We recommends installing battery modules in the
upper shelves first and
proceeding to the bottom.
▪
The battery can be mounted on a standard 19 inches cabinet or rack.
▪
Battery modules can be inserted into a rack frame according to the
customer battery configuration scheme.
5. Cable Connection
5.1 Single Battery Connection
▪
Before connect the cable with the inverter, the worker must confirm the output
switch of the inverter has been turn off, to prevent the risk of fire or electric
shock.
▪
Before connection, make sure to close the battery.
▪
Please follow the instructions to protect the module BMS against damage.
▪
DO NOT deviate from the sequence of steps below.
▪
Exercise extreme caution prevent the terminals from contacting anything except
their intended mounting points.
▪
Terminals and their connected wires have either positive or negative polarity
(Positive: +; Negative-). The polarity of a terminal or a wire connected to the
terminal is on the front of each module. Exercise extreme caution to prevent the
terminals and/or wires with opposite polarity from contacting with each other.
▪
The maximum voltage of the battery is no more than 60V, which is higher than
the safe voltage of 36V. Therefore, we still recommend that the battery terminals
or other exposed parts should not be directly touched during the installation.