Parameter
StrtPT
StopPT
RecPT
RecGra
Over-frequency Response
OFDMode ON <-
ARC ON
Tab. 11-4
Definition of Over-
frequency Response Parameters
Description
The Start frequency value for over-frequency response.
The Stop frequency value for over-frequency response.
StopPT 51.50 <<
StrtPT 50.50
This series inverter provides “over-frequency response” func�on.
Long pressing the “OFD Mode” to enter the “over-frequency response”
se�ng menu.
For example, StrtPT: 50.5Hz, StopPT:
51.5Hz, RecPT: 50.1Hz, when the grid
frequency increases beyond Start: 50.5Hz,
the inverter will linearly reduce the power
output with a gradient of 100% Pmax/Hz
un�l it reaches StopPT: 51.5Hz .
Rate of Power recovery(Percentage of active power)
In hysteresis mode, power is restored only when
it is below this frequency
50.0 50.1 50.2 50.3 50.4 50.5 50.6 50.7 50.8 50.9 51.0 51.1 51.2 51.3 51.4 51.5 51.6 51.7 51.8 51.9 52.0
Fig. 11-3
Frq-Watt Mode for Over-frequency Conditions
RecPT
StrtPT
StopPT
Rated
Output
Power(kW)
Grid Frequency(Hz)
OFDMode HYS <-
ARC ON
Range
45HZ-65HZ
45HZ-65HZ
45HZ-65HZ
[3,500] 0.01%Pmax/s
Hysteresis mode