50
-
"Q(U)" Mode Parameters Explanation
Pstart
0%-130% Rate out power
The QU mode starts when the active power
is greater than this value
The QU mode stops when the active power
is less than this value
Grid voltage limit at point (U1,Q1) on the
Q(U) mode curve
Grid voltage limit at point (U2,Q2) on the
Q(U) mode curve
Grid voltage limit at point (U3,Q3) on the
Q(U) mode curve
Grid voltage limit at point (U4,Q4) on the
Q(U) mode curve
Grid voltage limit at point (U5,Q5) on the
Q(U) mode curve
Grid voltage limit at point (U6,Q6) on the
Q(U) mode curve
Increase or decrease the time required for
the reactive power to reach the speci�ied
value of the curve.
Value of Q/Pn at point (U1,Q1) on the Q(U)
mode curve
Value of Q/Pn at point (U2,Q2) on the Q(U)
mode curve
Value of Q/Pn at point (U3,Q3) on the Q(U)
mode curve
Value of Q/Pn at point (U4,Q4) on the Q(U)
mode curve
Value of Q/Pn at point (U5,Q5) on the Q(U)
mode curve
Value of Q/Pn at point (U6,Q6) on the Q(U)
mode curve
0%-130% Rate out power
0-110% VRated
-60% -60% Q/Pn
0-110% VRated
-60% -60% Q/Pn
0-110% VRated
-60% -60% Q/Pn
0-110% VRated
-60% -60% Q/Pn
0-110% VRated
-60% -60% Q/Pn
0-110% VRated
0-1000s
-60% -60% Q/Pn
Pstop
Q1
Q2
Q3
V1
V2
V3
Q4
V4
Q5
V5
Q6
V6
RMpTime
Parameter
Range
Description