Take off the door paying attention that already connected cables are not pulled out.
Pass the cable through the cable holder on the ironer left side.
Electric supply must be done connecting the cable to the terminals mounted on the ironer:
Ξ
: ground
L1, L2, L3: phase
N: neutral
As soon as the electric connection is made, check the suction fan correct working. In
case the suction fan are supplied with a 3-phase system, please check that the motor sense
of rotation is correct and that the direction is the one of the air exhaust. In case the motor fan
are turning in the wrong direction, please change round two supply phases.
In case the machine is gas heated, please check the correct position of phase and
neutral in case of 1 phase machines. The wrong connection cause the missing survey of the
ionization sensor.
Ironer must be connected to a efficient ground system: the manufacturer decline any responsibility in case
this connection would not be complying with rules on matter.
Before any maintenance operation cut the electric supply to the machine: for maintenance refer to the ironer
electric diagram available in the pocket on the side door.
WARNING! Even if the main switch is on “0”, cables before it have tension!
10.
GAS CONNECTION (only gas heated ironers)
Gas connection must be made by qualified technicians and in compliance with national and local rules in
force. Please check the supplied gas, it must correspond to the one indicated on the technical data labels
stuck on the machine back.
Please check the correct position of the regulation ring (if existing). After that, close the side panels if still
open, start the machine and test the pressure on the nozzle: use the following tables.