6
DEChub ONE
Mounting the Single-Slot Hub
The single-slot hub may be placed on a table top or mounted in a 19-inch
equipment rack. To use it on a table top, attach four self-sticking rubber foot pads
(provided) on the underside of the single-slot hub, placing two foot pads on the
DEChub ONE and two foot pads on the attached network module. To rack-
mount a single-slot hub, with the DEChub ONE power off, follow these steps:
1
Connect rack-mount brackets to single-slot hub.
Align the screw holes on each end
of the rack-mount brackets with
the holes on the DEChub ONE
and on the network module.
Attach the brackets using eight
#6-32 flat-head screws.
2
Position and secure the single-slot hub unit in the equipment rack.
Align the screw holes on the rack-mount brackets with the equipment rack
holes. Attach the rack-mount single-slot hub to the rack using four #10-32
screws and U-nuts.
3
Connect the cables to the single-slot hub.
Connect the AUI, OBM, and setup ports, as required. Refer to the cabling
sections for information on connecting the AUI port, OBM port, and setup port.
4
Provide strain relief for the cabling.
Use TyRaps or other suitable means to secure the cables to the rack along the
raceways. Avoid placing undue strain on the cable connectors – do not tighten
the TyRaps excessively or exceed the nominal bend radius of the cables.
5
Connect the power cord to the single-slot hub power connector and then
to an outlet on the rack or to a wall outlet.
The module begins self-testing as described in its installation manual.