For  continued  safe  operation,  the  Blocked  Vent  Shut-Off  System 
(BVSO)  is  required  to  be  inspected  and  maintained  annually  by  a 
qualified agency. 

1. 

Disconnect power to the appliance

2. 

Remove the two screws holding on the BVSO assembly cover; 

3. 

Remove the cover; 

4. 

Remove  the  two  screws  holding  the  control  box  to  the  heat 
transfer tube assembly. Sliding the control box in the appropriate 
direction will unlock it from the heat transfer tube assembly; 

5. 

Carefully remove any build-up from the thermal switch surface; 

6. 

Clear  and  remove  any  build-up  or  obstruction  inside  the  heat 
transfer tube; 

7. 

Re-mount,  lock  and  fasten  the  control  box  with  the  2  screws 
removed in step 4; 

8. 

Re-attach  the  assembly  cover  with  the  screws  removed  in   
step 2; 

9. 

Re-establish power to the appliance. 

 
 
 
 
 
 

 

PART 4 

INFORMATION 

 
 

 
 
 
Model: 

 

 
Serial number: 

 

 
Furnace installation date: 

 

 
Service telephone – Day: 

 

 
Night: 

 

 
Dealer name and address: 

 

 
 
 
 
 
 
 

START-UP TEST RESULTS  

 

 

 
Nozzle: 

 

 
Pressure: 

 

 
Lb/psi 

 
Burner adjustments: 

 
Primary air 

 

 

 
Fine air 

 

 

 
Draw Assembly 

 
 

 
CO

2

 

 
%                         Smoke scale : 

 

 
(Bacharach) 

 
 
Gross stack temperature: 

 

 
 
° F 

 
 
Ambient temperature: 

 

 
 
° F 

 
 
Chimney draft: 

 

 
 
" W.C. 

 
 
Overfire draft: 

 

 
 
" W.C. 

 
 
Test performed by: 

 

 

Summary of Contents for AMP300B34-SE2PM

Page 1: ...on in this manual for the installation servicing of the furnace and keep the document near the unit for future reference HOMEOWNER Please keep this manual near the furnace for future reference Caution...

Page 2: ...this manual can result in furnace malfunction property damage personal injury and or death WARNING Fire hazard The furnace must be installed in a level position never where it will slope toward the fr...

Page 3: ...n the water lines if possible Open faucets in appropriate areas b Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes from freezing Contact...

Page 4: ...ioration is discovered the chimney must be repaired or the vent must be replaced b Inspection to ascertain that the vent system is clear and free of obstructions Any blockages must be removed before i...

Page 5: ...ts and glues l Antistatic fabric softeners for clothes dryers m Acid based masonry cleaning materials 1 6 OIL TANKS AND LINES Check your local codes for the installation of the tank and accessories A...

Page 6: ...safety device must be installed between the flue outlet of the appliance and the draft regulator as indicated in the instructions It is further imperative that the BVSO be maintained annually For mor...

Page 7: ...time the burner motor ignition coil produces a spark 3 Spark ignites oil droplets 4 Cad cell senses flame and burner continues to fire Ignition transformer ceases sparking R40 F 5 After Fan Limit con...

Page 8: ...WER OFF DELAY BOARD ST9103A BLOWER ON DELAY BOARD 1158 2 2 5 Vent temperature test 1 Place a thermometer into the test hole located in the breech pipe 2 The vent temperature should be between 400 and...

Page 9: ...peration Soot will have collected in the first sections of the heat exchangers only if the burner was started after the combustion chamber was flooded with fuel oil or if the burner has been operating...

Page 10: ...remove any build up from the thermal switch surface 6 Clear and remove any build up or obstruction inside the heat transfer tube 7 Re mount lock and fasten the control box with the 2 screws removed i...

Page 11: ...TABLE 2 Technical specifications AMP300B34 SE2PMA OTF210G21B TABLE 2 1 Air delivery CFM with air filter AFUE value established after minimum 20 hours of operation 11...

Page 12: ...FIGURE 3 Model AMP300B34 SE2PMA OTF210G21B DNS 0822 Rev B TABLE 2 2 Minimum clearances combustible materials 12...

Page 13: ...FIGURE 4 Wiring diagram AMP300B34 SE2PMA OTF210G21B 13...

Page 14: ...14 PARTS LIST Model AMP300B34 SE2PMA OTF210G21B B50046A...

Page 15: ...15 PARTS LIST Model AMP300B34 SE2PMA OTF210G21B8...

Reviews: