Dimplex CXLS24 Installation Instructions Manual Download Page 3

7

.

 Fitting directly on the " oor. 

If the ! oor is carpeted then the carpet 

may be slit and underlay cut away to allow the feet to rest " rmly on the 
! oor. Carpet gripper must be locally removed so that the feet may rest in 
a level position.

8.

 Having decided on the method of standing the heater on the ! oor the 

position of the wall bracket should be marked on the wall.

9. Remove wall " xing bracket from heater by removing the screws and 
spacer bushes at each end. 

11. Solid Brick/High Density Block Walls. (

See step 12 if walls are of 

low density block) 

These must be drilled and plugged with the No. 10 size 

plastic inserts provided.  The correct size of drill (8mm) should be used and 
the hole should be drilled to a depth of 15mm greater than the length of the 
plastic insert, so that the " xing is made below the plaster layer.

12

Low Density Block Walls

. A specialised " xing, such as the Uni" x LB70. 

should be employed following closely the manufacture’s instructions.

Panelled Internal Walls. 

Here it is best to locate the studding and use 

No.10 size woodscrews. Where it is not possible to locate the studding 
use  type  M5  Rawlplug  INTERSETS  on  securely  fastened  plasterboard 
panelling. For other wall panel materials the wall panel manufacturer should 
be consulted for details of suitable wall " xing devices.

10.  Four " xing positions must be chosen for the 24N, three 
for the 18N and two for the 12N .  Mark the positions for 
the " xing holes - two at the extreme ends and the others 
spaced evenly between them.  Remove the bracket from 
the wall, drill the holes in the positions marked, and insert 
suitable " xings  detailed in Steps 11 and 12.  Secure the 
wall bracket to the wall.

Summary of Contents for CXLS24

Page 1: ...e heater Only heat resisting cable minimum rating T85 should be used If used in a bathroom the heater must be installed such that switches and other controls cannot be touched by a person in the bath...

Page 2: ...each end packaging piece Stand heater on its feet and remove all packaging pieces 5 Position heater against wall in intended nal position taking note of the minimum xing dimensions given below If tted...

Page 3: ...than the length of the plastic insert so that the xing is made below the plaster layer 12 Low Density Block Walls A specialised xing such as the Uni x LB70 should be employed following closely the ma...

Page 4: ...the following must be strictly adhered to a For skirtings higher than 100mm 4 it will be necessary to position the heater with the screws attached through the alternative xing slots to the front b Fo...

Page 5: ...l packing by sliding it up and off the elements taking care not to damage the insulation 23 Remove one element to allow access for the back row of bricks On the CXL24N CXLS24N remove the element to ri...

Page 6: ...n 20 are replaced securely 29 Replace the spacer nut washer and screw removed in 18 and reconnect the two quick connect terminals removed in 19 30 Connect the off peak supply to the storage terminal b...

Page 7: ...ircuit 900W 1450W 2000W Note if the heater is situated underneath a shelf or overhand up to 250mm high then the brown wire should remain in circuit 33 Holding the bottom edge if the front panel toward...

Page 8: ...AIR SENSING STAT Peak Circuit Diagram CXL24N CXLS24N BROWN BROWN CUT OUT MAUVE BLUE BLUE BLUE BROWN MAUVE BROWN CONVECTOR ELEMENT CONVECTOR ELEMENT ELEMENT SELECTOR BLOCK MAINS BLOCK L SWITCH NEON AI...

Reviews: