Occupancy Sensor Device – EP 0x22, EP 0x28 and 0x29
Each end point contains a logic module that can be configured to control the occupancy sensor signal
base on the user defined settings for the temperature sensor input or the user defined settings for the
light sensor input.
The manufacture specific attributes in section 4.2.1.2 is used to configure the logic module.
The ZCL “Measurement and Sensing” cluster in this section is implemented as a server cluster. Refer
to ZigBee Cluster Library Specification.
4.2.1
Occupancy sensing - Cluster id 0x0406
The occupancy sensing cluster is described in ZigBee Cluster Library Specification section 4.8
4.2.1.1
Attribute
Id#
Name
type
range
Man
/Opt
Relevance and ref.
0x0000
Occupancy
8-bit Bitmap
0000000x
M
Reporting is supported
0x0001
Occupancy Sensor Type
8-bit
Enumeration
0x00 – 0xfe
M
Hard coded to PIR
sensor
0x0010
PIROccupiedTo
UnoccupiedDelay
Uint16
Type range
O
The time delay, in
seconds
, before the PIR
sensor changes to its
unoccupied.
0x0011
PIRUnoccupiedTo
OccupiedDelay
Uint16
Type range
O
The time delay, in
seconds
, before the PIR
sensor changes to its
occupied
0x0012
PIRUnoccupiedTo
OccupiedThreshold
Uint8
Type range
O
Specifies the
number
of
movement detection
events that must occur
before the PIR sensor
changes to its occupied
state.
Note: Default value for PIR occupied to unoccupied is 4 minutes
4.2.1.2
Manufacture Specific Attribute
Id#
Name
type
range
Man
/Opt
Relevance and ref.
0xFC00
ArmThreshold_
MinTemperature
Sint16
0x954d –
0x7ffe
M
Write/read is supported
0xFC01
ArmThreshold_
MaxTemperature
Sint16
0x954d –
0x7ffe
M
Write/read is supported
0xFC02
TargetLevel
Uint16
0x0002 –
0xfffd
M
Write/read is supported