XTLplus Series Installation and Programming Guide | Digital Monitoring Products
54
COMPLIANCE
HOUSEHOLD BURGLAR-ALARM SYSTEM UNITS - ANSI/UL 1023
Bell Cutoff
The bell cutoff time cannot be less than 4 minutes.
Entry Delay
The maximum entry delay used must not be more than 45 seconds.
Exit Delay
The maximum exit delay used must not be more than 60 seconds.
Wireless External Contact
When used, the External Contact of 1101, 1102, or 1106 transmitters must be programmed Normally Closed.
Wireless Supervision Time
The Zone Information Supervision Time cannot be set to 0 (zero).
Wireless Audible Annunciation
The Wireless Audible option must be selected as
DAY
for residential applications.
Panel Location
Mount panel inside protected area.
Test Frequency
The Test Frequency option must be programmed to send a report at least once every 30 days.
CENTRAL STATION BURGLAR ALARM UNITS - ANSI/UL 1610
Supervision
Commercial Burglary is provided when the Check-in and Fail Time time is set to 3 minutes.
Remote Disarm
REMOTE DISARM
must be programmed as
NO
.
Central Station
MESSAGE TO TRANSMIT
programming for zones must not be set to local (
L
).
HOUSEHOLD FIRE WARNING SYSTEM - ANSI/UL 985 NFPA 72 SPECIFICATIONS
Bell Output Definition
The bell output of the Model XTLplus must be programmed to operate steady on burglary alarms and temporal
on fire alarms.
Household System
An alarm sounding device must be installed indoors so that it is clearly heard in all sleeping areas.
Wireless Supervision Time
The Zone Information Supervision Time must be 3 minutes for fire devices.
Wireless Fire Verification
When used, the Model 1161 and 1162 wireless smoke detectors must not be programmed as Fire Verification (FV)
zone type.
Battery Standby
For listed applications, the panel must have 24 Hour battery standby operation. The Model XTL+BAT3500
battery should be used for fire installations.
Test Frequency
The Test Frequency option must be programmed to send a report at least once every 30 days.