9100-127-2989-99 REV B
1501 Route 34 South, Farmingdale, NJ 07727
Tel: (732) 919-3119 Fax: (732) 751-5778 www.dialight.com
4
Wireless Occupancy Sensor Gen 2 Specifications
Description
Wide Angle and Narrow Long Range Wireless High Bay Occupancy
Sensors
Certification
UL916, CSA C22.2 NO.205
Power Input
2x “AA” Lithium Batteries 1.5V
Operating Temperature
Operating Temperature: -40°C to +60
°C
Estimated Battery Life
Up to 10 years
Radio Frequency
2.4Ghz
Sensing Area
Wide Angle 20’-30’ (minor – major motion range), 1250 sq ft, 120
°
Long Range
100’ (maximum range), 7600 sq ft (floor + distance
coverage), 10
°
coverage angle
Sensing Technology
Passive Infrared
Dimensions
5”D x 2.38”H
Weight
~8.8oz
Material
Housing: Grey Polycarbonate
Lens: High density polyethylene
IP Ratings
IP66
Green LED
Green LED flashes one time when motion is detected
Indicates battery voltage above 2.7 Volts.
Green LED flashes twice every 5 seconds while searching for a network
connection.
Red LED
A single red LED3 flash indicates motion detected
and low battery voltage below 2.7 Volts.
Reset Button
Resets the processor
LED On/Off Switch
Located on bottom of sensor board, it will turn the LED indicators ON or
OFF.
Leave Button
Push and hold for 5 seconds to force sensor to leave its gateway
Join Button
Push and hold for 5 seconds. Sensor will double blink while trying to join a
gateway, Sensor will stop blinking if it doesn’t join a gateway within 30
minutes.