background image

 

 

8

 

 

 

2.10.1  Supply air adjustment (ECM variable speed 

motors) 

On units equipped with ECM variable speed blower motors, 
the air supply must be adjusted based on heating/air 
conditioning output. The start/stop delays of the blower must 
also be adjusted by positioning the DIP switches on the 
electronic board. Refer to the following tables and the wiring 
diagram in this manual for the proper settings: 

Table 3:  Heating Mode 

SW1 – HEAT  

DIP Switch Positions 

1 2 

POSITION 

Input 

USGPH 

OFF OFF 

0.90 

ON OFF 

1.10 

OFF 

ON 

C* 

N / A 

ON 

ON 

D* 

N / A 

Table 4:  Air Conditioning Mode 

SW2 – COOL  

DIP Switch Positions 

1 2 

POSITION 

Output 

Tons 

OFF OFF 

5.0 

ON OFF 

4.0 

OFF ON 

3.5 

ON ON 

3.0 

Table 5:  CFM adjustment - All Modes 

SW3 – ADJ (Adjustment) 

DIP Switch Positions 

1 2 

POSITION 

CFM HTG.   

%  increase  

or decrease

 

CFM A/C  

%  increase  

or decrease

 

OFF OFF 

0% 

0% 

ON OFF 

+10% 

+10% 

OFF ON 

-10% 

-10% 

ON ON 

N/A 

0% 

Table 6:  Delay adjustments - Heating Mode 

SW4 – Delay 

DIP Switch Positions 

1 2 

POSITION 

Input 

USGPH 

OFF OFF 

0.90 

ON OFF 

1.10 

OFF ON 

1.10 

ON ON  D

*

 

N / A 

2.11 

INSTALLATION OF ACCESSORIES 

WARNING 

Electrical shock hazard. 
Turn OFF electrical power at the fuse box or service panel 
before making any electrical connections and ensure a 
proper ground connection is made before connecting line 
voltage. 
Failure to do so can result in death or bodily injury.

 

2.11.1 Humidifier (HUM) 

The 120 VAC HUM terminal on the electronic board of the 
blower is tied directly to terminal 8 of the 9-terminal connector 
of the electronic board. It supplies 120 VAC electric power 
when the burner is in operation. 

A 24 VAC signal can also be supplied from the W and C 
terminals on the blower electronic board to activate a switching 
relay. 

Also refer to the instructions supplied with the accessory. 

2.11.2  Electronic air Cleaner (EAC) 

The EAC terminal on the electronic board supplies 120 
VAC when the blower is operating in the heating or air 
conditioning mode. This signal can be used to activate an 
electronic air cleaner that is not equipped with an air flow 
switch. If the cleaner is equipped with an air flow switch, 
the “S” terminal on the electronic board can be used to 
provide a constant supply of 120 VAC. 

Also refer to the instructions supplied with the accessory. 

2.11.3  Air Conditioner (or Heat Pump) 

An air conditioning coil may be installed on the supply air 
side ONLY. 

WARNING 

Poisonous carbon monoxide gas hazard. 
Install the evaporator coil on the supply side of the 
furnace ducting ONLY. 
An evaporator coil installed on the return air side of 
the ducting can cause condensation to form inside 
the heat exchanger, resulting in heat exchanger 
failure. This in turn, can result in death, bodily injury 
and/or property damage. 

A clearance of 15 cm (6") is required between the bottom 
of the coil drain pan and the top of the heat exchanger. If 
a heat pump is installed, a “dual-energy” thermostat, or 
other control is recommended, in order to prevent the 
simultaneous operation of the furnace and the heat pump. 
It also prevents a direct transition from heating by way of 
the heat pump to heating with oil. Refer to the thermostat 
instructions or those of another control used for the proper 
wiring. 

If a coil blower compartment is used, install air tight, 
motorized and automatic air dampers. Cold air coming 
from the coil and passing across the furnace can cause 
condensation and shorten the life of the heat exchanger. 

2.11.4  Emergency Heating Mode – Variable 

Speed Motor (ECM) 

If the ECM blower motor is defect and that no spare are 
available right away, you can temporarily replace it with a 
conventional fractional PSC blower motor. Connect 
neutral wire to neutral terminal on the control panel of the 
machine and the hot line to the EAC terminal. This one is 
working as long as heating or cooling is requested, and 
the blower will work until a new ECM motor is installed. 

IMPORTANT

 

We recommend to use this mode only for a short period 
since it affects the efficiency of the unit and the user 
comfort. 

Summary of Contents for AMT154SDMA

Page 1: ...ke Qu bec www dettson ca Attention Do not tamper with the unit or its controls Call a qualified service technician INSTALLER SERVICE TECHNICIAN USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION...

Page 2: ...ply air Temperature Rise Test 10 3 3 8 Limit Control Check 10 3 3 9 Restart after burner failure 10 4 MAINTENANCE 10 4 1 CLEANING THE HEAT EXCHANGER 10 4 2 CLEANING THE BLOCKED VENT SHUT OFF DEVICE BV...

Page 3: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Page 4: ...re the ambient and return air temperatures are above 15 C 60 F In addition the furnace should be installed as closely as possible to the vent so that the connections are direct and kept to a minimum T...

Page 5: ...ired for Riello burners Refer to the burner control instruction manual and markings for proper adjustment of the post purge delay 2 5 VENTING WARNING Poisonous carbon monoxide gas hazard Never install...

Page 6: ...equate supply of combustion air It is common practice to assume that older homes have sufficient infiltration to accommodate the combustion air requirement for the furnace However home improvements su...

Page 7: ...ated the return air must be sealed and also be directed to the space other than where the furnace is located 2 9 1 Air filter A properly sized air filter must be installed on the return air side of th...

Page 8: ...heating or air conditioning mode This signal can be used to activate an electronic air cleaner that is not equipped with an air flow switch If the cleaner is equipped with an air flow switch the S te...

Page 9: ...of the oil piping and pump Slowly close and tighten the bleed screw Once closed the flame will light up 3 3 2 Pressure adjustment The oil pressure must be adjusted according to the Technical Specifica...

Page 10: ...burner should restart after a few minutes The time required for the restart also depends on the adjustment of the blower OFF delay 3 3 9 Restart after burner failure 1 Set the thermostat lower than r...

Page 11: ...uction inside the heat transfer tube 7 Re mount lock and fasten the control box with the 2 screws removed in step 4 8 Re attach the assembly cover with the screws removed in step 2 9 Re establish powe...

Page 12: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Page 13: ...n 87 5 86 2 87 5 86 2 Volts Hertz Phase Rated current Amps Minimum ampacity for wire sizing Amps Max fuse size Amps Control transformer VA External control power available Heating VA Cooling VA Heatin...

Page 14: ...Time ShortRun On Delay CFM Level Time Off Delay CFM Level Time A 1 OFF 2 OFF 0 90 13 45 sec 44 30 sec 38 3 min B 1 ON 2 OFF 1 10 13 30 sec 44 30 sec 38 3 min C 1 OFF 2 ON 1 10 13 30 sec 50 30 sec 38...

Page 15: ...WITH AIR FILTER Table 10 Minimum clearances from combustible material LOCATION APPLICATION CLEARANCES combustible materials RECOMMANDED ACCESS FOR SERVICE FURNACE 2 54 cm 1 0 6 m 24 SUPPLY PLENUM WIT...

Page 16: ...16 Figure 7 Furnace Dimensions...

Page 17: ...17 Figure 8 Wiring Diagram 4 Speed Motor PSC...

Page 18: ...18 Figure 9 Wiring Diagram Variable Speed Motor ECM...

Page 19: ...19 Figure 10 Parts List With 4 Speed motor PSC B50095B...

Page 20: ...TERIOR 33 F06F015 ZINC WASHER 1 7 16 34 Z99F061 SIGHT GLASS FOR HEAT EXCHANGER 35 Z06G001 BLOCKED VENT SHUT OFF BVSO 225 36 B03675 GASKET SMOKE OUTLET 37 B03765 CLEAN OUT ASSEMBLY Item 36 included 38...

Page 21: ...21 Figure 11 Parts List With variable speed motor ECM B50096C...

Page 22: ...ELECTRICAL BOX COVER Panel only 32 B03118 01 ELECTRICAL KIT BVSO EXTERIOR 33 F06F015 ZINC WASHER 1 7 16 34 Z99F061 SIGHT GLASS FOR HEAT EXCHANGER 35 Z06G001 BLOCKED VENT SHUT OFF BVSO 225 36 B03675 G...

Reviews: