- 18 -
5.4 Max. over current protec�on device
In order to protect the inverter AC connec�on, it is recommended to install a circuit breaker to
prevent overcurrent. See table 5.3 below.
Rated output
voltage(V)
Inverter
Rated output
current(A)
Current for protection
device(A)
SUN-3K-G03
220/230
20
4.5/4.3A
SUN-4K-G03
220/230
20
SUN-5K-G03
220/230
20
SUN-6K-G03
220/230
6.1/5.8A
7.6/7.2A
9.1/8.7A
20
SUN-7K-G03
220/230
20
SUN-8K-G03
220/230
20
SUN-10K-G03
220/230
10.6/10.1A
12.1/11.6A
15.2/14.5A
20
SUN-12K-G03
220/230
18.2/17.4A
30
Table 5.3 Recommended current protector specifica�ons
5.5 Inverter monitoring connec�on
Inverter has the func�on of wireless remote monitoring. The inverter with Wi-Fi func�on is
equipped with Wi-Fi Plug to connect the inverter and network. Wi-Fi Plug's opera�on,
installa�on, Internet access, APP downloading and other processes are detailed in the
instruc�ons.
PC
Router
WIFI
GPRS
Web Server
Phone
Pic 5.12 Internet monitoring solu�on