Components
Digitize Inc.
2-10
700226-0001 Rev. F 05/11
2.10
Dual EOL IDM
The
Dual EOL IDM Board
is basically two EOL IDM boards combined on one open printed
circuit board.
Each EOL module provides a direct interface between variable resistance inputs and the Q-
Mux controller. The module is used to monitor fire alarm and security devices. A 1.43K
Ohm EOL resistor is included with each of the two Q-EOL modules.
Photo and Diagram of a Dual EOL IDM Bd.
Digitize Part Number: 02-4033
Dimensions: 2.69 in. x 3.21in.; Open PCB. Mounting holes are 2.13” x 2.37”
Power Requirements: 15 VDC @ 20 milliamps max. if both EOL IDMs are used.
Operating Environment: Install in a dry, indoor environment.
Operating Temperature: 32°F-165°F
Operating Humidity: 0-95%, non-condensing
Approvals: ETL Approved
What is this?? See Section 9.