersion Heater

Dial to adjust

water temperature

Earth (green/yellow)

Live (brown)

Neutral (blue)

The water heater must be filled with water 

before switching on the immersion heater. Failure 

to do so will damage the element and void any 

guarantee on the product.

!

Summary of Contents for EDL200UK-630RF

Page 1: ...Air Source Heat Pump Water Heater Installation and User Instructions RD01144 2 Important This manual must be left with user after Installation Edel RF...

Page 2: ...ture reference Installers are required to carry out installation commissioning and ser vicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hot Water I...

Page 3: ...Electrical Connections 11 6 9 1 1 Electricity Provider Contact 11 6 9 1 2 Connecting the PV Function 11 7 Set Up and Use 12 7 1 Commissioning 12 7 2 Using your Hot Water Heat Pump 13 7 3 Control Box 1...

Page 4: ...and or user This appliance can be used by children aged 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given s...

Page 5: ...installation If in any doubt please call the appropriate help desk Disregarding the instructions given in this manual in its entirety and any relevant regulations standards and codes of practice will...

Page 6: ...must be taken when placing the water heater in a garage or outbuilding All exposed pipework must be correctly insulated to avoid frost damage The position and orientation of the water heater should b...

Page 7: ...2 15 22 9 0 8 28 18 1 0 35 27 1 4 G3 4 22 28 9 1 0 35 18 1 4 42 27 1 7 G1 28 35 9 1 4 42 18 1 7 54 27 2 3 Dimplex recommend an annual maintenance inspection is carried out on the water heater In hard...

Page 8: ...on vessel membrane before filling the cylinder The pre charge should be greater than or equal to 3 bar 6 2 Cold Water Inlet with Inlet Group The discharge pipe should not be connected to a soil discha...

Page 9: ...dwellings occupied by people with impaired vision or mobility con sideration should be given to the installation of a suita ble safety device to warn when discharge takes place e g electronically oper...

Page 10: ...2 5 25 0 External terminal X 1 51 0 51 0 Total System Calculated Pressure Drop 320m3 hr 207 7 Pa 6 7 1 Worked Example The pressure drop information provided is for 160mm semi rigid Ubbink ducting othe...

Page 11: ...hoose load shedding level 1 the electrical back up is prevented from running If you choose load shedding level 0 both the electrical back up and the heat pump will be prevented from running see Sectio...

Page 12: ...ischarge and check after closing that valve is not dripping 9 Open expansion relief valve to ensure proper discharge and check after closing that valve is not dripping 10 Check all shower outlets toil...

Page 13: ...ature remains in the authorised 7 C to 35 C range Outside of this range electrical backup ensures that the domestic hot water is heated The domestic hot water temperature provided by the heat pump is...

Page 14: ...This function can be programmed to run between 1 and 99 days and is effective as soon as the number of days has been confirmed HOLIDAYS HOLI RETURN 8 Set number of days in standby mode Enter HOLIDAY...

Page 15: ...exisitng programme MONDAY Set Up and Use Frost PT Frost Protection Mode ECO Heat Pump Only Running CONF Heat Pump Only Running electrical back up if needed 7 10 Programming Heating time for the tank v...

Page 16: ...al until the screen displays Inst Menu Press the Clock and Menu buttons simultaneously Keep both buttons pressed down until the screen goes blank 7 11 1 PV Mode Setting Description Unit Range Factory...

Page 17: ...emperature reaches 43o C The heat pump will complete the remaining charge to set temperature 7 11 2 3 Minimum Temperature To C Min No To C Min 43 o c Select Mode Enter It is possible to allow the oper...

Page 18: ...f locking for accessing the menus In the Installer menu turn the dial to Locking LOCKING LOCKING NO Select No Enter NO Locking is not activated but manual locking is possible by pressing Menu for 3 se...

Page 19: ...ers The Counters menu shows the number of start ups from the heat pump and the electrical backup In the Installer menu turn the dial to Counters Counter No 1 Number of start ups from the heat pump Cou...

Page 20: ...heater and the thermostat 10 The immersion heater boss can also be used for access to view the internal components of the cyl inder 11 Re commission unit see chapter 7 1 8 2 Heat Pump Any work on the...

Page 21: ...ich would reduce the cross sectional area of the conductor 4 Ensured the conductors are tightly and securely connected to the controls or immersion heater 5 Ensured the bared conductors are correctly...

Page 22: ...higher than the volume in the tank The time period the appliance operates is not too short 12hrs minimum if connected to piping The water temperature is not set too low Condensates are not drain ing T...

Page 23: ...045 2 Expansion vessel fixing kit R00094 2 DN16 3 4 BSP x 1000 flex pipe R00095 1 1 2 BSP T P valve R00020 1 15 x 22 straight PE tundish R00047 1 Temp sensor 25 C 1243950 C3S PCB Controller 1244096 70...

Page 24: ...aintained continuously at the standard set temperature if no signal or control is connected to the external control switch OVER PRESS Heat pump pressure too high No water in tank Water is too hot 75 C...

Page 25: ...being in contact with a part which vibrates Replace expansion valve The compressor is not working and safety temperature is activated Weakness in compressor Replace compressor ERR 02 Incorrect temper...

Page 26: ...mation 9 1 Warranty Limits Please read the following statements carefully as it affects your warranty Please ensure that the installer has fully completed the Benchmark Checklist on the inside back pa...

Page 27: ...d Water supply being other than cold domestic water such as rainwater or water from a well or which has particularly hostile or abnormal properties which do not comply with the national rules and curr...

Page 28: ...28 B C D E A 152 Figure 11 Edel Air Source Water Heater Dimensions for reference only Technical Data and Product Fiche 10 Technical Data and Product Fiche Air Intake Air Discharge...

Page 29: ...d Product Fiche Cylinder is tested in accordance with EN12897 2006 GDC Group Ltd Edel Air Source Water Heater Product Fiche Reference EDL200UK 630RF EDL270UK 630RF Load Profile Primary M L Energy Rati...

Page 30: ...2 kW 240V Ventilation Air flow rate 320 to 400 m3 h Air temperature 7 C to 35 C Max air pipe length rigid piping 20m in total intake and rejection Condensates flow rate 0 3 L h Condensates drainage p...

Page 31: ...31 Power Supply Green Yellow Black Blue Brown Black Blue Blue Black Sensors Black Black Black Black Blue Black Blue Brown Black Brown Communication Bus Display 1 2 Red Fan B1244454 F HPS DV...

Page 32: ...Red Blue Blue Black Brown Blue Green Yellow Blue Black Blue Blue Red Red Blue HTS WTS HPS High Pressure Switch C25 Compressor Start Capacitor C2 Fan Capacitor C4 Valve F Fan DV Defrost Valve RE Immer...

Page 33: ...33 Notes...

Page 34: ...and pressure relief valve and expansion valve been fitted and discharge tested Yes No The tundish and discharge pipework have been connected and terminated to Part G of the Building Regulations Yes A...

Page 35: ...mments Signature SERVICE 3 Date Engineer Name Company Name Telephone Number Comments Signature SERVICE 4 Date Engineer Name Company Name Telephone Number Comments Signature SERVICE 5 Date Engineer Nam...

Page 36: ...plex reserve the right to revise products literature and guarantee terms without prior notice due to a policy of continuous improvement www KIWA co uk www HWA co uk To speak to customer services pleas...

Reviews: