17.7.17
UNIGATE
®
fieldbus gateway UNIGATE
®
MB - EtherCAT
®
V. 1.4
53
Deutschmann Automation GmbH & Co. KG
Technical data
12.1.1 Interface data
The table below lists the technical data of the interfaces and ports on the device. The data has
been taken from the corresponding Standards.
Interface designation
EtherCAT
®
RS232-C
RS485/RS422
No. Physical interface
Ethernet 100 BaseT
RS232-C
RS485/RS422
1
Standard
DIN 66020
EIA Standard
2
Transmission mode
Symmetrical
asynchronous
serial
full-duplex
Difference signal
Asymmetrical
asynchronous
serial
full-duplex
Level
Symmetrical
asynchronous
serial
half-duplex
full-duplex at RS422
Difference signal
3
Transmission method
Multimaster CSMA/CD Master / slave
Master / slave
4
Number of users : - Transmitters
- Receiver
65535
65535
1
1
32
32
5
Cable length: - Maximum
- Baud rate-dependent
100 m
15 m
no
1200 m
93.75 kBd
1200 m
312 kBd
500 m
625 kBd
250 m
6
Bus topology
Line-, tree- or star
Point-to-point
Line
7
Data rate:
- Maximum
- Standard
100 Mbit/s
100 Mbit/s
120 kBit/s
2.4 k/B
4.8 k/B
9.6 kBit/s
19.2 kBit/s
38.4 kBit/s
625 kBaud
2.4 kBit/s
4.8 kBit/s
9.6 kBit/s
19.2 kBit/s
57.6 kB
312.5 kB
625 kB
8
Transmitter: - Load
- Maximum voltage
- Signal, unloaded
- Signal, loaded
100
3 ... 7 k
25 V
15 V
5 V
54
- 7 V ... 12 V
5 V
1.5 V
9
Receiver: - Input resistance
- Maximum input signal
- Sensitivity
100
3 ... 7
15 V
3 V
12
- 7 V ... 12 V
0.2 V
10
Transmit range (SPACE):
- Voltage level
- Logic level
+ 3 ... + 15 V
0
- 0.2 ... + 0.2 V
0
11
Transmit pause (MARK):
- Voltage level
- Logic level
- 3 ... –15 V
1
+ 1.5 ... +5 V
1
Table: Technical data of the interfaces at the module