background image

EN-6

English

5.2

5.2 Connecting the Condensed 

Water Pipe

The condensed water hose is fed through the foil cladding at the
rear of the device. It should be routed so that the condensate
produced (during heat pump operation) can flow away freely.
There is a pressureless seal valve which must 

also be relocated

when shortening the condensed water hose (valve can be easily
removed and replaced into the hose). This valve is of special im-
portance if longer air hoses are fitted to the device or if a filter is
installed on the exhaust air side. The condensate should be
drained into a siphon (see maintenance information 7.1).

5.3 Electrical Connection

The hot-water heat pump is wired ready for use; power is sup-
plied via connection cables plugged into an earthed wall socket
(~230 V, 50 Hz). This socket has to remain accessible after in-
stallation.
To control external devices for the second heat generator (hot-
water heat pumps with internal heat exchanger only), a separate
cable has to be connected to the device via an available cable
union and be strain relieved. (For this electrical connection, the
hot-water heat pump plastic cover has to be removed.) The cable
must then be led through the available cable feedthrough pro-
vided, and guided through the partition. The electrical connection
terminal (X5 – 4/5/PE) with a floating contact to control (ON/OFF)
the external ancillary devices (pump, solenoid valve etc.) is lo-
cated on the rear of the partition in the device. 

External heating element control

It is possible to optionally control the heating element via an ex-
ternal switch (e.g. timer), in parallel to the “Heating Element”
switch on the hot-water heat pump operator panel. For this con-
nection, a floating contact on the external switchgear is required.
Furthermore, an additional cable (min. 2 x 1.0 mm

2

 / max. cable

outside diameter 10 mm) must be inserted into the device and at-
tached to connection 6 and 7 of terminal strip X5.

Hot-water heat pump with heat exchanger

Heat pump operation is blocked if the factory-mounted copper
bridge between pole terminals 8 and 9 is removed (see Section
6.2).

Hot-water heat pump without heat exchanger

6 Start-Up

6.1 Hot-Water System

ATTENTION!

Only operate hot-water heat pump when filled with water!

Hot-water system requirements

The following materials may be found in the consumer's hot-
water system:

Copper

Stainless steel

Brass

Plastic

Depending on the materials used in the hot-water system (cus-
tomer installation), material incompatibility may lead to corrosion
damage. This especially applies to zinc-plated and aluminous
materials. If there is a risk of water contamination during opera-
tion, the installation of a filter may be required.

Hot-water system start-up

All installations at the water circuit, air circuit, as well as all
electrical installations must have been performed correctly
and fully completed

Filling hot-water system via external connection.

De-aerate hot water system (open hot-water taps at the
highest extraction points until there are no more traces of
air).

Check entire hot-water system for leaks.

Supply voltage.

Switch on “Heat Pump” switch (see illustration).

The desired hot-water temperature is infinitely adjustable
(up to 60 °C) via the temperature control button (see illustra-
tion). A certain heat-up time should always be allowed for,
until the desired temperature level has been reached. 

X3

Internal wiring only

X5 (4 + 5) Connection terminal with floating contact for second 

heat generator

X5 (6 + 7) Connection for external heating element control (optional)
X5 (8 + 9) External release contact

;

3(

1

/

3(

1

;

/

Summary of Contents for BWP 30 H

Page 1: ...or Indoor Installation Pompe chaleur de production d eau chaude installation int rieure Montage und Gebrauchsanweisung Deutsch English Fran ais Instructions d installation et d utilisation Installatio...

Page 2: ......

Page 3: ...DE 4 3 3 Transport von Hand DE 4 4 Aufstellung DE 5 4 1 Aufstellungsort DE 5 4 2 Aufstellung DE 5 5 Montage DE 6 5 1 Anschluss der Wasserleitungen DE 6 5 2 Anschluss der Kondensatleitung DE 6 5 3 Ele...

Page 4: ...r mepumpe wurden die relevanten EG Richtlinien eingehal ten Siehe auch CE Konformit tserkl rung Der Sachkundige hat daf r zu sorgen dass vor Beginn von Instandhaltungs Instandsetzungsarbeiten an k lt...

Page 5: ...mpe ratur kann ber den eingestellten Sollwert steigen Notheizung Bei einer St rung der W rmepumpe kann durch den Heiz stab die Warmwasserversorgung aufrecht erhalten werden H here Wassertemperatur Ist...

Page 6: ...ten Maximaltemperatur des Heizstabreglers erw rmt Temperaturregler W rmepumpe Die Temperaturkontrolle im Warmwasserspeicher und die Rege lung f r den Verdichterbetrieb bernimmt der Temperaturregler Di...

Page 7: ...en freiblasende Aufstellung bei der Aufstellung der Warmwasser W rmepumpe erforderlich siehe Bild Die Verbin dung zur Warmwasser W rmepumpe erfolgt optional mit iso lierten Luftleitungen der NW 160 di...

Page 8: ...oder abluftseitig ein Filter vorgeschalten wurde Das Kon densat ist in einen Siphon abzuleiten siehe hierzu auch War tungshinweis unter 7 1 5 3 Elektrischer Anschluss Die Warmwasser W rmepumpe ist an...

Page 9: ...um Erreichen des gew hlten Tempera turniveaus ist immer eine entsprechende Aufladezeit erfor derlich 6 2 Bedienung der Warmwasser W rmepumpe Bedienblende Temperaturanzeige Der F hler des Thermometers...

Page 10: ...h des Elektroheizstabes Die werkseitig eingestellte Abschalttem peratur von 65 C kann durch den Fachmann ge ndert werden siehe Pkt 2 4 Schalter W rmetauscher nur bei Warmwasser W rmepumpen mit innerem...

Page 11: ...ge bzw turnusm ige Reinigen des Verdampfers ACHTUNG Verletzungsgefahr durch scharfkantige Lamellen Lamellen d rfen nicht deformiert oder besch digt werden Bei der etwaigen Verwendung von Luftfiltern s...

Page 12: ...ugesetzt sind Kondensat l uft nicht ab Wasser unter dem Ger t Bitte berpr fen Sie ob das Dichtlippenventil am Kondensatschlauchende verunrei nigt oder verstopft ist reinigen Sie es ggf das Ventil l ss...

Page 13: ...s 35 8 bis 35 4 3 Schalldruckpegel 2 dB A 2 in 1m Abstand bei Freiaufstellung ohne Ansaug und Ausblaskanal bzw ohne 90 Rohrbogen ausblasseitig 53 53 4 4 Luftstrom im W rmepumpenbetrieb m3 h 450 450 4...

Page 14: ...ne Teile und Ger te Anlagenm ngel die auf nicht vom Liefe rer bezogene Teile zur ckzuf hren sind fallen nicht unter den Garantieanspruch Sofern der Mangel nicht beseitigt werden kann oder die Nach bes...

Page 15: ...Lift Truck or Lift Truck Transport EN 4 3 3 Manual Transport EN 4 4 Set Up EN 5 4 1 Installation Location EN 5 4 2 Set Up EN 5 5 Installation EN 5 5 1 Connecting the Water Pipes EN 5 5 2 Connecting th...

Page 16: ...n of the hot water heat pump complies with all relevant EG directives see also CE decla ration of conformity The technician must ensure that the refrigerant is flushed adequately to allow maintenance...

Page 17: ...ment in antifreeze mode can exceed the set value Emergency heating The water supply is maintained by the electric heating ele ment if the heat pump is out of order Higher water temperature If the requ...

Page 18: ...the set maximum temperature of the heating element controller has been reached Heat pump temperature controller Temperature control in the water cylinder and the regulation for compressor operation i...

Page 19: ...nd is as far away from the unit s intake opening as possible Also observe the minimum clearances as shown in the illustration The hot water heat pump air connection stubs intake stub and outlet stub a...

Page 20: ...s con nection a floating contact on the external switchgear is required Furthermore an additional cable min 2 x 1 0 mm2 max cable outside diameter 10 mm must be inserted into the device and at tached...

Page 21: ...r water temperature 60 2 C is desired the Heating Element switch can be used to switch on the integrated 1 5 kW radiator If the Heating Element switch is in the I position the approx upper third of th...

Page 22: ...the hot water heat pump observe possible coasting of ventilator General information The hot water heat pump is virtually maintenance free A one off visual inspection for possible leakage in the water...

Page 23: ...ds 60 C The heat pump switches off prematurely set temperature has not been reached Please check whether ducts have been bent or their openings have been sealed or whether any air filters are heavily...

Page 24: ...o 35 4 3 Sound pressure level 2 dB A 2 At a distance of 1 m free standing installation without inlet and outlet ducting or without 90 pipe bends on the outlet side 53 53 4 4 Air flow during heating on...

Page 25: ...3 3 Transport manuel FR 5 4 Installation FR 5 4 1 Emplacement FR 5 4 2 Installation FR 5 5 Montage FR 6 5 1 Raccordement des conduites d eau FR 6 5 2 Raccordement de la conduite d coulement des conde...

Page 26: ...r eau chaude les normes CE aff rentes ont t respect es Voir galement la d claration de conformit CE La personne qualifi e doit s assurer que avant les travaux d entretien et de mise en tat sur les par...

Page 27: ...la temp rature de l air descend en dessous de 8 1 5 C hyst r se de 3 K la cartouche chauffante lectri que se met automatiquement en route et chauffe l eau tem p rature nominale la temp rature consigne...

Page 28: ...ctivation par ther mostat de temp rature de l air par la cartouche chauffante jusqu obtention de la temp rature consigne du r gulateur de temp rature de la pompe chaleur Pour limiter la dur e de ser v...

Page 29: ...t sans heurts de la pompe cha leur pour eau chaude et faciliter les travaux de maintenance et de remise en tat il convient lors de son installation de respec ter une distance min de 0 6 m autour de l...

Page 30: ...r l va cuation de l air Faire d boucher les condensats sur un siphon voir aussi Remarque de maintenance au point 7 1 5 3 Branchements lectriques La pompe chaleur pour eau chaude est pr c bl e et pr te...

Page 31: ...tionn soit atteint 6 2 Commande de la pompe chaleur pour eau chaude Tableau de commande Indicateur de temp rature Le capteur du thermom tre thermom tre analogique dis tance enregistre la temp rature d...

Page 32: ...dant du r gulateur de la pompe chaleur et n cessaire au fonctionnement de la car touche chauffante lectrique La temp rature de mise en arr t de 65 C r gl e en usine peut tre chang e par une personne q...

Page 33: ...s au minimum apr s la mise en service de la pompe chaleur La remplacer si n cessaire Le contr le lectrique est r alis au moyen d un amp rem tre adapt sans vider le ballon d eau Proc dure suivre 1 reti...

Page 34: ...pas de rem dier la d faillance veuillez vous adresser votre installateur ou votre service apr s vente 9 Mise hors service T ches accomplir mettre la pompe chaleur pour eau chaude hors tension Fermer c...

Page 35: ...e 8 et 35 entre 8 et 35 4 3 Niveau de pression sonore 2 dB A 2 1 m de distance pour un emplacement d pourvu de conduite d aspiration et d vacuation d air ou de coude 90 pour la ventilation 53 53 4 4 C...

Page 36: ...FR 12 Fran ais 11...

Page 37: ...Heat Exchanger Integration Diagram for Thermal Solar Installation Sch ma d int gration changeur therm installation solaire therm A IV 2 Stromlaufpl ne Circuit Diagrams Sch mas lectriques A V 2 1 Warm...

Page 38: ...orrosion 8 Temperaturregler WP HP temperature controller R gulateur de temp rature PC 9 Schutztemperaturbegrenzer Protection temperature limiter Limiteur de temp rature de protection 10 Temperaturregl...

Page 39: ...bei Warmwasser W rmepumpen ohne innerem W rmetauscher entfallen die Anschl sse f r den zweiten W rmeerzeuger d h kein Heizwasservor lauf und kein Heizwasserr cklauf No connections for second heat gene...

Page 40: ...HFN YDOYH ODSHW DQWL UHWRXU DKQ 7DS 5RELQHW 7KHUPRPHWHU 7KHUPRPHWHU 7KHUPRPqWUH YRP ROOHNWRU URP WKH FROOHFWRU HQ SURYHQDQFH GX FROOHFWHXU 6LFKHUKHLWVYHQWLO 6DIHW YDOYH 6RXSDSH GH VpFXULWp QWO IWXQJ H...

Page 41: ...ndix Annexes 2 1 2 Stromlaufpl ne Circuit Diagrams Sch mas lectriques 2 1 Warmwasser W rmepumpen mit innerem W rmetauscher Hot Water Heat Pumps with Internal Heat Exchanger Pompes chaleur pour eau cha...

Page 42: ...EO 3 3 EQ 0 0 1 3 9 3 EDU 3 1 7 75 67 7 6 6 7 JU Q JHOE UHHQ HOORZ YHUW MDXQH VFKZDU ODFN QRLU lUPHSXPSH HDW SXPS 3RPSH j FKDOHXU OHNWUR HL VWDE OHFWULF KHDWLQJ HOHPHQW DUWRXFKH FKDXIIDQWH pOHFWULTXH...

Page 43: ...Safety temperature limiter E1 Limiteur de temp rature de s curit E1 F3 Klixon M1 Klixon M1 Klixon M1 K1 Relais externe Pumpe Relay ext Pump Relais ext pompe K2 Anlaufrelais M1 Starting relay for M1 Re...

Page 44: ...tion Bezeichnung W rmepumpen Designation Heat pumps D signation Pompes chaleur Typ BWP 30H Type s BWP 30HLW Type s EG Richtlinien Niederspannungsrichtlinie 2006 96 EG EMV Richtlinie 2004 108 EG Druckg...

Page 45: ...www dimplex de A IX Anhang Appendix Annexes 3...

Page 46: ...A X Anhang Appendix Annexes 3...

Page 47: ...www dimplex de A XI Anhang Appendix Annexes 3...

Page 48: ...schland GmbH Gesch ftsbereich Dimplex Am Goldenen Feld 18 D 95326 Kulmbach Irrt mer und nderungen vorbehalten Subject to alterations and errors Sous r serve d erreurs et modifications 49 0 9221 709 56...

Reviews: