65
-
Model
Input Side
Max.DC Power(kW)
Max.DC Input Voltage(V)
Start-up DC Input Voltage(V)
MPPT Opera�ng Range(V)
Max.DC Input Current(A)
SUN-7K-G05
9.1
1000
13+13
SUN-8K-G05
10.4
SUN-10K-G05
13
SUN-12K-G05
15.6
Max. Short Circuit Current (A)
19.5+19.5
Number of MPPT/Strings per MPPT
2/1
12
DC Injec�on Current(mA)
Grid Frequency Range
Max.Efficiency
Euro Efficiency
>99%
MPPT Efficiency
Output Side
Efficiency
General Data
Rated Output Power(kW)
Max.Ac�ve Power(kW)
Rated AC Grid Voltage(V)
AC Grid Voltage Range(V)
Rated Grid Frequency(Hz)
Opera�ng Phase
Rated AC Grid Output Current(A)
Max.AC Output Current(A)
Output Power Factor
7
7.7
11.7/11.1A
<0.5%
47-52 or 57-62
(
op�onal
)
98.3%
97.5%
3L/N/PE 220/380V 230/400V
0.85Un-1.1Un(this may vary with grid standards)
50/60(Op�onal)
Three phase
8
8.8
13.3/12.8A
0.8 leading~0.8 lagging
<3%
10
11
16.7/15.9A
13.2
10.6/10.1A
12.1/11.6A
15.2/14.5A
18.2/17.4A
19.2
22.1
27.7
33.2
21.4
24.6
30.8
36.9
20/19.1A
Grid Current THD
330×457×185
330×457×205
Transformerless
Size(mm, W×H×D)
10
11
Weight(kg)
Topology
<1W(Night)
Internal consump�on
Opera�ng temperature
Ingress protec�on
IP65
<25 dB
Natural cooling
Max. opera�on al�tude
Cooling Concept
Noise Emission(Typical)
2000m
Grid Connec�on Standard
Opera�on surrounding humidity
0~100%
Sta�y EMC / Standard
Maximum output fault
current (a.c. A, peak )
Maximum output overcurrent
protec�on (a.c. A,peak)
0
MAX inverter backfeed current (A)
140
120~850
200~850
250V
-25 ~ 65
℃
,>45
℃
dera�ng
CEI 0-21,VDE-AR-N 4105,NRS 097,IEC 62116,IEC 61727,
G99,G98,VDE 0126-1-1,RD 1699,C10-11
IEC/EN 62109-1,IEC/EN 62109-2,
IEC/EN 61000-6-1,IEC/EN 61000-6-2,IEC/EN 61000-6-3,IEC/EN 61000-6-4
>20 Years
Designed Life�me