background image

7

Pre-Installation

5.8  Building Regulation G3 Discharge

       Requirements

As part of the requirements of Building Regulation G3  

this product is factory fitted with a T&P valve, which 

complies with BS EN 1490. Any discharge from a water 

heater system should be conveyed to where it is visible, 

but will not cause danger to persons in or about the 

building. The tundish and the discharge pipes should be 

fitted in accordance with the requirements of 

Building Regulation approved document G3, (England 

and Wales), Part P of Northern Ireland and Standard 

4.9 of Scotland.

5.8.1  Discharge Pipe D2

Dimplex strongly recommends the use of metal 

pipework only and Dimplex does not take responsibility 

for any damage caused from discharges.

The discharge pipe D2 should be at least one pipe size 

larger than the nominal outlet size of the safety device 

unless its total equivalent hydraulic resistance exceeds 

that of a straight pipe 9m long, i.e. for discharge pipes 

between 9m and 18m the equivalent resistance length 

should be at least two sizes larger than the nominal out-

let size of the safety device; between 18m and 27m at 

least 3 sizes larger, and so on; bends must be taken into 

account in calculating the flow resistance. See 

Figure 2, Table 2 and the worked example.

5.8.2  Worked Example

Figure 2: Typical discharge pipe arrangement

 

If required, precautions can be taken to minimise 

effects of water hardness, i.e. installation of water con

-

ditioner or water softener. These devices should be in-

stalled in hard water areas where high water 

storage temperatures are required, i.e. greater than 

60°C storage temperatures, particularly when water 

hardness exceeds 200ppm. Should the water heater re-

quire de-scaling, this must be performed by a 

qualified technician.

Table 2: Discharge

Value 

outlet 

size

Minimum size 

of discharge 

pipe before 

tundish (mm)

Minimum size 

of discharge 

pipe after 

tundish (mm)

Maximum 

allowed length 

of pipe after 

tundish (m)

Length to be 

subtracted for 

each elbow or 

bend

(m)

G1/2

15

22

9

0.8

28

18

1.0

35

27

1.4

G3/4

22

28

9

1.0

35

18

1.4

42

27

1.7

G1

28

35

9

1.4

42

18

1.7

54

27

2.3

Dimplex recommend an annual maintenance 

inspection is carried out on the water heater. In hard wa-

ter areas this should include inspection of the 

immersion heater, [above 120ppm or 120mg/l]. A local 

water  treatment  company  should  be  able  to  offer  free 

water quality testing. The heating elements may require 

periodic de-scaling. The installer should do this as part of 

a maintenance agreement.

- The cold water inlet pipework should have at least an 

  inside diameter of 19mm and should meet the

  requirements of the water regulations for the supply 

  of wholesome water.

Note: An alternative approach for sizing discharge pipes 

would be to follow Annex D, section D.2 of BS 6700:2006 

+ A1:2009).

- The cold water supply to the water heater must come 

  directly from the cold water mains after the mains 

  stop valve to the property.

This example is for a G½ temperature relief valve with 

a discharge pipe (D2) having 4 No. 22mm elbows and 

length of 7m from the tundish to the point of discharge.

The discharge pipe (D2) from the Tundish should:

“have a vertical section of pipe at least 300mm long 

   below the tundish before any elbows or bends in the 

   pipework and be installed with a continuous fall of at 

   least 1 in 200 thereafter.”

The following instructions have to be followed when 

installing the cold water mains supply to the water 

heater:

Minimum dynamic pressure

150Kpa (1.5 bar)

Maximum inlet supply pressure

1200Kpa (12 bar)

Minimum flow rate 

15l/min

Max. chlorine content

250mg/L

Max. water hardness

200mg/L

For satisfactory and safe performance of the water 

heater the water supply must meet the following 

criteria:

5.7  Cold Water Supply

The discharge pipe (D2) should be made of:

“metal; or other material that has been demonstrated   

   to be capable of safely withstanding temperatures of 

   the water discharged and is clearly and permanently 

   marked to identify the product and performance 

   standard”

From Table 2, the maximum resistance allowed for a 

straight length of 22mm copper discharge pipe (D2) from 

a G½ temperature relief valve is 9.0m. Subtract the re-

sistance for 4 No. 22mm elbows at 0.8m each = 3.2m.

Summary of Contents for EDL200UK-630RF

Page 1: ...Air Source Heat Pump Water Heater Installation and User Instructions RD01144 2 Important This manual must be left with user after Installation Edel RF...

Page 2: ...ture reference Installers are required to carry out installation commissioning and ser vicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hot Water I...

Page 3: ...Electrical Connections 11 6 9 1 1 Electricity Provider Contact 11 6 9 1 2 Connecting the PV Function 11 7 Set Up and Use 12 7 1 Commissioning 12 7 2 Using your Hot Water Heat Pump 13 7 3 Control Box 1...

Page 4: ...and or user This appliance can be used by children aged 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given s...

Page 5: ...installation If in any doubt please call the appropriate help desk Disregarding the instructions given in this manual in its entirety and any relevant regulations standards and codes of practice will...

Page 6: ...must be taken when placing the water heater in a garage or outbuilding All exposed pipework must be correctly insulated to avoid frost damage The position and orientation of the water heater should b...

Page 7: ...2 15 22 9 0 8 28 18 1 0 35 27 1 4 G3 4 22 28 9 1 0 35 18 1 4 42 27 1 7 G1 28 35 9 1 4 42 18 1 7 54 27 2 3 Dimplex recommend an annual maintenance inspection is carried out on the water heater In hard...

Page 8: ...on vessel membrane before filling the cylinder The pre charge should be greater than or equal to 3 bar 6 2 Cold Water Inlet with Inlet Group The discharge pipe should not be connected to a soil discha...

Page 9: ...dwellings occupied by people with impaired vision or mobility con sideration should be given to the installation of a suita ble safety device to warn when discharge takes place e g electronically oper...

Page 10: ...2 5 25 0 External terminal X 1 51 0 51 0 Total System Calculated Pressure Drop 320m3 hr 207 7 Pa 6 7 1 Worked Example The pressure drop information provided is for 160mm semi rigid Ubbink ducting othe...

Page 11: ...hoose load shedding level 1 the electrical back up is prevented from running If you choose load shedding level 0 both the electrical back up and the heat pump will be prevented from running see Sectio...

Page 12: ...ischarge and check after closing that valve is not dripping 9 Open expansion relief valve to ensure proper discharge and check after closing that valve is not dripping 10 Check all shower outlets toil...

Page 13: ...ature remains in the authorised 7 C to 35 C range Outside of this range electrical backup ensures that the domestic hot water is heated The domestic hot water temperature provided by the heat pump is...

Page 14: ...This function can be programmed to run between 1 and 99 days and is effective as soon as the number of days has been confirmed HOLIDAYS HOLI RETURN 8 Set number of days in standby mode Enter HOLIDAY...

Page 15: ...exisitng programme MONDAY Set Up and Use Frost PT Frost Protection Mode ECO Heat Pump Only Running CONF Heat Pump Only Running electrical back up if needed 7 10 Programming Heating time for the tank v...

Page 16: ...al until the screen displays Inst Menu Press the Clock and Menu buttons simultaneously Keep both buttons pressed down until the screen goes blank 7 11 1 PV Mode Setting Description Unit Range Factory...

Page 17: ...emperature reaches 43o C The heat pump will complete the remaining charge to set temperature 7 11 2 3 Minimum Temperature To C Min No To C Min 43 o c Select Mode Enter It is possible to allow the oper...

Page 18: ...f locking for accessing the menus In the Installer menu turn the dial to Locking LOCKING LOCKING NO Select No Enter NO Locking is not activated but manual locking is possible by pressing Menu for 3 se...

Page 19: ...ers The Counters menu shows the number of start ups from the heat pump and the electrical backup In the Installer menu turn the dial to Counters Counter No 1 Number of start ups from the heat pump Cou...

Page 20: ...heater and the thermostat 10 The immersion heater boss can also be used for access to view the internal components of the cyl inder 11 Re commission unit see chapter 7 1 8 2 Heat Pump Any work on the...

Page 21: ...ich would reduce the cross sectional area of the conductor 4 Ensured the conductors are tightly and securely connected to the controls or immersion heater 5 Ensured the bared conductors are correctly...

Page 22: ...higher than the volume in the tank The time period the appliance operates is not too short 12hrs minimum if connected to piping The water temperature is not set too low Condensates are not drain ing T...

Page 23: ...045 2 Expansion vessel fixing kit R00094 2 DN16 3 4 BSP x 1000 flex pipe R00095 1 1 2 BSP T P valve R00020 1 15 x 22 straight PE tundish R00047 1 Temp sensor 25 C 1243950 C3S PCB Controller 1244096 70...

Page 24: ...aintained continuously at the standard set temperature if no signal or control is connected to the external control switch OVER PRESS Heat pump pressure too high No water in tank Water is too hot 75 C...

Page 25: ...being in contact with a part which vibrates Replace expansion valve The compressor is not working and safety temperature is activated Weakness in compressor Replace compressor ERR 02 Incorrect temper...

Page 26: ...mation 9 1 Warranty Limits Please read the following statements carefully as it affects your warranty Please ensure that the installer has fully completed the Benchmark Checklist on the inside back pa...

Page 27: ...d Water supply being other than cold domestic water such as rainwater or water from a well or which has particularly hostile or abnormal properties which do not comply with the national rules and curr...

Page 28: ...28 B C D E A 152 Figure 11 Edel Air Source Water Heater Dimensions for reference only Technical Data and Product Fiche 10 Technical Data and Product Fiche Air Intake Air Discharge...

Page 29: ...d Product Fiche Cylinder is tested in accordance with EN12897 2006 GDC Group Ltd Edel Air Source Water Heater Product Fiche Reference EDL200UK 630RF EDL270UK 630RF Load Profile Primary M L Energy Rati...

Page 30: ...2 kW 240V Ventilation Air flow rate 320 to 400 m3 h Air temperature 7 C to 35 C Max air pipe length rigid piping 20m in total intake and rejection Condensates flow rate 0 3 L h Condensates drainage p...

Page 31: ...31 Power Supply Green Yellow Black Blue Brown Black Blue Blue Black Sensors Black Black Black Black Blue Black Blue Brown Black Brown Communication Bus Display 1 2 Red Fan B1244454 F HPS DV...

Page 32: ...Red Blue Blue Black Brown Blue Green Yellow Blue Black Blue Blue Red Red Blue HTS WTS HPS High Pressure Switch C25 Compressor Start Capacitor C2 Fan Capacitor C4 Valve F Fan DV Defrost Valve RE Immer...

Page 33: ...33 Notes...

Page 34: ...and pressure relief valve and expansion valve been fitted and discharge tested Yes No The tundish and discharge pipework have been connected and terminated to Part G of the Building Regulations Yes A...

Page 35: ...mments Signature SERVICE 3 Date Engineer Name Company Name Telephone Number Comments Signature SERVICE 4 Date Engineer Name Company Name Telephone Number Comments Signature SERVICE 5 Date Engineer Nam...

Page 36: ...plex reserve the right to revise products literature and guarantee terms without prior notice due to a policy of continuous improvement www KIWA co uk www HWA co uk To speak to customer services pleas...

Reviews: