10
TABLE 1
Technical Specifications
Power, total (Kw)
10
15
18
20
23
20
23
27
Power, first stage (Kw)
5
10
9
10
13
10
13
15
Net capacity (BTU/h)
34 120
51 180
61 420
68 240
78 480
68 240
78 480
92 130
Heating temperature rise range (F)
1
40-50
45-60
50-75
55-75
60-80
55-75
60-80
60-80
ELECTRICAL SYSTEM
Volts - Hertz - Phase
Electrical element #1 (Kw)
5
5
4
5
4
5
4
5
Electrical element #2 (Kw)
5
5
5
5
5
5
5
5
Electrical element #3 (Kw)
5
4
5
4
5
4
5
Electrical element #4 (Kw)
5
5
5
5
5
4
Electrical element #5 (Kw)
5
5
4
Electrical element #6 (Kw)
4
Blower motor Consumption (Amp. Max.)
3.3
3.3
3.3
3.3
3.3
6.9
6.9
6.9
Heating Elements Consumption (Amp)
41
61
74
82
94
82
94
111
Total Consumption (Amp)
44.3
64.3
77.3
85.3
97.3
88.9
100.9
117.9
Circuit Amperage
(wire sizing)
2
55
80
97
107
122
111
126
147
Maximum size circuit breaker (Amp)
2
60
80
100
110
125
125
150
150
BLOWER DATA (factory adjusted to a staic pressure of 0.5" W.C.)
Blower speed at 0.50" W.C. static pressure
LOW
MED-LOW
MED-LOW
MED-HIGH MED-HIGH
MED-LOW
MED-LOW
MED-LOW
Blower speed at 0.20" W.C. static pressure
LOW
MED-LOW
MED-LOW
MED-LOW
MED-HIGH
MED-LOW
MED-LOW
MED-LOW
Motor (HP) / number of speeds
Nominal blower size (diam. X width)
GENERAL INFORMATION
Overall dimensions (width x depth x height)
Supply
Return
Filter quantity and size
Shipping weight
Maximum cooling capacity
RATINGS AND PERFORMANCE
5 tons
FEMxx-M2301CM-B
1/3 HP / 4 speeds
1 HP / 4 speeds
2 wires 240 - 60 - 1
10 x 8
48 Kg / 105 lbs
FEMxx-M2301DM-B
19" x 19"
12 x 10
2) Calculated on the basis of Norm C22.2 Nr. 236
1) Select a blower speed that will generate the specified temperature rise
20" x 20" x 36.5"
15" x 18"
3 tons
(1) 20" x 20"