4.2

 

Occupancy Sensor Device – EP 0x22, EP 0x28 and 0x29 

Each end point contains a logic module that can be configured to control the occupancy sensor signal 

base on the user defined settings for the temperature sensor input or the user defined settings for the 

light sensor input. 

 

The manufacture specific attributes in section 4.2.1.2 is used to configure the logic module.  

 

The ZCL “Measurement and Sensing” cluster in this section is implemented as a server cluster. Refer 

to ZigBee Cluster Library Specification. 

 

4.2.1

 

Occupancy sensing - Cluster id 0x0406 

The occupancy sensing cluster is described in ZigBee Cluster Library Specification section 4.8 

4.2.1.1

 

Attribute  

Id# 

Name 

type 

range 

Man 

/Opt 

Relevance and ref. 

0x0000 

Occupancy 

8-bit Bitmap 

0000000x 

Reporting is supported 

0x0001 

Occupancy Sensor Type 

8-bit 
Enumeration 

0x00 – 0xfe 

Hard coded to PIR 
sensor 

0x0010 

PIROccupiedTo 
UnoccupiedDelay 

Uint16 

Type range 

The time delay, in 

seconds

, before the PIR 

sensor changes to its 
unoccupied. 

0x0011 

PIRUnoccupiedTo 
OccupiedDelay 

Uint16 

Type range 

The time delay, in 

seconds

, before the PIR 

sensor changes to its 
occupied 

0x0012 

PIRUnoccupiedTo 
OccupiedThreshold 

Uint8 

Type range 

Specifies the 

number

 of 

movement detection 
events that must occur 
before the PIR sensor 
changes to its occupied 
state.

 

 
Note: Default value for PIR occupied to unoccupied is 4 minutes 

4.2.1.2

 

Manufacture Specific Attribute  

Id# 

Name 

type 

range 

Man 

/Opt 

Relevance and ref. 

0xFC00 

ArmThreshold_ 
MinTemperature 

Sint16 

0x954d – 
0x7ffe 

Write/read is supported 

0xFC01 

ArmThreshold_ 
MaxTemperature 

Sint16 

0x954d – 
0x7ffe 

Write/read is supported 

0xFC02 

TargetLevel

 

Uint16 

0x0002 – 
0xfffd 

Write/read is supported 

 
 

 

 

Summary of Contents for ZHOT101

Page 1: ...1 Technical Manual for ZHOT101 ZigBee Occupancy Temperature Light Sensor ...

Page 2: ...r in this manual Furthermore Develco Products reserves the right to alter the hardware software and or specifications detailed herein at any time without notice and Develco Products does not make any commitment to update the information contained herein All the trademarks listed herein are owned by their respective owners RoHS ...

Page 3: ...P 0x22 EP 0x28 and 0x29 8 4 3 Temperature Sensor Device EP 0x26 11 4 4 Light Sensor Device EP 0x27 12 5 MMI user guide 13 5 1 Push Button Menu 13 5 2 Action upon Push Button Release 13 5 3 Action on Power On 14 5 4 Join Device on a Network 14 5 5 Toggle Identify Mode 14 6 General network behaviour 15 6 1 Installation 15 6 2 Normal Keep alive 15 6 3 Low battery 16 7 ZigBee Home Automation Commissio...

Page 4: ...to any product to improve reliability without further notice Develco Products A S does not assume any liability arising out of the application or use of any product or circuit described herein neither does it convey any license under patent rights or the rights of third parties ...

Page 5: ...pancy sensor is PIR based sensing moving objects up to 6 meters from the sensor The off time is adjustable remotely via ZigBee The end point is configured as Home Automation profile Occupancy Sensor 2 1 2 Light The light sensor is a low accuracy sensor reporting light level The end point is configured as Home Automation profile Light Sensor 2 1 3 Temperature The temperature sensor measures tempera...

Page 6: ...26 Application profile Id 0x0104 Home Automation Application device Id 0x0302 3 4 Light Sensor End point number 0x27 Application profile Id 0x0104 Home Automation Application device Id 0x0106 3 5 Develco Utility Application profile Id 0xC0C9 Develco Products private profile Application device Id 0x0001 Private profile for internal Develco Products use only The DevUtil end point support a Develco p...

Page 7: ...range M 4 1 1 1 1 ManufacturerName Develco Products A S 4 1 1 1 2 ModelIdentifier ZHOT101 ZigBee Occupancy Temperature Light Sensor 4 1 2 Identify Cluster id 0x0003 4 1 2 1 Attribute Id Name type range Man Opt Relevance and ref 0x0000 IdentifyTime Uint16 Type range M 4 1 2 2 Commands The identify cluster has 2 commands as server Id Name Payload Man Opt Relevance and ref 0x00 Identify Uint16 Identi...

Page 8: ...ap 0000000x M Reporting is supported 0x0001 Occupancy Sensor Type 8 bit Enumeration 0x00 0xfe M Hard coded to PIR sensor 0x0010 PIROccupiedTo UnoccupiedDelay Uint16 Type range O The time delay in seconds before the PIR sensor changes to its unoccupied 0x0011 PIRUnoccupiedTo OccupiedDelay Uint16 Type range O The time delay in seconds before the PIR sensor changes to its occupied 0x0012 PIRUnoccupie...

Page 9: ...ained by using the standard occupancy sensor functionality Standard ZCL attributes Using the manufacture specific attributes in section 4 2 1 2 provide the user with an extra check before the air condition is turned on The installer can configure the ArmThreshold_MaxTemperature attribute to 25 degrees and when movements are detected in the room the relay only turns on the air condition when the te...

Page 10: ...e device is installed to obtain energy savings in an office controlling the light A ZigBee relay is installed to turn on the light when the occupancy sensor detects movements in the room This functionality can be obtained by using the standard occupancy sensor Standard functionality ZCL attributes Using the manufacture specific attributes in section 4 2 1 2 provide the user with an extra check bef...

Page 11: ... reported when a tamper event is trigger On state changes The attribute is sent every 2 minute until the OutOfService attribute is set to FALSE Note A ZCL binding has to be established before the tamper event can be send 4 3 Temperature Sensor Device EP 0x26 The ZCL Measurement and Sensing cluster in this section is implemented as a server cluster Refer to ZigBee Cluster Library Specification 4 3 ...

Page 12: ...redValue Uint16 MinValue to MaxValue M ZCL Reporting is hard coded to every 2 minutes 0x0001 MinMeasuredValue Uint16 0x0002 0xfffd M 0x0002 MaxMeasuredValue Uint16 0x0001 0xfffe M 0x0004 LightSensorType 8 bit Enumeration 0x00 0xff O 4 4 1 1 1 MinMeasuredValue The minimum Lux value supported by the device is 3 Lux Converting 3 Lux into min measured value 10000 LOG 3 1 4772 Min measured value in Hex...

Page 13: ... on the LED As illustrated in the figure the menu system allows for device specific modes e g Pair Devices for Devices such as relays and occupancy sensors 5 2 Action upon Push Button Release The number of blinks associated with a given mode entry is shown in the below table along with the associated action performed upon user button release As indicated if the user holds the button past the Reset...

Page 14: ...ower up For the first 30 seconds hereafter the device will be in Identify Mode 5 4 Join Device on a Network To allow a device to join a network one either has to power up a device that has not previously joined a network or push the button until the Reset To Factory default mode is indicated and subsequently release the button This will cause the device to reset to its factory default state and sc...

Page 15: ... leave network mode Network settings are stored in NV memory are after a power cycle the device re join the same network If the device has to join a new PAN coordinator the MMI menu supports a Reset To Factory Fresh Settings mode This will erase all current network information 6 2 Normal Keep alive The device is sending a keep alive message to the PAN coordinator every 15 minute to verify that the...

Page 16: ...tery voltage can be read from the power configuration cluster described in section 4 3 1 The attribute BatteryVoltage is measuring the battery voltage in units of 100mV There is no led indication for low battery on the PIR sensor itself ...

Page 17: ...sh Settings menu is reached continuous flash of LED and then release button Form Network Not Supported Allow Others To Join Network Not Supported Restore Factory Fresh Settings All devices Press and hold button until Reset To Factory Fresh Settings menu is reached continuous flash of LED and then release button Pair Devices Routers and End Devices Press and hold button until Pair Devices menu is r...

Page 18: ...wn left right Off time configurable 2 s 65 000 s 8 3 Light Resolution 3 to 70 000 Lux Common light source illuminance lux table Street Light 20 Dusk 1 to 100 Living Room 50 to 200 Office 200 to 600 Operating Room 5 k to 10 k Cloudy 2 k to 10 k hazy 25 k to 50 k Bright Sun 50 k to 100 Tolerance 10 000 lux 5 of the measurement and 5 Lux 10 000 lux 10 of the measurement and 5 Lux Reporting configurab...

Page 19: ...formation Technical support Please contact Develco Products for support products develcoproducts com Sales Please contact Develco Products for information on prices availability and lead time info develcoproducts com ...

Page 20: ...or existing metering solutions AMR for meter manufacturers Communication modules for integration in meters or appliances ZigBee Z Wave PLC GPRS GSM and others Data concentrators with back office communication GPRS SMS Internet Fiber PLC Home Automation BENEFITS Cheap and reliable metering Reduced energy consumption Optimized energy consumption peak level out Avoidance of blackouts Sale of extra se...

Reviews: