4
WARNING
Electrical shock hazard.
This furnace is not watertight and is not designed
for outdoor installation. This furnace shall be
installed in such a manner as to protect the
electrical components from water.
Outdoor installation would lead to a hazardous
electrical
condition and to premature furnace
failure, property damage, bodily injury or death.
1.4)
VENTING
WARNING
Poisonous carbon monoxide gas, fire as well as
explosion hazard.
Read and follow all instructions in this section.
Failure to properly vent this furnace can result in
property damage, personal injury and/or death.
CAUTION
When the furnace (chimney installation) is vented
together with other combustion appliances such as a
water heater, the allowable venting materials (“L”-Vent
etc.) for use with those appliances must be investigated.
WARNING
Poisonous carbon monoxide gas hazard.
Never install a hand operated damper in the vent
pipe. However, any Underwriters Laboratories listed
electrically operated automatic type vent damper
may be installed if desired. Be sure to follow
instructions provided with vent damper. Read and
follow all instructions in this section.
Failure to properly vent this furnace or other
appliances can result in property damage, personal
injury and/or death.
Venting of the furnace should be to the outside and in accordance
with local codes and other authorities having jurisdiction.
OIL FIRED APPLIANCES SHALL BE CONNECTED TO FLUES
HAVING SUFFICIENT DRAFT AT ALL TIMES TO ENSURE SAFE
AND PROPER OPERATION OF THE APPLIANCE.
For additional venting information refer to ANSI/NFPA 211
Chimneys, Fireplaces, Vents and Solid Fuel Burning Appliances
and/or CSA B139 Installation Code.
This furnace is certified for use with Type “L” vent (maximum flue
gas temperature 575
o
F (302
o
C)). The flue pipe clearance knockout
in the front top or side panel should be removed. Install the flue
elbow so that it exits the furnace cabinet through that opening.
Pre-installation vent system inspection:
Before this furnace is installed, it is highly recommended that any
existing vent system be completely inspected.
For any chimney or vent, this should include the following:
a.
Inspection for any deterioration in the chimney or vent. If
deterioration is discovered, the chimney must be repaired or
the vent must be replaced;
b.
Inspection to ascertain that the vent system is clear and free of
obstructions. Any blockages must be removed before installing
this furnace;
c.
Cleaning the chimney or vent if previously used for venting a
solid fuel burning appliance or fireplace;
d.
Confirming that all unused chimney or vent connections are
properly sealed;
e.
Verification that the chimney is properly lined and sized per the
applicable codes. (Refer to list of codes on page 4.)
Masonry Chimney
This furnace can be vented into an existing masonry chimney. This
furnace must not be vented into a chimney servicing a solid fuel-
burning appliance. Before venting this furnace into a chimney, the
chimney must be checked for deterioration and repaired if
necessary. The chimney must be properly lined and sized per local
or national codes.
If the furnace is vented into a common chimney, the chimney must
be of sufficient area to accommodate the total flue products of all
appliances vented into the chimney.
The following requirements are provided to ensure a safe venting
system :
a.
Ensure that the chimney flue is clear of any dirt or debris;
b.
Ensure that the chimney is not servicing an open fireplace;
c.
Never reduce the pipe size below the outlet size of the furnace;
d.
All pipes should be supported using the proper clamps and/or
straps. These supports should be at least every 4 feet;
e.
All horizontal runs of pipe should have at least a ¼ inch per
foot of upward slope;
f.
All runs of pipe should be as short as possible, with as few
turns as possible;
g.
Seams should be tightly joined and checked for leaks;
h.
The flue pipe must not extend into the chimney but be flush
with the inside wall;
i.
The chimney must extend 3 feet above the highest point where
it passes through a roof of a building and at least 2 feet higher
than any portion of a building within a horizontal distance of 10
feet. It shall also be extended at lest 5 feet above the highest
connected equipment flue collar;
j.
Check local codes for any variances.
Factory Built Chimneys
This furnace may be used with an approved factory built chimney.
Refer to chimney manufacturer’s instructions for proper installation
1.4.1) Barometric draft control
The barometric draft control shipped with the furnace MUST be used
to ensure proper operation. Installation instructions are enclosed with
the control.