14
Table 8: Airflow Data, Models with 1.0 HP variable speed (ECM) motors
SW1- HEAT
DIP switch position
HEAT INPUT
(USGPH)
CFM with
SW3-ADJ
DIP switch position A
CFM with
SW3-ADJ
DIP switch position B
CFM with
SW3-ADJ
DIP switch position C
A
(1=OFF, 2=OFF)
0.90
1450
1640
1235
B
(1=ON, 2=OFF)
1.10
1700
1920
1445
C
(1=OFF, 2=ON)
D
(1=ON, 2=ON)
SW2- COOL
DIP switch position
A/C size
(TON)
CFM with
SW3-ADJ
DIP switch position A
CFM with
SW3-ADJ
DIP switch position B
CFM with
SW3-ADJ
DIP switch position C
A
(1=OFF, 2=OFF)
5.0
1500
1650
1350
B
(1=ON, 2=OFF)
4.0
1200
1320
1080
C
(1=OFF, 2=ON)
3.5
1050
1155
945
D
(1=ON, 2=ON)
3.0
900
990
810
SW2- COOL
DIP switch position
A/C size
(TON)
CFM with
SW3-ADJ
DIP switch position A
CFM with
SW3-ADJ
DIP switch position B
CFM with
SW3-ADJ
DIP switch position C
A
(1=OFF, 2=OFF)
5.0
2000
2200
1800
B
(1=ON, 2=OFF)
4.0
1600
1760
1440
C
(1=OFF, 2=ON)
3.5
1400
1540
1260
D
(1=ON, 2=ON)
3.0
1200
1320
1080
SW4- DEALY
DIP switch position
HEAT INPUT
(USGPH)
PreRun
On-Delay
CFM
Level - Time
ShortRun
On-Delay
CFM
Level - Time
Off-Delay
CFM
Level - Time
A
(1=OFF, 2=OFF)
0.90
13% - 45 sec.
44% - 30 sec
38% - 3 min.
B
(1=ON, 2=OFF)
1.10
13% - 30 sec.
44% - 30 sec
38% - 3 min.
C
(1=OFF, 2=ON)
1.10
13% - 30 sec.
50% - 30 sec
38% - 3 min.
D
(1=ON, 2=ON)
No adjustment
required
A/C size
PreRun
On-Delay
CFM
Level - Time
ShortRun
On-Delay
CFM
Level - Time
Off-Delay
CFM
Level - Time
-
All
NO DELAY
NO DELAY
100% - 90 sec
DELAY PROFILE FOR OIL HEATING MODE
PreRun and ShortRun are the periods of time when the the blower starts at very low CFM to minimize the
distributon of cool air in the system and then runs up to normal speed.
Off Delay is the time required to cool down the heat exchanger with low CFMs, to minimize cool draft in the
air distribution system.
OIL HEATING MODE
24 VAC input (R) on W only
CONTINUOUS FAN
24 VAC input (R) on G only
COOLING OR HEAT PUMP HEATING MODE
24 VAC input (R) to G, Y/Y2 and O (for cooling)
In Cooling - Dehumidification mode, with no 24 VAC input to DH, the CFMs are reduced by 15%.
The CFMs shown are reduced by 20% if there is 24 VAC input to Y1 (first stage cooling mode)
Settings not used in this mode.
Setting not used in this application
DELAY PROFILE FOR COOLING OR HEAT PUMP HEATING MODE
Summary of Contents for AMT154SDMA
Page 16: ...16 Figure 7 Furnace Dimensions...
Page 17: ...17 Figure 8 Wiring Diagram 4 Speed Motor PSC...
Page 18: ...18 Figure 9 Wiring Diagram Variable Speed Motor ECM...
Page 19: ...19 Figure 10 Parts List With 4 Speed motor PSC B50095B...
Page 21: ...21 Figure 11 Parts List With variable speed motor ECM B50096C...