![DEUTSCHMANN AUTOMATION UNIGATE CL - Powerlink Instruction Manual Download Page 34](http://html1.mh-extra.com/html/deutschmann-automation/unigate-cl-powerlink/unigate-cl-powerlink_instruction-manual_2488374034.webp)
Technical data
Deutschmann Automation GmbH & Co. KG
34
UNIGATE Fieldbus Gateway UNIGATE CL - Powerlink V. 1.8
17.6.10
15 Technical data
15.1 Device data
The technical data of the module is given in the table below.
Table: Technical data of the module
No. Parameter
Data
Explanations
1
Location
Switch cabinet
DIN-rail mounting
2
Enclosure
IP20
Protection against foreign
bodies and water to IEC 529
(DIN 40050)
4
Service life
10 years
5
Housing size
23 x 111 x 115 mm
(screw-plug-connector included)
23 x 100 x 115 mm
(screw-plug connector not included)
W x H x D
6
Installation position
Any
7
Weight
Approx. 130 g
8
Operating temperature
0ºC ... +55ºC
9
Storage/transport
temperature
-40 ºC ... +70 ºC
10
Atmospheric pressure
during operation
during transport
795 hPa ... 1080 hPa
660 hPa ... 1080 hPa
11
Installation altitude
2000 m
4000 m
Unrestricted
Restricted -
Ambient temperature
≤
40ºC
12
Relative humidity
Max. 80 %
No condensation,
no corrosive atmosphere
14
External
power supply
10..33 V DC
Standard power supply unit to
DIN 19240
15
Current consumption at 24
VDC
Typ. 120 mA
max 150 mA
17
Reverse voltage protection
Yes
But does not function!
18
Short-circuit protection
Yes
19
Overload protection
Poly-switch
Thermal fuse
20
Undervoltage detection
(USP)
≤
9 V DC
21
Emergency power supply
≥
5 ms
Device fully operable
Summary of Contents for UNIGATE CL - Powerlink