background image

 

 

4

 

 

 

2 INSTALLATION 

The unit is shipped with a burner and its controls. It requires a 
115VAC power supply to the control panel and thermostat 
hook-up as shown on the wiring diagram, one or more oil line 
connections, suitable ductwork and connection to a properly 
sized vent. 

All local and national code requirements governing the 
installation of oil burning equipment, wiring and the flue 
connection MUST be followed. Some of the codes that may 
apply are: 

CSA B139:

  

Installation code for oil burning equipment. 

ANSI/NFPA 31:

   Installation of oil burning equipment. 

ANSI/NFPA 90B:

  Warm air heating and air conditioning 

systems. 

ANSI/NFPA 211:

   Chimneys, Fireplaces, Vents and solid fuel 

burning appliances.

 

ANSI/NFPA 70:

   National Electrical Code.  

CSA C22.1 or 
CSA C22.10

Canadian Electrical Code. 

Only the latest issues of these codes may be used. 

2.1 

POSITIONING THE FURNACE 

WARNING 

Fire and explosion hazard. 

The furnace must be installed in a level position, never 
where it will slope toward the front. 

Do not store or use gasoline or any other flammable 
substances near the furnace. 

Non-observance of these instructions will potentially result 
in death, bodily injury and/or property damage. 

CAUTION 

This furnace is not watertight and is not designed for outdoor 
installation. It must be installed in such a manner as to protect 
its electrical components from water. Outdoor installation will 
lead to a hazardous electrical condition and to premature 
failure of the equipment.

 

The minimum clearances from combustible material for 
each of the positions are specified in Table 4. 

If the furnace is installed in a basement or on a dirt floor, in a 
crawl space for example, it is recommended to install the unit 
on a cement base 2.5 cm to 5.0 cm (1" to 2") thick. 

The unit must be installed in an area where the ambient and 
return air temperatures are above 15°C (60°F). In addition, the 
furnace should be installed as closely as possible to the vent, 
so that the connections are direct and kept to a minimum. The 
heater should also be located close to the centre of the air 
distribution system. 

2.1.1  Installation in an enclosure 

The unit can be installed in an enclosure such as a closet. 
However, 2 ventilation openings are required for combustion 
air. The openings should be located in front of the furnace 
approximately 15 cm (6") above the floor and 15 cm (6") below 
the ceiling. Figure 1 indicates the minimum dimensions 
required and the location of the openings. 

Figure 1:  Location and dimensions of ventilation air 

openings in a closet door 

 

2.2 ELECTRICAL 

SYSTEM 

CAUTION 

The exterior of the unit must have an uninterrupted ground 
to minimize the risk of bodily harm, if ever an electrical 
problem develops. A green ground screw is supplied with 
the control box for that purpose.

 

The appliance must be installed in accordance with the 
current ANSI/NFPA 70 National Electrical Code, CSA 
C22.1 Canadian Electrical Code Part 1 and/or local codes. 

The control system depends on the correct polarity of the 
power supply. Connect “HOT” wire (H) and “NEUTRAL” 
wire (N) as shown in Figures 3 and 4. 

A separate line voltage supply should be used, with fused 
disconnect switch or circuit breaker, between the main 
power panel and the unit. 

Only copper wire may be used for the 115V circuit on this 
unit. If wires need to be changed, the replacements must 
have the same temperature resistance as the originals. 

2.3 

INSTALLATION OF THE THERMOSTAT 

A thermostat must be installed to control the temperature 
of the area to be heated. Follow the instructions supplied 
with the thermostat. Also refer to the wiring diagrams 
provided with the heating/air conditioning unit. The 
connections must be made as indicated on the following 
diagrams and the wiring diagrams. 

Figure 2:  Heating & Air Conditioning - With 4 Speed 

Motor 

 

Summary of Contents for AMT154SDMA

Page 1: ...ke Qu bec www dettson ca Attention Do not tamper with the unit or its controls Call a qualified service technician INSTALLER SERVICE TECHNICIAN USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION...

Page 2: ...ply air Temperature Rise Test 10 3 3 8 Limit Control Check 10 3 3 9 Restart after burner failure 10 4 MAINTENANCE 10 4 1 CLEANING THE HEAT EXCHANGER 10 4 2 CLEANING THE BLOCKED VENT SHUT OFF DEVICE BV...

Page 3: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Page 4: ...re the ambient and return air temperatures are above 15 C 60 F In addition the furnace should be installed as closely as possible to the vent so that the connections are direct and kept to a minimum T...

Page 5: ...ired for Riello burners Refer to the burner control instruction manual and markings for proper adjustment of the post purge delay 2 5 VENTING WARNING Poisonous carbon monoxide gas hazard Never install...

Page 6: ...equate supply of combustion air It is common practice to assume that older homes have sufficient infiltration to accommodate the combustion air requirement for the furnace However home improvements su...

Page 7: ...ated the return air must be sealed and also be directed to the space other than where the furnace is located 2 9 1 Air filter A properly sized air filter must be installed on the return air side of th...

Page 8: ...heating or air conditioning mode This signal can be used to activate an electronic air cleaner that is not equipped with an air flow switch If the cleaner is equipped with an air flow switch the S te...

Page 9: ...of the oil piping and pump Slowly close and tighten the bleed screw Once closed the flame will light up 3 3 2 Pressure adjustment The oil pressure must be adjusted according to the Technical Specifica...

Page 10: ...burner should restart after a few minutes The time required for the restart also depends on the adjustment of the blower OFF delay 3 3 9 Restart after burner failure 1 Set the thermostat lower than r...

Page 11: ...uction inside the heat transfer tube 7 Re mount lock and fasten the control box with the 2 screws removed in step 4 8 Re attach the assembly cover with the screws removed in step 2 9 Re establish powe...

Page 12: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Page 13: ...n 87 5 86 2 87 5 86 2 Volts Hertz Phase Rated current Amps Minimum ampacity for wire sizing Amps Max fuse size Amps Control transformer VA External control power available Heating VA Cooling VA Heatin...

Page 14: ...Time ShortRun On Delay CFM Level Time Off Delay CFM Level Time A 1 OFF 2 OFF 0 90 13 45 sec 44 30 sec 38 3 min B 1 ON 2 OFF 1 10 13 30 sec 44 30 sec 38 3 min C 1 OFF 2 ON 1 10 13 30 sec 50 30 sec 38...

Page 15: ...WITH AIR FILTER Table 10 Minimum clearances from combustible material LOCATION APPLICATION CLEARANCES combustible materials RECOMMANDED ACCESS FOR SERVICE FURNACE 2 54 cm 1 0 6 m 24 SUPPLY PLENUM WIT...

Page 16: ...16 Figure 7 Furnace Dimensions...

Page 17: ...17 Figure 8 Wiring Diagram 4 Speed Motor PSC...

Page 18: ...18 Figure 9 Wiring Diagram Variable Speed Motor ECM...

Page 19: ...19 Figure 10 Parts List With 4 Speed motor PSC B50095B...

Page 20: ...TERIOR 33 F06F015 ZINC WASHER 1 7 16 34 Z99F061 SIGHT GLASS FOR HEAT EXCHANGER 35 Z06G001 BLOCKED VENT SHUT OFF BVSO 225 36 B03675 GASKET SMOKE OUTLET 37 B03765 CLEAN OUT ASSEMBLY Item 36 included 38...

Page 21: ...21 Figure 11 Parts List With variable speed motor ECM B50096C...

Page 22: ...ELECTRICAL BOX COVER Panel only 32 B03118 01 ELECTRICAL KIT BVSO EXTERIOR 33 F06F015 ZINC WASHER 1 7 16 34 Z99F061 SIGHT GLASS FOR HEAT EXCHANGER 35 Z06G001 BLOCKED VENT SHUT OFF BVSO 225 36 B03675 G...

Reviews: